2305.5 Hold-down connectors.
Whittier Municipal Code · 2026-09 edition · updated 2026-09-27 · Whittier
In Seismic Design Category D, E or F, hold-down connectors shall be designed to resist
shear wall overturning moments using approved cyclic load values or 75 percent of the allowable seismic load values that do not consider cyclic loading of the product. Connector bolts into wood framing shall require steel plate washers on the post on the opposite side of the anchorage device. Plate size shall be a minimum of 0.229 inch by 3 inches by 3 inches (5.82 mm by 76 mm by 76 mm) in size. Hold-down connectors shall be tightened to finger tight plus one half (1/2) wrench turn left prior to covering the wall framing.
(Ord. No. 3143, § 4, 12-13-22)