Chapter 6 — WATER SUPPLY AND DISTRIBUTION
612.7 Inspection and Testing.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
The inspection and testing of sprinkler systems shall be in accordance with Section 612.7.1 and Section 612.7.2. 612.7.1 Pre-Concealment Inspection. The following shall be verified prior to the concealment of any sprinkler system piping: (1) Sprinklers are installed in all areas in accordance
with Section 612.3.1.
(1) Sprinklers are installed in all areas in accordance
with Section 612.3.1. (2) Where sprinkler water spray patterns are obstructed
by construction features, luminaires or ceiling fans,
2019 CALIFORNIA PLUMBING CODE 163
WATER SUPPLY AND DISTRIBUTION any other purpose or distributed to any other persons or parti es.
(3) Sprinklers are the correct temperature rating and are
installed at or beyond the required separation dis
(3) Sprinklers are the correct temperature rating and are
installed at or beyond the required separation distances from heat sources in accordance with Section 612.3.3 and Section 612.3.3.1. (4) The minimum pipe size in accordance with the
requirements of Table 612.5.3.2(4) through Table
(4) The minimum pipe size in accordance with the
requirements of Table 612.5.3.2(4) through Table 612.5.3.2(9) or, where the piping system was hydraulically calculated in accordance with Section 612.5.3.1, the size used in the hydraulic calculation. (5) The pipe length does not exceed the length permit ted by Table 612.5.3.2(4) through Table 612.5.3.2(9)
(5) The pipe length does not exceed the length permit ted by Table 612.5.3.2(4) through Table 612.5.3.2(9) or, where the piping system was hydraulically calculated in accordance with Section 612.5.3.1, pipe lengths and fittings shall not exceed those used in the hydraulic calculation. (6) Nonmetallic piping that conveys water to sprinklers
is certified as having a pressure rating of not less
(6) Nonmetallic piping that conveys water to sprinklers
is certified as having a pressure rating of not less than 130 psi (896 kPa) at 120°F (49°C). (7) Piping is properly supported. (8) The piping system is tested in accordance with Sec tion 609.4.
(8) The piping system is tested in accordance with Sec tion 609.4. 612.7.2 Final Inspection. Upon completion of the residential sprinkler system, the system shall be inspected. The following shall be verified during the final inspection: (1) Sprinklers are not painted, damaged, or otherwise
hindered from the operation.
(1) Sprinklers are not painted, damaged, or otherwise
hindered from the operation. (2) Where a pump is required to provide water to the
system, the pump starts automatically upon system
(2) Where a pump is required to provide water to the
system, the pump starts automatically upon system water demand. (3) Pressure reducing valves, water softeners, water fil ters, or other impairments to water flow that were
(3) Pressure reducing valves, water softeners, water fil ters, or other impairments to water flow that were not part of the original design has not been installed. (4) The sign or valve tag in accordance with Section
612.6 is installed, and the owner’s manual for the
The sign or valve tag in accordance with Section
612.6 is installed, and the owner’s manual for the system is present.
TABLE 612.5.3.2(3) ELEVATION LOSS (PLe)
| ELEVATION (feet) | PRESSURE LOSS (psi) |
|---|---|
164 2019 CALIFORNIA PLUMBING CODE
WATER SUPPLY AND DISTRIBUTION
TABLE 612.5.3.2(4) ALLOWABLE PIPE LENGTH FOR 3 ⁄4 INCH TYPE M COPPER WATER TUBING*
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
AVAILABLE PRESSURE - Pt (psi) | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
- NP – Means not permitted.
2019 CALIFORNIA PLUMBING CODE 165
WATER SUPPLY AND DISTRIBUTION any other purpose or distributed to any other persons or parti es.
TABLE 612.5.3.2(5) ALLOWABLE PIPE LENGTH FOR 1 INCH TYPE M COPPER WATER TUBING
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
AVAILABLE PRESSURE - Pt (psi) | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
166 2019 CALIFORNIA PLUMBING CODE
WATER SUPPLY AND DISTRIBUTION
| TABLE 612.5.3.2(6) ALLOWABLE PIPE LENGTH FOR 3⁄4 INCH IPS CPVC PIPE | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
2019 CALIFORNIA PLUMBING CODE 167
WATER SUPPLY AND DISTRIBUTION any other purpose or distributed to any other persons or parti es.
| TABLE 612.5.3.2(7) ALLOWABLE PIPE LENGTH FOR 1 INCH IPS CPVC PIPE | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
168 2019 CALIFORNIA PLUMBING CODE
WATER SUPPLY AND DISTRIBUTION
| TABLE 612.5.3.2(8) ALLOWABLE PIPE LENGTH FOR 3⁄4 INCH PEX TUBING* | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
- NP – Means not permitted.
2019 CALIFORNIA PLUMBING CODE 169
WATER SUPPLY AND DISTRIBUTION any other purpose or distributed to any other persons or parti es.
| TABLE 612.5.3.2(9) ALLOWABLE PIPE LENGTH FOR 1 INCH PEX TUBING | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) | AVAILABLE PRESSURE - Pt (psi) |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
| SPRINKLER FLOW RATE (gpm) |
WATER DISTRIBUTION SIZE (inch) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
ALLOWABLE LENGTH OF PIPE FROM SERVICE VALVE TO FARTHEST SPRINKLER (feet) |
170 2019 CALIFORNIA PLUMBING CODE
WATER SUPPLY AND DISTRIBUTION
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
▸Chapter 6 — WATER SUPPLY AND DISTRIBUTION
Overview- 601.2 Hot and Cold Water Required. Except where not
- 601.3 Identification of a Potable and NonpotableWater System. …
- 601.5 [AGR] Meat and Poultry Processing Plants. Except as prov…
- 601.4 [CA] Schools of Cosmetology and Cosmeto-
- 601.6 [AGR] Collection Centers and Facilities.601.6.1 The wate…
- 601.7 [AGR] Renderers. This area shall be provided with
- 601.8 [AGR] Horse Meat and Pet Food Establishments.601.8.1 The…
- 602.3 Backflow Prevention. No plumbing fixture, device,
- 602.4 Approval by Authority. No water piping supplied
- 603.0 Cross-Connection Control.603.1 General. Cross-connection…
- 603.2 Approval of Devices or Assemblies. Before a
- 602.0 Unlawful Connections.602.1 Prohibited Installation. No i…
- 602.2 Cross-Contamination. No person shall make a connection o…
- 603.3 Backflow Prevention Devices, Assemblies, andMethods. Bac…
- 603.4 General Requirements. Assemblies shall comply
- 603.5 Specific Requirements. Specific requirements for
- 604.0 Materials.604.1 Pipe, Tube, and Fittings. Pipe, tube, fi…
- 604.2 Lead Content. The maximum allowable lead content in pipe…
- 604.3 Copper or Copper Alloy Tube. Copper or copper
- 604.4 Hard-Drawn Copper or Copper Alloy Tubing. Hard-drawn cop…
- 604.5 Flexible Connectors. Flexible water connectors
- 604.6 Cast-Iron Fittings. Cast-iron fittings up to and
- 604.7 Malleable Iron Fittings. Malleable iron water fittings s…
- 604.8 Previously Used Piping and Tubing. Piping and
- 604.9 Epoxy Coating. The epoxy coating used on existing, under…
- 604.10 Plastic Materials. Approved plastic materials shall
- 605.0 Joints and Connections.
- 604.11 Solder. Solder shall comply with the requirements of
- 604.12 Flexible Corrugated Connectors. Flexible corrugated con…
- 604.13 Water Heater Connectors. Flexible metallic (copper and …
- 605.2 CPVC Plastic Pipe and Joints. CPVC plastic pipe
- 605.3 CPVC/AL/CPVC Plastic Pipe and Joints. Chlorinated polyvi…
- 605.4 Ductile Iron Pipe and Joints. Ductile iron pipe
- 605.5 Galvanized Steel Pipe and Joints. Galvanized
- 605.6 PE Plastic Pipe/Tubing and Joints. PE plastic
- 605.7 PE-AL-PE Plastic Pipe/Tubing and Joints. PEAL-PE plastic…
- 605.8 PE-RT. Polyethylene of raised temperature (PE-RT)
- 605.9 PEX Plastic Tubing and Joints. PEX plastic tubing and fi…
- 605.11 Polypropylene (PP) Piping and Joints. PP pipe
- 605.10 PEX-AL-PEX Plastic Tubing and Joints. PEXAL-PEX plastic…
- 605.12 PVC Plastic Pipe and Joints. PVC plastic pipe
- 605.13 Stainless Steel Pipe and Joints. Joining methods for st…
- 605.14 Slip Joints. In water piping, slip joints shall be perm…
- 605.15 Dielectric Unions. Dielectric unions where
- 605.16 Joints Between Various Materials. Joints
- 606.0 Valves.606.1 General. Valves up to and including 2 inche…
- 606.2 Fullway Valve. A fullway valve controlling outlets
- 606.3 Multidwelling Units. In multidwelling units, one or
- 606.4 Multiple Openings. Valves used to control two or
- 606.5 Control Valve. A control valve shall be installed
- 606.6 Accessible. Required shutoff or control valves shall
- 606.7 Multiple Fixtures. A single control valve shall be
- 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5] Each riser or branch
- 607.2 Potable Water Tanks. Potable water supply tanks,
- 607.3 Venting. Tanks used for potable water shall be tightly
- 607.4 Overflow. Tanks shall have not less than a 16 square
- 607.5 Valves. Pressurized tanks shall be provided with a
- 608.0 Water Pressure, Pressure Regulators, Pres-
- 608.2 Excessive Water Pressure. Where static water
- 608.3 Expansion Tanks, and Combination Tempera-ture and Pressu…
- 608.4 Pressure Relief Valves. Each pressure relief valve
- 608.5 Discharge Piping. The discharge piping serving a
- 609.3 Under Concrete Slab. Water piping installed within
- 608.6 Water-Heating Devices. A water-heating device
- 608.7 Vacuum Relief Valves. Where a hot-water storage
- 609.0 Installation, Testing, Unions, and Location.609.1 Instal…
- 609.2 Trenches. Water pipes shall not be run or laid in the
- 609.4 Testing. Upon completion of a section or of the entire
- 609.5 Unions. Unions shall be installed in the water supply
- 609.6 Location. Except as provided in Section 609.7, no
- 609.7 Abutting Lot. Nothing contained in this code shall
- 609.8 Low-Pressure Cutoff Required on BoosterPumps for Water D…
- 609.9 Disinfection of Potable Water System. New or
- 609.11 Pipe Insulation. Insulation of domestic hot water
- 610.2 Pressure Loss. Where a water filter, water softener,
- 609.10 Water Hammer. [Not adopted by HCD] Building water suppl…
- 610.3 Quantity of Water. The quantity of water required
- 610.4 Sizing Water Supply and Distribution Systems. Systems wi…
- 610.5 Sizing per Appendices A and C. Except as provided in Sec…
- 610.6 Friction and Pressure Loss. Except where the type
- 610.7 Conditions for Using Table 610.4. On a proposed
- 610.9 Size of Branches. Where Table 610.4 is used, the minimum…
- 610.10 Sizing for Flushometer Valves. Where using
- 610.8 Size of Meter and Building Supply Pipe UsingTable 610.4.…
- 610.13 Exceptions. The provisions of this section relative
- 610.12 Sizing for Velocity. Water piping systems shall not
- 610.11 Sizing Systems for Flushometer Tanks. The
- 611.2 Air Gap Discharge. Discharge from drinking water
- 611.3 Connection Tubing. The tubing to and from drinking water…
- 611.4 Sizing of Residential Softeners. Residential-use
- 612.0 Residential Fire Sprinkler Systems.612.1 Where Required.…
- 612.2 Types of Systems. This section shall apply to standalone…
- 612.3 Sprinklers. Sprinklers shall be installed in accordance …
- 612.4 Sprinkler Piping System. Sprinkler piping systems
- 612.5 Sprinkler Piping Design. Sprinkler piping systems
- 612.6 Instructions and Signs. An owner’s manual for the
- 612.7 Inspection and Testing. The inspection and testing of sp…
- 613.0 [OSHPD 1, 1R, 2, 3, 4 & 5] Domestic Hot-Water
- 613.2 At least two pieces of hot-water-heating equipment shall
- 613.3 Instantaneous heaters are permitted for supplying hot
- 613.4 Water storage tanks shall be fabricated of corrosion-
- 613.5 Temperature control valves shall be provided to auto-
- 613.6 Hot-water distribution system serving patient care
- 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
- 613.8 Sectionalizing valves shall be provided as required by
- 614.2 All piping for multistation or central dialysis units sh…
- 614.3 All valves shall be located in accessible locations.
- 614.4 Piping and valves shall be identified according to their
- 614.5 A means of preventing backwashing or flushing of the
- 614.6 A continuous audible alarm shall sound at the nurses’
- 614.7 Water used for dialysis treatment shall meet the latest
- 614.8 A diagram of all piping as installed shall be posted at …
- 615.1 Uses Not Permitted.615.1.1 [OSHPD 1, 1R, 2, 3, 4 & 5] No…
- 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5] Non-potable water sys-
- 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5] Outlets for non-potable
- 615.4 [OSHPD 1] Emergency Water Supply.615.4.1 For new acute c…
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR