603.4 General Requirements. Assemblies shall comply

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

with listed standards and be acceptable to the Authority Having Jurisdiction, with jurisdiction over the selection and installation of backflow prevention assemblies.

603.4.1 Backflow Prevention Valve. Where more than one backflow prevention valve is installed on a single premise, and the valves are installed in one location, each separate valve shall be permanently identified by the permittee in a manner satisfactory to the Authority Having Jurisdiction. 603.4.2 Testing. The premise owner or responsible person shall have the backflow prevention assembly tested by a certified backflow assembly tester at the time of installation, repair, or relocation and not less than on an annual schedule thereafter, or more often where required by the Authority Having Jurisdiction. The periodic testing shall be performed in accordance with the procedures referenced in ASSE Series 5000 by a tester qualified in accordance with those standards. 603.4.3 Access and Clearance. Access and clearance shall be provided for the required testing, maintenance, and repair. Access and clearance shall be in accordance with the manufacturer’s instructions, and not

TABLE 603.3.1 MINIMUM AIR GAPS FOR WATER DISTRIBUTION 4

FIXTURES WHERE NOT AFFECTED BY SIDEWALLS1
(inches)
WHERE AFFECTED BY SIDEWALLS2
(inches)
Effective openings3 not greater than1⁄2 of an inch
in diameter

1
11~~⁄~~2

Effective openings3 not greater than3⁄4 of an inch
in diameter

11~~⁄~~2
21~~⁄~~4

Effective openings3 not greater than 1 inch in
diameter

2

3




Effective openings3 greater than 1 inch in
diameter
Two times the diameter of
effective opening
Three times the diameter of
effective opening

1 Sidewalls, ribs, or similar obstructions do not affect air gaps where spaced from the inside edge of the spout opening a distance exceeding three times the diameter of the effective opening for a single wall, or a distance exceeding four times the effective opening for two intersecting walls. 2 Vertical walls, ribs, or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening other than specified in Footnote 1 above. The effect of three or more such vertical walls or ribs has not been determined. In such cases, the air gap shall be measured from the top of the wall. 3 The effective opening shall be the minimum cross-sectional area at the seat of the control valve or the supply pipe or tubing that feeds the device or outlet. Where two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas of the individual supply lines or the area of the single outlet, whichever is smaller. 4 Air gaps less than 1 inch (25.4 mm) shall be approved as a permanent part of a listed assembly that has been tested under actual backflow conditions with vacuums of 0 to 25 inches of mercury (85 kPa).

here two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas of the individual supply lines or the area of the single outlet, whichever is smaller. 4 Air gaps less than 1 inch (25.4 mm) shall be approved as a permanent part of a listed assembly that has been tested under actual backflow conditions with vacuums of 0 to 25 inches of mercury (85 kPa).

140 2019 CALIFORNIA PLUMBING CODE

WATER SUPPLY AND DISTRIBUTION

less than 12 inches (305 mm) between the lowest portion of the assembly and grade, floor, or platform. Installations elevated that exceed 5 feet (1524 mm) above the floor or grade shall be provided with a platform capable of supporting a tester or maintenance person. 603.4.4 Connections. Direct connections between potable water piping and sewer-connected wastes shall not be permitted to exist un der any condition with or without backflow protection. Where potable water is discharged to the drainage system, it shall be by means of an approved air gap of two pipe diameters of the supply inlet, but in no case shall the gap be less than 1 inch (25.4 mm). Connection shall be permitted to be made to the inlet side of a trap provided that an approved vacuum breaker is installed not less than 6 inches (152 mm), or the distance according to the device’s listing, above the flood-level rim of such trapped fixture, so that at no time will such device be subjected to backpressure. 603.4.5 Hot Water Backflow Preventers. Backflow preventers for hot water exceeding 110°F (43°C) shall be a type designed to operate at temperatures exceeding 110°F (43°C) without rendering a portion of the assembly inoperative. 603.4.6 Integral Backflow Preventers. Fixtures, appliances, or appurtenances with integral backflow preventers or integral air gaps manufactured as a unit shall be installed in accordance with their listing requirements and the manufacturer’s installation instructions. 603.4.7 Freeze Protection. In cold climate areas, backflow assemblies and devices shall be protected from freezing with an outdoor enclosure that complies with ASSE 1060 or by a method acceptable to the Authority Having Jurisdiction. 603.4.8 Drain Lines. Drain lines serving backflow devices or assemblies shall be sized in accordance with the discharge rates of the manufacturer’s flow charts of such devices or assemblies. 603.4.9 Prohibited Locations. Backflow prevention devices with atmospheric vents or ports shall not be installed in pits, underground, or submerged locations. Backflow preventers shall not be located in an area containing fumes that are toxic, poisonous, or corrosive.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
    Overview
    1. 601.2 Hot and Cold Water Required. Except where not
    2. 601.3 Identification of a Potable and NonpotableWater System. …
    3. 601.5 [AGR] Meat and Poultry Processing Plants. Except as prov…
    4. 601.4 [CA] Schools of Cosmetology and Cosmeto-
    5. 601.6 [AGR] Collection Centers and Facilities.601.6.1 The wate…
    6. 601.7 [AGR] Renderers. This area shall be provided with
    7. 601.8 [AGR] Horse Meat and Pet Food Establishments.601.8.1 The…
    8. 602.3 Backflow Prevention. No plumbing fixture, device,
    9. 602.4 Approval by Authority. No water piping supplied
    10. 603.0 Cross-Connection Control.603.1 General. Cross-connection…
    11. 603.2 Approval of Devices or Assemblies. Before a
    12. 602.0 Unlawful Connections.602.1 Prohibited Installation. No i…
    13. 602.2 Cross-Contamination. No person shall make a connection o…
    14. 603.3 Backflow Prevention Devices, Assemblies, andMethods. Bac…
    15. 603.4 General Requirements. Assemblies shall comply
    16. 603.5 Specific Requirements. Specific requirements for
    17. 604.0 Materials.604.1 Pipe, Tube, and Fittings. Pipe, tube, fi…
    18. 604.2 Lead Content. The maximum allowable lead content in pipe…
    19. 604.3 Copper or Copper Alloy Tube. Copper or copper
    20. 604.4 Hard-Drawn Copper or Copper Alloy Tubing. Hard-drawn cop…
    21. 604.5 Flexible Connectors. Flexible water connectors
    22. 604.6 Cast-Iron Fittings. Cast-iron fittings up to and
    23. 604.7 Malleable Iron Fittings. Malleable iron water fittings s…
    24. 604.8 Previously Used Piping and Tubing. Piping and
    25. 604.9 Epoxy Coating. The epoxy coating used on existing, under…
    26. 604.10 Plastic Materials. Approved plastic materials shall
    27. 605.0 Joints and Connections.
    28. 604.11 Solder. Solder shall comply with the requirements of
    29. 604.12 Flexible Corrugated Connectors. Flexible corrugated con…
    30. 604.13 Water Heater Connectors. Flexible metallic (copper and …
    31. 605.2 CPVC Plastic Pipe and Joints. CPVC plastic pipe
    32. 605.3 CPVC/AL/CPVC Plastic Pipe and Joints. Chlorinated polyvi…
    33. 605.4 Ductile Iron Pipe and Joints. Ductile iron pipe
    34. 605.5 Galvanized Steel Pipe and Joints. Galvanized
    35. 605.6 PE Plastic Pipe/Tubing and Joints. PE plastic
    36. 605.7 PE-AL-PE Plastic Pipe/Tubing and Joints. PEAL-PE plastic…
    37. 605.8 PE-RT. Polyethylene of raised temperature (PE-RT)
    38. 605.9 PEX Plastic Tubing and Joints. PEX plastic tubing and fi…
    39. 605.11 Polypropylene (PP) Piping and Joints. PP pipe
    40. 605.10 PEX-AL-PEX Plastic Tubing and Joints. PEXAL-PEX plastic…
    41. 605.12 PVC Plastic Pipe and Joints. PVC plastic pipe
    42. 605.13 Stainless Steel Pipe and Joints. Joining methods for st…
    43. 605.14 Slip Joints. In water piping, slip joints shall be perm…
    44. 605.15 Dielectric Unions. Dielectric unions where
    45. 605.16 Joints Between Various Materials. Joints
    46. 606.0 Valves.606.1 General. Valves up to and including 2 inche…
    47. 606.2 Fullway Valve. A fullway valve controlling outlets
    48. 606.3 Multidwelling Units. In multidwelling units, one or
    49. 606.4 Multiple Openings. Valves used to control two or
    50. 606.5 Control Valve. A control valve shall be installed
    51. 606.6 Accessible. Required shutoff or control valves shall
    52. 606.7 Multiple Fixtures. A single control valve shall be
    53. 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5] Each riser or branch
    54. 607.2 Potable Water Tanks. Potable water supply tanks,
    55. 607.3 Venting. Tanks used for potable water shall be tightly
    56. 607.4 Overflow. Tanks shall have not less than a 16 square
    57. 607.5 Valves. Pressurized tanks shall be provided with a
    58. 608.0 Water Pressure, Pressure Regulators, Pres-
    59. 608.2 Excessive Water Pressure. Where static water
    60. 608.3 Expansion Tanks, and Combination Tempera-ture and Pressu…
    61. 608.4 Pressure Relief Valves. Each pressure relief valve
    62. 608.5 Discharge Piping. The discharge piping serving a
    63. 609.3 Under Concrete Slab. Water piping installed within
    64. 608.6 Water-Heating Devices. A water-heating device
    65. 608.7 Vacuum Relief Valves. Where a hot-water storage
    66. 609.0 Installation, Testing, Unions, and Location.609.1 Instal…
    67. 609.2 Trenches. Water pipes shall not be run or laid in the
    68. 609.4 Testing. Upon completion of a section or of the entire
    69. 609.5 Unions. Unions shall be installed in the water supply
    70. 609.6 Location. Except as provided in Section 609.7, no
    71. 609.7 Abutting Lot. Nothing contained in this code shall
    72. 609.8 Low-Pressure Cutoff Required on BoosterPumps for Water D…
    73. 609.9 Disinfection of Potable Water System. New or
    74. 609.11 Pipe Insulation. Insulation of domestic hot water
    75. 610.2 Pressure Loss. Where a water filter, water softener,
    76. 609.10 Water Hammer. [Not adopted by HCD] Building water suppl…
    77. 610.3 Quantity of Water. The quantity of water required
    78. 610.4 Sizing Water Supply and Distribution Systems. Systems wi…
    79. 610.5 Sizing per Appendices A and C. Except as provided in Sec…
    80. 610.6 Friction and Pressure Loss. Except where the type
    81. 610.7 Conditions for Using Table 610.4. On a proposed
    82. 610.9 Size of Branches. Where Table 610.4 is used, the minimum…
    83. 610.10 Sizing for Flushometer Valves. Where using
    84. 610.8 Size of Meter and Building Supply Pipe UsingTable 610.4.…
    85. 610.13 Exceptions. The provisions of this section relative
    86. 610.12 Sizing for Velocity. Water piping systems shall not
    87. 610.11 Sizing Systems for Flushometer Tanks. The
    88. 611.2 Air Gap Discharge. Discharge from drinking water
    89. 611.3 Connection Tubing. The tubing to and from drinking water…
    90. 611.4 Sizing of Residential Softeners. Residential-use
    91. 612.0 Residential Fire Sprinkler Systems.612.1 Where Required.…
    92. 612.2 Types of Systems. This section shall apply to standalone…
    93. 612.3 Sprinklers. Sprinklers shall be installed in accordance …
    94. 612.4 Sprinkler Piping System. Sprinkler piping systems
    95. 612.5 Sprinkler Piping Design. Sprinkler piping systems
    96. 612.6 Instructions and Signs. An owner’s manual for the
    97. 612.7 Inspection and Testing. The inspection and testing of sp…
    98. 613.0 [OSHPD 1, 1R, 2, 3, 4 & 5] Domestic Hot-Water
    99. 613.2 At least two pieces of hot-water-heating equipment shall
    100. 613.3 Instantaneous heaters are permitted for supplying hot
    101. 613.4 Water storage tanks shall be fabricated of corrosion-
    102. 613.5 Temperature control valves shall be provided to auto-
    103. 613.6 Hot-water distribution system serving patient care
    104. 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
    105. 613.8 Sectionalizing valves shall be provided as required by
    106. 614.2 All piping for multistation or central dialysis units sh…
    107. 614.3 All valves shall be located in accessible locations.
    108. 614.4 Piping and valves shall be identified according to their
    109. 614.5 A means of preventing backwashing or flushing of the
    110. 614.6 A continuous audible alarm shall sound at the nurses’
    111. 614.7 Water used for dialysis treatment shall meet the latest
    112. 614.8 A diagram of all piping as installed shall be posted at …
    113. 615.1 Uses Not Permitted.615.1.1 [OSHPD 1, 1R, 2, 3, 4 & 5] No…
    114. 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5] Non-potable water sys-
    115. 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5] Outlets for non-potable
    116. 615.4 [OSHPD 1] Emergency Water Supply.615.4.1 For new acute c…
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.