Chapter 5 — WATER HEATERS
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Sections in this part
- 501.0 General.501.1 Applicability. The regulations of this chapter shall
- 503.2 Final Water Heater Inspection. This inspection
- 504.2 Vent. Water heaters of other than the direct-vent type
- 504.3 Clearance. The clearance requirements for water
- 504.4 Pressure-Limiting Devices.
- 504.5 Temperature-Limiting Devices. A water heater
- 504.6 Temperature, Pressure, and Vacuum Relief
- 505.2 Safety Devices. Storage-type water heaters and hot
- 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
- 505.4 Indirect-Fired Water Heaters. Indirect-fired water
- 506.0 Air for Combustion and Ventilation.506.1 General.
- 506.2 Indoor Combustion Air. The required volume of
- 506.4 Outdoor Combustion Air. Outdoor combustion air
- 506.3 Indoor Opening Size and Location. Openings
- 506.8 Louvers, Grilles, and Screens. The required size
- 506.5 Combination Indoor and Outdoor CombustionAir.
- 506.9 Combustion Air Ducts. Combustion air ducts shall
- 506.6 Engineered Installations. Engineered combustion
- 506.7 Mechanical Combustion Air Supply. Where
- 507.2 Seismic Provisions. Water heaters shall be
- 507.3 Appliance Support. Appliances and equipment shall
- 507.4 Ground Support. A water heater supported from the
- 507.5 Drainage Pan. Where a water heater is located in an
- 507.6 Added or Converted Equipment or Appliances.
- 507.7 Types of Gases. The appliance shall be connected to
- 507.8 Safety Shutoff Devices for Unlisted LP-GasAppliance Used Indoors.
- 507.9 Use of Air or Oxygen Under Pressure. Where air
- 507.10 Protection of Gas Appliances from Fumes orGases other than Products of Combustion.
- 507.11 Process Air.
- 507.12 Flammable Vapors. Appliances shall not be
- 507.13 Installation in Residential Garages. Appliances
- 507.14 Installation in Commercial Garages. Appliances
- 507.15 Installation in Aircraft Hangars.
- 507.16 Venting of Flue Gases. Appliances shall be vented
- 507.17 Extra Device or Attachment.
- 507.18 Adequate Capacity of Piping. When additional
- 507.19 Avoiding Strain on Gas Piping. Appliances shall
- 507.20 Gas Appliance Pressure Regulators. Where the
- 507.21 Venting of Gas Appliance Pressure Regula-tors.
- 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
- 507.23 Combination of Appliances and Equipment. A
- 507.24 Installation Instructions. The installing agency
- 507.25 Protection of Outdoor Appliances. Appliances
- 507.26 Accessibility for Service. Appliances shall be
- 507.27 Clearance to Combustible Materials.
- 508.0 Appliances on Roofs.508.1 General. Appliances on roofs shall be designed or
- 508.2 Installation of Appliances on Roofs. Appliances
- 508.3 Appliances on Roofs. Appliances located on roofs
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.2 Connection to Venting Systems.
- 509.3 Design and Construction. Venting systems shall
- 509.4 Type of Venting System to be Used. The type of
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents. The installation of gas vents shall meet
- 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
- 509.8 Through-the-Wall Vent Termination.
- 509.9 Condensation Drain. Provision shall be made to
- 509.11 Vent Connectors for Category II, Category III,
- 509.12 Draft Hoods and Draft Controls.
- 509.15 Obstructions. Devices that retard the flow of vent
- 509.13 Manually Operated Dampers.
- 509.14 Automatically Operated Vent Dampers. An
- 510.1 Single Appliance Vent Table 510.1.2(1) through
- 510.2 Multiple Appliance Vent Table 510.2(1) throughTable 510.2(9).
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopt Entire Chapter as
amended (amended sections
listed below)
Adopt only those sections
that are listed below
Chapter/Section
| BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| **BSC ** |
BSC- CG |
SFM | 1 | 2 | 1-AC | **AC ** | SS | SS/CC | 1 |
1R | 2 |
3 |
4 |
5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| X | **X ** | X | X | X | ||||||||||||||||||
The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2019 CALIFORNIA PLUMBING CODE 79
80 2019 CALIFORNIA PLUMBING CODE
CHAPTER 5
WATER HEATERS
inspection as deemed necessary to be assured that the work has been installed in accordance with the intent of this code. No appliance or part thereof shall be covered or concealed until the same has been inspected and approved by the Authority Having Jurisdiction.
504.0 Water Heater Requirements.504.1 Location. Water heater installations in bedrooms and¶
bathrooms shall comply with one of the following [NFPA 54:10.27.1]: (1) Fuel-burning water heaters shall be permitted to be
installed in a closet located in the bedroom or bathroom
» »
TIA TIA TIA
502.0 Permits.502.1 General. It shall be unlawful for a person to install,¶
remove, or replace or cause to be installed, removed, or replaced a water heater without first obtaining a permit from the Authority Having Jurisdiction to do so.
503.0 Inspection.503.1 Inspection of Chimneys or Vents.¶
This inspection shall be made after chimneys, vents, or parts thereof, authorized by the permit, have been installed and before such vent or part thereof has been covered or concealed.
505.0 Oil-Burning and Other Water Heaters.505.1 Water Heaters.¶
Water heaters deriving heat from fuels or types of energy other than gas shall comply with the standards referenced in Table 501.1(1), Section 505.3, or Section 505.4. Vents or chimneys for such appliances shall be of approved types. An adequate supply of air for combustion and for adequate ventilation of heater rooms or compartments shall be provided. Each such appliance shall be installed in a location approved by the Authority Having Jurisdiction and local and state fire-prevention agencies.
507.0 Appliance and Equipment Installation Require-¶
ments.507.1 Dielectric Insulator. The Authority Having Jurisdiction shall have the authority to require the use of an approved dielectric insulator on the water piping connections of water heaters and related water heating appliances.
509.0 Venting of Appliances.509.1 Listing.¶
Type B and Type B-W gas vents shall comply with UL 441, and Type L gas vents shall comply with UL 641. 509.1.1 Installation. Listed vents shall be installed in accordance with Section 509.0 and the manufacturer’s installation instructions. [NFPA 54:12.2.1] 509.1.2 Prohibited Discharge. Appliance vents shall not discharge into a space enclosed by screens having openings less than 1 ⁄4 of an inch (6.4 mm) mesh.
510.0 Sizing of Category I Venting Systems.¶
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
▸Chapter 5 — WATER HEATERS
Overview- 501.0 General.501.1 Applicability. The regulations of this cha…
- 503.2 Final Water Heater Inspection. This inspection
- 504.2 Vent. Water heaters of other than the direct-vent type
- 504.3 Clearance. The clearance requirements for water
- 504.4 Pressure-Limiting Devices. A water heater installation s…
- 504.5 Temperature-Limiting Devices. A water heater
- 504.6 Temperature, Pressure, and Vacuum Relief
- 505.2 Safety Devices. Storage-type water heaters and hot
- 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
- 505.4 Indirect-Fired Water Heaters. Indirect-fired water
- 506.0 Air for Combustion and Ventilation.506.1 General. Air fo…
- 506.2 Indoor Combustion Air. The required volume of
- 506.4 Outdoor Combustion Air. Outdoor combustion air
- 506.3 Indoor Opening Size and Location. Openings
- 506.8 Louvers, Grilles, and Screens. The required size
- 506.5 Combination Indoor and Outdoor CombustionAir. The use of…
- 506.9 Combustion Air Ducts. Combustion air ducts shall
- 506.6 Engineered Installations. Engineered combustion
- 506.7 Mechanical Combustion Air Supply. Where
- 507.2 Seismic Provisions. Water heaters shall be
- 507.3 Appliance Support. Appliances and equipment shall
- 507.4 Ground Support. A water heater supported from the
- 507.5 Drainage Pan. Where a water heater is located in an
- 507.6 Added or Converted Equipment or Appliances. When additio…
- 507.7 Types of Gases. The appliance shall be connected to
- 507.8 Safety Shutoff Devices for Unlisted LP-GasAppliance Used…
- 507.9 Use of Air or Oxygen Under Pressure. Where air
- 507.10 Protection of Gas Appliances from Fumes orGases other t…
- 507.11 Process Air. In addition to air needed for combustion i…
- 507.12 Flammable Vapors. Appliances shall not be
- 507.13 Installation in Residential Garages. Appliances
- 507.14 Installation in Commercial Garages. Appliances
- 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
- 507.16 Venting of Flue Gases. Appliances shall be vented
- 507.17 Extra Device or Attachment. No device or attachment sha…
- 507.18 Adequate Capacity of Piping. When additional
- 507.19 Avoiding Strain on Gas Piping. Appliances shall
- 507.20 Gas Appliance Pressure Regulators. Where the
- 507.21 Venting of Gas Appliance Pressure Regula-tors. Venting …
- 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
- 507.23 Combination of Appliances and Equipment. A
- 507.24 Installation Instructions. The installing agency
- 507.25 Protection of Outdoor Appliances. Appliances
- 507.26 Accessibility for Service. Appliances shall be
- 507.27 Clearance to Combustible Materials. Appliances and thei…
- 508.0 Appliances on Roofs.508.1 General. Appliances on roofs s…
- 508.2 Installation of Appliances on Roofs. Appliances
- 508.3 Appliances on Roofs. Appliances located on roofs
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.2 Connection to Venting Systems. Except as permitted in Se…
- 509.3 Design and Construction. Venting systems shall
- 509.4 Type of Venting System to be Used. The type of
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents. The installation of gas vents shall meet
- 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
- 509.8 Through-the-Wall Vent Termination. A mechanical draft ve…
- 509.9 Condensation Drain. Provision shall be made to
- 509.11 Vent Connectors for Category II, Category III,
- 509.12 Draft Hoods and Draft Controls. Vented appliances shall…
- 509.15 Obstructions. Devices that retard the flow of vent
- 509.13 Manually Operated Dampers. A manually operated damper s…
- 509.14 Automatically Operated Vent Dampers. An
- 510.1 Single Appliance Vent Table 510.1.2(1) through
- 510.2 Multiple Appliance Vent Table 510.2(1) throughTable 510.…
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR