Chapter 5 — WATER HEATERS

509.8 Through-the-Wall Vent Termination.

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

A mechanical draft venting system shall terminate at least 3 feet (914 mm) above any forced air inlet located within 10 feet (3048 mm) (See Figure 509.8). Exceptions: (1) This provision shall not apply to the combustion air

intake of a direct-vent appliance.

This provision shall not apply to the separation of the

integral outdoor air inlet and flue gas discharge of listed outdoor appliances. [NFPA 54:12.9.1] 509.8.1 Mechanical Draft Venting System. A mechanical draft venting system of other than direct-vent type shall terminate not less than 4 feet (1219 mm) below, 4 feet (1219 mm) horizontally from, or 1 foot (305 mm) above a door, operable window, or gravity air inlet into a building. The bottom of the vent terminal shall be located not less than 12 inches (305 mm) above finished ground level. [NFPA 54:12.9.2] 509.8.2 Direct-Vent Appliance. The vent terminal of a direct-vent appliance with an input of 10 000 Btu/h (2.93 kW) or less shall be located at least 6 inches (152 mm) from any air opening into a building, an appliance with an input over 10 000 Btu/h (2.9.3 kW) but not over 50 000 Btu/h (14.7 kW) shall be installed with a 9 inch (229 mm) vent termination clearance, and an appliance with an input over 50 000 Btu/h (14.7 kW) shall have at least a 12 inch (305 mm) vent termination clearance. The bottom of the vent terminal and the air intake shall be

(3) Other approved engineering methods. [NFPA

54:12.8.5(1)] 509.7.4.2 Non-Round Metal Pipe. Where a single-wall metal pipe is used and has a shape other than round, it shall have an effective area equal to the effective area of the round pipe for which it is substituted, and the internal dimension of the pipe shall be not less than 2 inches (50 mm). [NFPA 54:12.8.5(2)] 509.7.4.3 Venting Capacity. The vent cap or a roof assembly shall have a venting capacity not less than that of the pipe to which it is attached. [NFPA 54:12.8.5(3)] 509.7.5 Support of Single-Wall Metal Pipe. Portions of single-wall metal pipe shall be supported for the design and weight of the material employed. [NFPA 54:12.8.6] 509.7.6 Marking. Single-wall metal pipe shall comply with the marking provisions of Section 509.6.5. [NFPA 54:12.8.7]

(1) This provision shall not apply to the combustion air

intake of a direct-vent appliance. (2) This provision shall not apply to the separation of the

integral outdoor air inlet and flue gas discharge of listed

FIGURE 509.8 EXIT TERMINALS OF MECHANICAL DRAFT AND DIRECT-VENT VENTING SYSTEMS

[NFPA 54: FIGURE A.12.9]

98 2019 CALIFORNIA PLUMBING CODE

WATER HEATERS

located at least 12 inches (305 mm) above finished ground level. [NFPA 54:12.9.3] 509.8.3 Category I through Category IV and Non-Categorized Appliances. Through-the-wall vents for Category II and Category IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment. Where local experience indicates that condensate is a problem with Category I and Category III appliances, this provision shall also apply.

Type B, Type L, or listed vent material having equivalent insulation qualities. Exception: Single-wall metal pipe located within the exterior walls of the building and located in an unconditioned area other than an attic or a crawl space having a local 99 percent winter design temperature of 5°F (-15°C) or higher. [NFPA 54:12.11.2.2] 509.10.1.2 Residential-Type Appliances. Vent connectors for residential-type appliances shall comply with the following: (1) Vent connectors for listed appliances having

draft hoods, appliances having draft hoods and

Vent connectors for listed appliances having

draft hoods, appliances having draft hoods and equipped with listed conversion burners, and Category I appliances that are not installed in attics, crawl spaces, or other unconditioned areas shall be one of the following: (a) Type B or Type L vent material. (b) Galvanized sheet steel not less than 0.018

of an inch (0.457 mm) thick.

Drains for condensate shall be installed in accordance with the appliance and the vent manufacturer’s installation instructions. [NFPA 54:12.9.4] 509.8.4 Annular Spaces. Where vents, including those for direct-vent appliances or combustion air intake pipes, penetrate outside walls of buildings, the annular spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion products into the building. [NFPA 54:12.9.5] 509.8.5 Vent Terminals. Vent systems for Category IV appliances that terminate through an outside wall of a building and discharge flue gases perpendicular to the adjacent wall shall be located not less than 10 feet (3048 mm) horizontally from an operable opening in an adjacent building. Exception: This shall not apply to vent terminals that are 2 feet (610 mm) or more above or 25 feet (7620 mm) or more below operable openings. [NFPA 54:12.9.6]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
    Overview
    1. 501.0 General.501.1 Applicability. The regulations of this cha…
    2. 503.2 Final Water Heater Inspection. This inspection
    3. 504.2 Vent. Water heaters of other than the direct-vent type
    4. 504.3 Clearance. The clearance requirements for water
    5. 504.4 Pressure-Limiting Devices. A water heater installation s…
    6. 504.5 Temperature-Limiting Devices. A water heater
    7. 504.6 Temperature, Pressure, and Vacuum Relief
    8. 505.2 Safety Devices. Storage-type water heaters and hot
    9. 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
    10. 505.4 Indirect-Fired Water Heaters. Indirect-fired water
    11. 506.0 Air for Combustion and Ventilation.506.1 General. Air fo…
    12. 506.2 Indoor Combustion Air. The required volume of
    13. 506.4 Outdoor Combustion Air. Outdoor combustion air
    14. 506.3 Indoor Opening Size and Location. Openings
    15. 506.8 Louvers, Grilles, and Screens. The required size
    16. 506.5 Combination Indoor and Outdoor CombustionAir. The use of…
    17. 506.9 Combustion Air Ducts. Combustion air ducts shall
    18. 506.6 Engineered Installations. Engineered combustion
    19. 506.7 Mechanical Combustion Air Supply. Where
    20. 507.2 Seismic Provisions. Water heaters shall be
    21. 507.3 Appliance Support. Appliances and equipment shall
    22. 507.4 Ground Support. A water heater supported from the
    23. 507.5 Drainage Pan. Where a water heater is located in an
    24. 507.6 Added or Converted Equipment or Appliances. When additio…
    25. 507.7 Types of Gases. The appliance shall be connected to
    26. 507.8 Safety Shutoff Devices for Unlisted LP-GasAppliance Used…
    27. 507.9 Use of Air or Oxygen Under Pressure. Where air
    28. 507.10 Protection of Gas Appliances from Fumes orGases other t…
    29. 507.11 Process Air. In addition to air needed for combustion i…
    30. 507.12 Flammable Vapors. Appliances shall not be
    31. 507.13 Installation in Residential Garages. Appliances
    32. 507.14 Installation in Commercial Garages. Appliances
    33. 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
    34. 507.16 Venting of Flue Gases. Appliances shall be vented
    35. 507.17 Extra Device or Attachment. No device or attachment sha…
    36. 507.18 Adequate Capacity of Piping. When additional
    37. 507.19 Avoiding Strain on Gas Piping. Appliances shall
    38. 507.20 Gas Appliance Pressure Regulators. Where the
    39. 507.21 Venting of Gas Appliance Pressure Regula-tors. Venting …
    40. 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
    41. 507.23 Combination of Appliances and Equipment. A
    42. 507.24 Installation Instructions. The installing agency
    43. 507.25 Protection of Outdoor Appliances. Appliances
    44. 507.26 Accessibility for Service. Appliances shall be
    45. 507.27 Clearance to Combustible Materials. Appliances and thei…
    46. 508.0 Appliances on Roofs.508.1 General. Appliances on roofs s…
    47. 508.2 Installation of Appliances on Roofs. Appliances
    48. 508.3 Appliances on Roofs. Appliances located on roofs
    49. 508.4 Appliances in Attics and Under-Floor Spaces.
    50. 509.2 Connection to Venting Systems. Except as permitted in Se…
    51. 509.3 Design and Construction. Venting systems shall
    52. 509.4 Type of Venting System to be Used. The type of
    53. 509.5 Masonry, Metal, and Factory-Built Chimneys.
    54. 509.6 Gas Vents. The installation of gas vents shall meet
    55. 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
    56. 509.8 Through-the-Wall Vent Termination. A mechanical draft ve…
    57. 509.9 Condensation Drain. Provision shall be made to
    58. 509.11 Vent Connectors for Category II, Category III,
    59. 509.12 Draft Hoods and Draft Controls. Vented appliances shall…
    60. 509.15 Obstructions. Devices that retard the flow of vent
    61. 509.13 Manually Operated Dampers. A manually operated damper s…
    62. 509.14 Automatically Operated Vent Dampers. An
    63. 510.1 Single Appliance Vent Table 510.1.2(1) through
    64. 510.2 Multiple Appliance Vent Table 510.2(1) throughTable 510.…
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.