509.3 Design and Construction. Venting systems shall
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
be designed and constructed to convey flue, vent, or both gases to the outdoors. [NFPA 54:12.1]
509.3.1 Appliance Draft Requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions.
[NFPA 54:12.4.1] 509.3.2 Appliance Venting Requirements. Appliances required to be vented shall be connected to a venting system designed and installed in accordance with the provisions of Section 509.4 through Section 509.15.
[NFPA 54:12.4.2] 509.3.3 Mechanical Draft Systems. Mechanical draft systems shall be listed and installed in accordance with both the appliance and the mechanical draft system manufacturer’s installation instructions. [NFPA 54:12.4.3.1] 509.3.3.1 Venting. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced draft design. [NFPA 54:12.4.3.2] 509.3.3.2 Leakage. Forced draft systems and portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. [NFPA 54:12.4.3.3]
2019 CALIFORNIA PLUMBING CODE 89
WATER HEATERS any other purpose or distributed to any other persons or parti es.
509.3.3.3 Vent Connectors. Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. [NFPA 54:12.4.3.4] 509.3.3.4 Operation. Where a mechanical draft system is employed, provision shall be made to prevent the flow of gas to the main burners where the draft system is not performing so as to satisfy the operating requirements of the appliance for safe performance. [NFPA 54:12.4.3.5] 509.3.3.5 Exit Terminals. The exit terminals of mechanical draft systems shall be not less than 7 feet (2134 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 509.8 and Section 509.8.1 of this code. [NFPA 54:12.4.3.6] 509.3.4 Ventilating Hoods and Exhaust Systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications. [NFPA 54:12.4.4.1]
509.3.4.1 Automatically Operated Appli-ances. Where automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners where the damper is open to a position to properly vent the appliance and where the power means of exhaust is in operation.
i-ances.** Where automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners where the damper is open to a position to properly vent the appliance and where the power means of exhaust is in operation.
[NFPA 54:12.4.4.2] 509.3.5 Circulating Air Ducts and Furnace Plenums. Venting systems shall not extend into or pass through a fabricated air duct or furnace plenum. [NFPA 54:12.4.5.1] 509.3.6 Above-Ceiling or Nonducted Air Han- dling System. Where a venting system passes through an above-ceiling air space or other nonducted portion of an air-handling system, it shall conform to one of the following requirements: (1) The venting system shall be a listed special gas vent,
other system serving a Category III or Category IV
TABLE 509.4 TYPE OF VENTING SYSTEM TO BE USED
[NFPA 54: TABLE 12.5.1]
(1) The venting system shall be a listed special gas vent,
other system serving a Category III or Category IV appliance, or other positive pressure vent, with joints sealed in accordance with the appliance or vent manufacturer’s instructions. (2) The vent system shall be installed such that no fit tings or joints between sections are installed in the
(2) The vent system shall be installed such that no fit tings or joints between sections are installed in the above-ceiling space. (3) The venting system shall be installed in a conduit or
enclosure with joints between the interior of the enclo
| APPLIANCES | TYPE OF VENTING SYSTEM |
LOCATION OF REQUIREMENTS |
|---|---|---|
appliances |
||
equipped with draft hood |
Chimney |
Section 509.5 |
use with Type B gas vent |
pipe Listed chimney lin- ing system for gas venting Special gas vent listed for appliances |
Section 509.5.3 Section 509.4.3 |
naces |
Section 509.6.1.2 |
|
Category III appliances Category IV appliances |
furnished by manufacturers of listed appliances |
and Section 509.4.3 |
converted to use solid fuel Unlisted combination gas- and oil-burning appliances Combination gas- and solid-fuel-burning appliances Appliance listed for use with chimneys only Unlisted appliances |
Chimney |
Section 509.5 |
gas- and oil-burning appliances |
Chimney |
Section 509.5 |
in vented fireplace |
911.2 |
|
pipe |
||
integral vents |
turer’s installation instruction shall identify the specific plastic piping material. [NFPA 54:12.5.2] 509.4.2 Plastic Vent Joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s installation instructions. Where primer is required, it shall be of a contrasting color. [NFPA 54:12.5.3] 509.4.3 Special Gas Vents. Special gas vents shall be listed and installed in accordance with the special gas vent manufacturer’s installation instructions. [NFPA 54:12.5.4]
(3) The venting system shall be installed in a conduit or
enclosure with joints between the interior of the enclosure and the ceiling space sealed. [NFPA 54:12.4.5.2]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
▸Chapter 5 — WATER HEATERS
Overview- 501.0 General.501.1 Applicability. The regulations of this cha…
- 503.2 Final Water Heater Inspection. This inspection
- 504.2 Vent. Water heaters of other than the direct-vent type
- 504.3 Clearance. The clearance requirements for water
- 504.4 Pressure-Limiting Devices. A water heater installation s…
- 504.5 Temperature-Limiting Devices. A water heater
- 504.6 Temperature, Pressure, and Vacuum Relief
- 505.2 Safety Devices. Storage-type water heaters and hot
- 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
- 505.4 Indirect-Fired Water Heaters. Indirect-fired water
- 506.0 Air for Combustion and Ventilation.506.1 General. Air fo…
- 506.2 Indoor Combustion Air. The required volume of
- 506.4 Outdoor Combustion Air. Outdoor combustion air
- 506.3 Indoor Opening Size and Location. Openings
- 506.8 Louvers, Grilles, and Screens. The required size
- 506.5 Combination Indoor and Outdoor CombustionAir. The use of…
- 506.9 Combustion Air Ducts. Combustion air ducts shall
- 506.6 Engineered Installations. Engineered combustion
- 506.7 Mechanical Combustion Air Supply. Where
- 507.2 Seismic Provisions. Water heaters shall be
- 507.3 Appliance Support. Appliances and equipment shall
- 507.4 Ground Support. A water heater supported from the
- 507.5 Drainage Pan. Where a water heater is located in an
- 507.6 Added or Converted Equipment or Appliances. When additio…
- 507.7 Types of Gases. The appliance shall be connected to
- 507.8 Safety Shutoff Devices for Unlisted LP-GasAppliance Used…
- 507.9 Use of Air or Oxygen Under Pressure. Where air
- 507.10 Protection of Gas Appliances from Fumes orGases other t…
- 507.11 Process Air. In addition to air needed for combustion i…
- 507.12 Flammable Vapors. Appliances shall not be
- 507.13 Installation in Residential Garages. Appliances
- 507.14 Installation in Commercial Garages. Appliances
- 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
- 507.16 Venting of Flue Gases. Appliances shall be vented
- 507.17 Extra Device or Attachment. No device or attachment sha…
- 507.18 Adequate Capacity of Piping. When additional
- 507.19 Avoiding Strain on Gas Piping. Appliances shall
- 507.20 Gas Appliance Pressure Regulators. Where the
- 507.21 Venting of Gas Appliance Pressure Regula-tors. Venting …
- 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
- 507.23 Combination of Appliances and Equipment. A
- 507.24 Installation Instructions. The installing agency
- 507.25 Protection of Outdoor Appliances. Appliances
- 507.26 Accessibility for Service. Appliances shall be
- 507.27 Clearance to Combustible Materials. Appliances and thei…
- 508.0 Appliances on Roofs.508.1 General. Appliances on roofs s…
- 508.2 Installation of Appliances on Roofs. Appliances
- 508.3 Appliances on Roofs. Appliances located on roofs
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.2 Connection to Venting Systems. Except as permitted in Se…
- 509.3 Design and Construction. Venting systems shall
- 509.4 Type of Venting System to be Used. The type of
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents. The installation of gas vents shall meet
- 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
- 509.8 Through-the-Wall Vent Termination. A mechanical draft ve…
- 509.9 Condensation Drain. Provision shall be made to
- 509.11 Vent Connectors for Category II, Category III,
- 509.12 Draft Hoods and Draft Controls. Vented appliances shall…
- 509.15 Obstructions. Devices that retard the flow of vent
- 509.13 Manually Operated Dampers. A manually operated damper s…
- 509.14 Automatically Operated Vent Dampers. An
- 510.1 Single Appliance Vent Table 510.1.2(1) through
- 510.2 Multiple Appliance Vent Table 510.2(1) throughTable 510.…
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR