509.7 Single-Wall Metal Pipe. Single-wall metal pipe

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

shall be constructed of galvanized sheet steel not less than 0.0304 of an inch (0.7722 mm) thick or of other approved, noncombustible, corrosion-resistant material. [NFPA 54:12.8.1] 509.7.1 Cold Climate. Uninsulated single-wall metal pipe shall not be used outdoors for venting appliances in regions where the 99 percent winter design temperature is below 32°F (0°C). [NFPA 54:12.8.2] 509.7.2 Termination. The termination of single-wall metal pipe shall meet the following requirements: (1) Single-wall metal pipe shall terminate at least 5 feet

(1524 mm) in vertical height above the highest con

509.7.3 Installation with Appliances Permitted bySection 509.4. Single-wall metal pipe shall not be used as a vent in dwellings and residential occupancies.

[NFPA 54:12.8.4.1]

(1) Single-wall metal pipe shall terminate at least 5 feet

(1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. (2) Single-wall metal pipe shall extend at least 2 feet

(610 mm) above the highest point where it passes

(2) Single-wall metal pipe shall extend at least 2 feet

(610 mm) above the highest point where it passes through a roof of a building and at least 2 feet (610 mm) higher than any portion of a building within a horizontal distance of 10 feet (3048 mm). (See Figure 509.5.4) (3) An approved cap or roof assembly shall be attached

to the terminus of a single-wall metal pipe. [NFPA

«

An approved cap or roof assembly shall be attached

to the terminus of a single-wall metal pipe. [NFPA 54:12.8.3]

509.7.3.1 Limitations. Single-wall metal pipe shall be used for runs directly from the space in which the appliance is located through the roof or exterior wall to the outer air. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jacket, or roof thimble. [NFPA 54:12.8.4.2] 509.7.3.2 Attic or Concealed Space. Singlewall metal pipe shall not originate in an unoccupied attic or concealed space and shall not pass through an attic, inside wall, concealed space, or floor.

[NFPA 54:12.8.4.3] 509.7.3.3 Incinerator. Single-wall metal pipe used for venting an incinerator shall be exposed and readily examinable for its full length and shall have required clearances maintained. 509.7.3.4 Clearances. Minimum clearances from single-wall metal pipe to combustible material shall be in accordance with Table 509.7.3.4(1). Reduced clearances from single-wall metal pipe to combustible material shall be as specified for vent connectors in Table 509.7.3.4(2). [NFPA 54:12.8.4.4] 509.7.3.5 Combustible Exterior Wall. Singlewall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: (1) For listed appliances with draft hoods and appli ances listed for use with Type B gas vents, the

shall be as specified for vent connectors in Table 509.7.3.4(2). [NFPA 54:12.8.4.4] 509.7.3.5 Combustible Exterior Wall. Singlewall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: (1) For listed appliances with draft hoods and appli ances listed for use with Type B gas vents, the

For listed appliances with draft hoods and appli ances listed for use with Type B gas vents, the thimble shall be a minimum of 4 inches (100 mm) larger in diameter than the metal pipe.

TABLE 509.7.3.4(1) CLEARANCE FOR CONNECTORS [NFPA 54: TABLE 12.8.4.4]*
MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL (inches)
APPLIANCE
LISTED TYPE B GAS
VENT MATERIAL
LISTED TYPE L VENT
MATERIAL
SINGLE-WALL METAL
PIPE
FACTORY-BUILT
CHIMNEY SECTIONS
Listed appliances with draft hoods and appli-
ances listed for use with Type B gas vents
As listed
As listed
6
As listed

Residential boilers and furnaces with listed
gas conversion burner and with draft hood
6
6
9
As listed

Residential appliances listed for use with
Type L vents
Not permitted
As listed
9
As listed

Unlisted residential appliances with draft
hood
Not permitted
6
9
As listed
Residential and low-heat appliances other
than those above
Not permitted
9
18
As listed

Medium-heat appliances
Not permitted Not permitted 36 As listed
  • These clearances shall apply unless the installation instructions of a listed appliance or connector specify different clearances, in which case the listed clearances shall apply.

2019 CALIFORNIA PLUMBING CODE 95

WATER HEATERS any other purpose or distributed to any other persons or parti es.

(3) For residential and low-heat appliances, the

thimble shall be a minimum of 12 inches (300 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such opening shall be noncombustible. [NFPA 54:12.8.4.6] 509.7.3.6 Roof Thimble. Where a single-wall metal pipe passes through a roof constructed of combustible material, a noncombustible, nonventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches (457 mm) above and 6 inches (152 mm) below the roof with the annular space open at the bottom and closed at the top. The thimble shall be sized in accordance with Section 509.7.3.5. [NFPA 54:12.8.4.5] 509.7.4 Size of Single-Wall Metal Pipe. Singlewall metal piping shall comply with the Section 509.7.4.1 through Section 509.7.4.3. [NFPA 54:12.8.5] 509.7.4.1 Sizing of Venting System. A venting system of a single-wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions:

» »

Table 509.7.3.4(2) and in the sections applying to various types of appliances. 2 B - Equals the reduced clearance permitted in accordance with Table 509.7.3.4(2). 3 The protection applied to the construction using combustible material shall extend far enough in each direction to make C equal to A.

FIGURE 509.7.3.4(1) 1, 2, 3

EXTENT OF PROTECTION NECESSARY TO REDUCE CLEARANCES FROM GAS APPLIANCES

OR VENT CONNECTORS

[NFPA 54: FIGURE 10.3.2.3(a)]

Note: Masonry walls shall be attached to combustible walls using wall ties. Spacers shall not be used directly behind appliance or connector.

FIGURE 509.7.3.4(2) WALL PROTECTION REDUCTION SYSTEM

[NFPA 54: FIGURE 10.3.2.3(b)]

FIGURE 509.7.3.4(3) MASONRY CLEARANCE REDUCTION SYSTEM

[NFPA 54: FIGURE 10.3.2.3(c)]

«

Where there is a run of not less than 6 feet (1829 mm) of metal pipe in the opening between the draft hood outlet and the thimble, the thimble shall be a minimum of 2 inches (50 mm) larger in diameter than the metal pipe. (2) For unlisted appliances having draft hoods, the

thimble shall be a minimum of 6 inches (150

(2) For unlisted appliances having draft hoods, the

thimble shall be a minimum of 6 inches (150 mm) larger in diameter than the metal pipe. (3) For residential and low-heat appliances, the

thimble shall be a minimum of 12 inches (300

96 2019 CALIFORNIA PLUMBING CODE

WATER HEATERS

TABLE 509.7.3.4(2) REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11

WATER HEATERS

[NFPA 54: TABLE 10.2.3]
TYPE OF PROTECTION APPLIED TO
AND COVERING ALL SURFACES OF
COMBUSTIBLE MATERIAL WITHIN
THE DISTANCE SPECIFIED AS THE
REQUIRED CLEARANCE WITH NO
PROTECTION [SEE FIGURE
509.7.3.4(1) THROUGH FIGURE
509.7.3.4(3)]

WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
TYPE OF PROTECTION APPLIED TO
AND COVERING ALL SURFACES OF
COMBUSTIBLE MATERIAL WITHIN
THE DISTANCE SPECIFIED AS THE
REQUIRED CLEARANCE WITH NO
PROTECTION [SEE FIGURE
509.7.3.4(1) THROUGH FIGURE
509.7.3.4(3)]

36 (inches) 36 (inches) 18 (inches) 18 (inches) 12 (inches) 12 (inches) 9 (inches) 9 (inches) 6 (inches) 6 (inches)
TYPE OF PROTECTION APPLIED TO
AND COVERING ALL SURFACES OF
COMBUSTIBLE MATERIAL WITHIN
THE DISTANCE SPECIFIED AS THE
REQUIRED CLEARANCE WITH NO
PROTECTION [SEE FIGURE
509.7.3.4(1) THROUGH FIGURE
509.7.3.4(3)]

ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)
TYPE OF PROTECTION APPLIED TO
AND COVERING ALL SURFACES OF
COMBUSTIBLE MATERIAL WITHIN
THE DISTANCE SPECIFIED AS THE
REQUIRED CLEARANCE WITH NO
PROTECTION [SEE FIGURE
509.7.3.4(1) THROUGH FIGURE
509.7.3.4(3)]

USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
TYPE OF PROTECTION APPLIED TO
AND COVERING ALL SURFACES OF
COMBUSTIBLE MATERIAL WITHIN
THE DISTANCE SPECIFIED AS THE
REQUIRED CLEARANCE WITH NO
PROTECTION [SEE FIGURE
509.7.3.4(1) THROUGH FIGURE
509.7.3.4(3)]

ABOVE
COLUMN
1
SIDES
AND
REAR
COLUMN
2
ABOVE
COLUMN
1
SIDES
AND
REAR
COLUMN
2
ABOVE
COLUMN
1
SIDES
AND
REAR
COLUMN
2
ABOVE
COLUMN
1
SIDES
AND
REAR
COLUMN
2
ABOVE
COLUMN
1
SIDES
AND
REAR
COLUMN
2
(1)
31⁄2 inch thick masonry wall
without ventilated air space

–– 24 –– 12 –– 9 –– 6 –– 5

(2)
1⁄2 of an inch insulation board
over 1 inch glass fiber or min-
eral wool batts

24 18 12 9 9 6 6 5 4 3
[NFPA 54: TABLE 10.2.3]

(3)
0.024 inch (nominal 24 gauge)
sheet metal over 1 inch glass
fiber or mineral wool batts
reinforced with wire on rear
face with ventilated air space

18
12
9
6
6
4
5
3
3
3

(4)
31⁄2 inch thick masonry wall
with ventilated air space

–– 12 –– 6 –– 6 –– 6 –– 6

(5)
0.024 inch (nominal 24 gauge)
sheet metal with ventilated air
space

18
12
9
6
6
4
5
3
3
2
(6)
1⁄2 of an inch thick insulation
board with ventilated air space

18 12 9 6 6 4 5 3 3 3

(7)
0.024 inch (nominal 24 gauge)
sheet metal with ventilated air
space over 0.024 inch (nomi-
nal 24 gauge) sheet metal with
ventilated air space

18 12 9 6 6 4 5 3 3 3

(8)
1 inch glass fiber or mineral
wool batts sandwiched
between two sheets 0.024 inch
(nominal 24 gauge) sheet
metal with ventilated air space
18
12 9 6 6 4 5 3 3 3

Notes: 1 Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing. 2 Clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disregarding an intervening protection applied to the combustible material. 3 Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite the appliance or connector. 4 Where clearance reduction systems use a ventilated air space, adequate provision for air circulation shall be provided as described. [See Figure 509.7.3.4(2) and Figure 509.7.3.4(3)] 5 There shall be not less than 1 inch (25.4 mm) between clearance reduction systems and combustible walls and ceilings for reduction systems using a ventilated air space. 6 Where a wall protector is mounted on a single flat wall away from corners, it shall have a minimum 1 inch (25.4 mm) air gap. To provide air circulation, the bottom and top edges, or only the side and top edges, or edges shall be left open. 7 Mineral wool batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot (lb/ft3) (128 kg/m3) and a minimum melting point of 1500°F (816°C). 8 Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1 British thermal unit inch per hour square foot degree Fahrenheit [Btu•in/(h•ft 2 •°F)] [0.1 W/(m•K)] or less. 9 There shall be not less than 1 inch (25.4 mm) between the appliance and the protector. In no case shall the clearance between the appliance and the combustible surface be reduced below that allowed in this table. 10 Clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable. 11 Listed single-wall connectors shall be installed in accordance with the terms of their listing and the manufacturer’s installation instructions.

2019 CALIFORNIA PLUMBING CODE 97

WATER HEATERS any other purpose or distributed to any other persons or parti es.

(1) For a draft hood-equipped appliance, in accor dance with Section 510.0.

(1) For a draft hood-equipped appliance, in accor dance with Section 510.0. (2) For a venting system for a single appliance with

a draft hood, the areas of the connector and the

(2) For a venting system for a single appliance with

a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall not exceed seven times the draft hood outlet area. (3) Other approved engineering methods. [NFPA

54:12.8.5(1)]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
    Overview
    1. 501.0 General.501.1 Applicability. The regulations of this cha…
    2. 503.2 Final Water Heater Inspection. This inspection
    3. 504.2 Vent. Water heaters of other than the direct-vent type
    4. 504.3 Clearance. The clearance requirements for water
    5. 504.4 Pressure-Limiting Devices. A water heater installation s…
    6. 504.5 Temperature-Limiting Devices. A water heater
    7. 504.6 Temperature, Pressure, and Vacuum Relief
    8. 505.2 Safety Devices. Storage-type water heaters and hot
    9. 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
    10. 505.4 Indirect-Fired Water Heaters. Indirect-fired water
    11. 506.0 Air for Combustion and Ventilation.506.1 General. Air fo…
    12. 506.2 Indoor Combustion Air. The required volume of
    13. 506.4 Outdoor Combustion Air. Outdoor combustion air
    14. 506.3 Indoor Opening Size and Location. Openings
    15. 506.8 Louvers, Grilles, and Screens. The required size
    16. 506.5 Combination Indoor and Outdoor CombustionAir. The use of…
    17. 506.9 Combustion Air Ducts. Combustion air ducts shall
    18. 506.6 Engineered Installations. Engineered combustion
    19. 506.7 Mechanical Combustion Air Supply. Where
    20. 507.2 Seismic Provisions. Water heaters shall be
    21. 507.3 Appliance Support. Appliances and equipment shall
    22. 507.4 Ground Support. A water heater supported from the
    23. 507.5 Drainage Pan. Where a water heater is located in an
    24. 507.6 Added or Converted Equipment or Appliances. When additio…
    25. 507.7 Types of Gases. The appliance shall be connected to
    26. 507.8 Safety Shutoff Devices for Unlisted LP-GasAppliance Used…
    27. 507.9 Use of Air or Oxygen Under Pressure. Where air
    28. 507.10 Protection of Gas Appliances from Fumes orGases other t…
    29. 507.11 Process Air. In addition to air needed for combustion i…
    30. 507.12 Flammable Vapors. Appliances shall not be
    31. 507.13 Installation in Residential Garages. Appliances
    32. 507.14 Installation in Commercial Garages. Appliances
    33. 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
    34. 507.16 Venting of Flue Gases. Appliances shall be vented
    35. 507.17 Extra Device or Attachment. No device or attachment sha…
    36. 507.18 Adequate Capacity of Piping. When additional
    37. 507.19 Avoiding Strain on Gas Piping. Appliances shall
    38. 507.20 Gas Appliance Pressure Regulators. Where the
    39. 507.21 Venting of Gas Appliance Pressure Regula-tors. Venting …
    40. 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
    41. 507.23 Combination of Appliances and Equipment. A
    42. 507.24 Installation Instructions. The installing agency
    43. 507.25 Protection of Outdoor Appliances. Appliances
    44. 507.26 Accessibility for Service. Appliances shall be
    45. 507.27 Clearance to Combustible Materials. Appliances and thei…
    46. 508.0 Appliances on Roofs.508.1 General. Appliances on roofs s…
    47. 508.2 Installation of Appliances on Roofs. Appliances
    48. 508.3 Appliances on Roofs. Appliances located on roofs
    49. 508.4 Appliances in Attics and Under-Floor Spaces.
    50. 509.2 Connection to Venting Systems. Except as permitted in Se…
    51. 509.3 Design and Construction. Venting systems shall
    52. 509.4 Type of Venting System to be Used. The type of
    53. 509.5 Masonry, Metal, and Factory-Built Chimneys.
    54. 509.6 Gas Vents. The installation of gas vents shall meet
    55. 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
    56. 509.8 Through-the-Wall Vent Termination. A mechanical draft ve…
    57. 509.9 Condensation Drain. Provision shall be made to
    58. 509.11 Vent Connectors for Category II, Category III,
    59. 509.12 Draft Hoods and Draft Controls. Vented appliances shall…
    60. 509.15 Obstructions. Devices that retard the flow of vent
    61. 509.13 Manually Operated Dampers. A manually operated damper s…
    62. 509.14 Automatically Operated Vent Dampers. An
    63. 510.1 Single Appliance Vent Table 510.1.2(1) through
    64. 510.2 Multiple Appliance Vent Table 510.2(1) throughTable 510.…
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR