Chapter 10 — TRAPS AND INTERCEPTORS
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Sections in this part
- 1001.2 Where Required. Each plumbing fixture shall be
- 1002.2 Fixture Traps.
- 1002.3 Change of Direction.
- 1002.4 Vent Pipe Opening. The vent pipe opening from
- 1003.0 Traps — Described.1003.1 General Requirements. Each trap, except for
- 1003.2 Slip Joint Fittings. A maximum of one approved
- 1003.3 Size. The size (nominal diameter) of a trap for a
- 1004.0 Traps.1004.1 Prohibited. No form of trap that depends for its seal
- 1004.2 Movable Parts. Bladders, check valves or another
- 1007.2 Trap Seal Primers. Potable water supply trap seal
- 1009.2 Approval.
- 1009.3 Design.
- 1009.4 Relief Vent. Interceptors (clarifiers) shall be so
- 1009.5 Location. Each interceptor (clarifier) cover shall be
- 1009.6 Maintenance of Interceptors. Interceptors shall
- 1009.7 Discharge.
- 1010.2 [AGR] Meat and Poultry Processing Plants.
- 1010.3 [AGR] Collection Centers and Facilities. All
- 1010.4 [AGR] Horse Meat and Pet Food Establish-ments.
- 1010.5 [AGR] Draining and Plumbing. There shall be
- 1014.0 Grease Interceptors.1014.1 General. Where it is determined by the Authority
- 1014.2 Hydromechanical Grease Interceptors.
- 1014.3 Gravity Grease Interceptors. Required gravity
- 1015.2 Components, Materials, and Equipment. FOG
- 1015.3 Sizing and Installation. FOG disposal systems
- 1015.4 Performance. FOG disposal systems shall produce
- 1015.5 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1015.6 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1016.0 Sand Interceptors.1016.1 Discharge. Where the discharge of a fixture or drain
- 1016.2 Authority Having Jurisdiction. Sand interceptors
- 1016.3 Construction and Size. Sand interceptors shall be
- 1016.4 Separate Use. Sand and similar interceptors for
- 1017.2 Design of Interceptors.
- 1017.0 Oil and Flammable Liquid Interceptors.1017.1 Interceptors Required.
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency |
**BSC ** |
BSC- CG |
SFM | 1 | 2 | 1-AC | **AC ** | SS |
SS/CC |
1 | 1R | 2 | 3 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
amended (amended sections listed below) |
**X ** | X | X | **X ** | **X ** | X | X | ||||||||||||||||
that are listed below |
|||||||||||||||||||||||
The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2019 CALIFORNIA PLUMBING CODE 201
202 2019 CALIFORNIA PLUMBING CODE
CHAPTER 10
TRAPS AND INTERCEPTORS
1001.0 General.1001.1 Applicability.¶
This chapter shall govern the materials, design, and installation of traps and interceptors.
1002.0 Traps Protected by Vent Pipes.1002.1 Vent Pipes.¶
Each plumbing fixture trap, except as otherwise provided in this code, shall be protected against siphonage, backpressure, and air circulation shall be assured throughout the drainage system using a vent pipe installed in accordance with the requirements of this code.
1005.0 Trap Seals.1005.1 General. Each fixture trap shall have a liquid seal of¶
not less than 2 inches (51 mm) and not more than 4 inches (102 mm), except where a deeper seal is found necessary by the Authority Having Jurisdiction. Traps shall be set true with respect to their liquid seals and, where necessary, they shall be protected from freezing.
1006.0 Floor Drain Traps.1006.1 General. Floor drains shall connect into a trap so¶
constructed that it can be readily cleaned and of a size to serve efficiently the purpose for which it is intended. The drain inlet shall be so located that it is in full view. Where subject to the reverse flow of sewage or liquid waste, such drains shall be equipped with an approved backwater valve.
1007.0 Trap Seal Protection.1007.1 General.¶
Floor drain or similar traps directly connected to the drainage system and subject to infrequent use shall be protected with a trap seal primer, except where not deemed necessary for safety or sanitation by the Authority Having Jurisdiction. Trap seal primers shall be accessible for maintenance.
1008.0 Building Traps.1008.1 General. Building traps shall not be installed except¶
where required by the Authority Having Jurisdiction. Each building trap where installed shall be provided with a cleanout and with a relieving vent or fresh-air intake on the inlet side of the trap, which needs not be larger than one-half the diameter of the drain to which it connects. Such relieving vent or fresh-air intake shall be carried above grade and terminate in a screened outlet located outside the building.
1009.0 Interceptors (Clarifiers) and Separators.1009.1 Where Required.¶
Interceptors (clarifiers) (including grease, oil, sand, solid interceptors, etc.) shall be required by the Authority Having Jurisdiction where they are necessary for the proper handling of liquid wastes containing grease, flammable wastes, sand, solids, acid or alkaline substances, or other ingredients harmful to the building drainage system, the public or private sewer, or to public or private sewage disposal.
1010.0 Slaughterhouses, Packing Establishments,¶
etc.1010.1 General. A fish, fowl, and animal slaughterhouse or establishment; a fish, fowl, and meat packing or curing establishment; a soap factory, tallow-rendering, fat-rendering, and a hide-curing establishment shall be connected to and shall drain or discharge into an approved grease interceptor (clarifier).
1011.0 Minimum Requirements for Auto Wash Racks.1011.1 General.¶
A private or public wash rack or floor or slab used for cleaning machinery or machine parts shall be adequately protected against storm or surface water and shall drain or discharge into an approved interceptor (clarifier).
1012.0 Commercial and Industrial Laundries.1012.1 General.¶
Laundry equipment in commercial and industrial buildings that do not have integral strainers shall discharge into an interceptor having a wire basket or similar device that is removable for cleaning and that will prevent passage into the drainage system of solids 1 ⁄2 of an inch (12.7 mm) or larger in maximum dimensions, such as string, rags, buttons, or other solid materials detrimental to the public sewerage system.
1013.0 Bottling Establishments.1013.1 General.¶
Bottling plants shall discharge their process wastes into an interceptor that will provide for the separation of broken glass or other solids, before discharging liquid wastes into the drainage system.
1015.0 FOG (Fats, Oils, and Greases) Disposal Sys-¶
tem.1015.1 Purpose. The purpose of this section is to provide the necessary criteria for the sizing, application, and installation of FOG disposal systems designated as a pretreatment or discharge water quality compliance strategy.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
▸Chapter 10 — TRAPS AND INTERCEPTORS
Overview- 1001.2 Where Required. Each plumbing fixture shall be
- 1002.2 Fixture Traps. Each fixture trap shall have a protectin…
- 1002.3 Change of Direction. A trap arm shall be permitted to c…
- 1002.4 Vent Pipe Opening. The vent pipe opening from
- 1003.0 Traps — Described.1003.1 General Requirements. Each tra…
- 1003.2 Slip Joint Fittings. A maximum of one approved
- 1003.3 Size. The size (nominal diameter) of a trap for a
- 1004.0 Traps.1004.1 Prohibited. No form of trap that depends f…
- 1004.2 Movable Parts. Bladders, check valves or another
- 1007.2 Trap Seal Primers. Potable water supply trap seal
- 1009.2 Approval. The size, type, and location of each intercep…
- 1009.3 Design. Interceptors (clarifiers) for sand and similar …
- 1009.4 Relief Vent. Interceptors (clarifiers) shall be so
- 1009.5 Location. Each interceptor (clarifier) cover shall be
- 1009.6 Maintenance of Interceptors. Interceptors shall
- 1009.7 Discharge. The waste pipe from oil and sand interceptor…
- 1010.2 [AGR] Meat and Poultry Processing Plants.
- 1010.3 [AGR] Collection Centers and Facilities. All
- 1010.4 [AGR] Horse Meat and Pet Food Establish-ments. There sh…
- 1010.5 [AGR] Draining and Plumbing. There shall be
- 1014.0 Grease Interceptors.1014.1 General. Where it is determi…
- 1014.2 Hydromechanical Grease Interceptors. Plumbing fixtures …
- 1014.3 Gravity Grease Interceptors. Required gravity
- 1015.2 Components, Materials, and Equipment. FOG
- 1015.3 Sizing and Installation. FOG disposal systems
- 1015.4 Performance. FOG disposal systems shall produce
- 1015.5 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1015.6 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1016.0 Sand Interceptors.1016.1 Discharge. Where the discharge…
- 1016.2 Authority Having Jurisdiction. Sand interceptors
- 1016.3 Construction and Size. Sand interceptors shall be
- 1016.4 Separate Use. Sand and similar interceptors for
- 1017.2 Design of Interceptors. Each manufactured interceptor t…
- 1017.0 Oil and Flammable Liquid Interceptors.1017.1 Intercepto…
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR