Chapter 10 — TRAPS AND INTERCEPTORS
1003.0 Traps — Described.1003.1 General Requirements. Each trap, except for
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
traps within an interceptor or similar device shall be selfcleaning. Traps for bathtubs, showers, lavatories, sinks, laundry tubs, floor drains, urinals, drinking fountains, dental units, and similar fixtures shall be of standard design, weight and shall be of ABS, cast-brass, cast-iron, lead, PP, PVC, or other approved material. An exposed and readily accessible drawncopper alloy tubing trap, not less than 17 B & S Gauge (0.045 inch) (1.143 mm), shall be permitted to be used on fixtures discharging domestic sewage. Exception: ( 1) Drawn-copper alloy tubing traps shall not be used for uri nals. Each trap shall have the manufacturer’s name
( 1) Drawn-copper alloy tubing traps shall not be used for uri nals. Each trap shall have the manufacturer’s name stamped legibly in the metal of the trap, and each tubing trap shall have the gauge of the tubing in addition to the manufacturer’s name. A trap shall have a smooth and uniform interior waterway. (2) [HCD 1 & HCD 2] Non-water supplied urinals conform-
ing to ASME A112.19.19-2016, Standard for Vitreous China
| TRAP ARM PIPE DIAMETER (inches) |
DISTANCE TRAP TO VENT MINIMUM (inches) |
LENGTH MAXIMUM (inches) |
|---|---|---|
Notes: 1 Maintain 1⁄4 inch per foot slope (20.8 mm/m). 2 The developed length between the trap of a water closet or similar fixture (measured from the top of the closet flange to the inner edge of the vent) and its vent shall not exceed 6 feet (1829 mm).
(2) [HCD 1 & HCD 2] Non-water supplied urinals conform-
ing to ASME A112.19.19-2016, Standard for Vitreous China Nonwater Urinals, or reference standards in Table 1701.1 for non-vitreous ceramic or plastic urinal fixtures.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
▸Chapter 10 — TRAPS AND INTERCEPTORS
Overview- 1001.2 Where Required. Each plumbing fixture shall be
- 1002.2 Fixture Traps. Each fixture trap shall have a protectin…
- 1002.3 Change of Direction. A trap arm shall be permitted to c…
- 1002.4 Vent Pipe Opening. The vent pipe opening from
- 1003.0 Traps — Described.1003.1 General Requirements. Each tra…
- 1003.2 Slip Joint Fittings. A maximum of one approved
- 1003.3 Size. The size (nominal diameter) of a trap for a
- 1004.0 Traps.1004.1 Prohibited. No form of trap that depends f…
- 1004.2 Movable Parts. Bladders, check valves or another
- 1007.2 Trap Seal Primers. Potable water supply trap seal
- 1009.2 Approval. The size, type, and location of each intercep…
- 1009.3 Design. Interceptors (clarifiers) for sand and similar …
- 1009.4 Relief Vent. Interceptors (clarifiers) shall be so
- 1009.5 Location. Each interceptor (clarifier) cover shall be
- 1009.6 Maintenance of Interceptors. Interceptors shall
- 1009.7 Discharge. The waste pipe from oil and sand interceptor…
- 1010.2 [AGR] Meat and Poultry Processing Plants.
- 1010.3 [AGR] Collection Centers and Facilities. All
- 1010.4 [AGR] Horse Meat and Pet Food Establish-ments. There sh…
- 1010.5 [AGR] Draining and Plumbing. There shall be
- 1014.0 Grease Interceptors.1014.1 General. Where it is determi…
- 1014.2 Hydromechanical Grease Interceptors. Plumbing fixtures …
- 1014.3 Gravity Grease Interceptors. Required gravity
- 1015.2 Components, Materials, and Equipment. FOG
- 1015.3 Sizing and Installation. FOG disposal systems
- 1015.4 Performance. FOG disposal systems shall produce
- 1015.5 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1015.6 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1016.0 Sand Interceptors.1016.1 Discharge. Where the discharge…
- 1016.2 Authority Having Jurisdiction. Sand interceptors
- 1016.3 Construction and Size. Sand interceptors shall be
- 1016.4 Separate Use. Sand and similar interceptors for
- 1017.2 Design of Interceptors. Each manufactured interceptor t…
- 1017.0 Oil and Flammable Liquid Interceptors.1017.1 Intercepto…
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR