Chapter 10 — TRAPS AND INTERCEPTORS
1014.0 Grease Interceptors.1014.1 General. Where it is determined by the Authority
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Having Jurisdiction that waste pretreatment is required, an approved type of grease interceptor(s) complies with ASME
A112.14.3, ASME A112.14.4, CSA B481, PDI G-101, or PDI G-102, and sized in accordance with Section 1014.2.1 or Section 1014.3.6, shall be installed in accordance with the manufacturer’s installation instructions to receive the drainage from fixtures or equipment that produce grease-laden waste located in areas of establishments where food is prepared, or other establishments where grease is introduced into the drainage or sewage system in quantities that can effect line stoppage or hinder sewage treatment or private sewage disposal systems. A combination of hydromechanical, gravity grease interceptors and engineered systems shall be allowed to meet this code and other applicable requirements of the Authority Having Jurisdiction where space or existing physical constraints of existing buildings necessitate such installations. A grease interceptor shall not be required for individual dwelling units or private living quarters. Water closets, urinals, and other plumbing fixtures conveying human waste shall not drain into or through the grease interceptor. 1014.1A [OSHPD 1, 1R, 2, 3, 4 & 5] The Authority Having Jurisdiction is the individual official, board, department or agency authorized to administer and enforce the sewage treatment system in the area of the location of the health facil- ity. 1014.1B [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors shall not be installed in food preparation area of the kitchens. 1014.1C [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors shall be installed outside of the kitchen area in location affording ease of maintenance and servicing.
1014.1.1 Trapped and Vented. Each fixture discharging into a grease interceptor shall be individually trapped and vented in an approved manner. 1014.1.2 Maintenance. Grease interceptors shall be maintained in efficient operating condition by periodic removal of the accumulated grease and latent material. No such collected grease shall be introduced into drainage piping or a public or private sewer. Where the Authority Having Jurisdiction determines that a grease interceptor is not being properly cleaned or maintained, the Authority Having Jurisdiction shall have the authority to mandate the installation of additional equipment or devices and to mandate a maintenance program. 1014.1.3 Food Waste Disposers and Dishwash-ers. No food waste disposer or dishwasher shall be connected to or discharge into a grease interceptor. Commercial food waste disposers shall be permitted to discharge directly into the building’s drainage system. Exception: Food waste disposers shall be permitted to discharge to grease interceptors that are designed to receive the discharge of food waste.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
▸Chapter 10 — TRAPS AND INTERCEPTORS
Overview- 1001.2 Where Required. Each plumbing fixture shall be
- 1002.2 Fixture Traps. Each fixture trap shall have a protectin…
- 1002.3 Change of Direction. A trap arm shall be permitted to c…
- 1002.4 Vent Pipe Opening. The vent pipe opening from
- 1003.0 Traps — Described.1003.1 General Requirements. Each tra…
- 1003.2 Slip Joint Fittings. A maximum of one approved
- 1003.3 Size. The size (nominal diameter) of a trap for a
- 1004.0 Traps.1004.1 Prohibited. No form of trap that depends f…
- 1004.2 Movable Parts. Bladders, check valves or another
- 1007.2 Trap Seal Primers. Potable water supply trap seal
- 1009.2 Approval. The size, type, and location of each intercep…
- 1009.3 Design. Interceptors (clarifiers) for sand and similar …
- 1009.4 Relief Vent. Interceptors (clarifiers) shall be so
- 1009.5 Location. Each interceptor (clarifier) cover shall be
- 1009.6 Maintenance of Interceptors. Interceptors shall
- 1009.7 Discharge. The waste pipe from oil and sand interceptor…
- 1010.2 [AGR] Meat and Poultry Processing Plants.
- 1010.3 [AGR] Collection Centers and Facilities. All
- 1010.4 [AGR] Horse Meat and Pet Food Establish-ments. There sh…
- 1010.5 [AGR] Draining and Plumbing. There shall be
- 1014.0 Grease Interceptors.1014.1 General. Where it is determi…
- 1014.2 Hydromechanical Grease Interceptors. Plumbing fixtures …
- 1014.3 Gravity Grease Interceptors. Required gravity
- 1015.2 Components, Materials, and Equipment. FOG
- 1015.3 Sizing and Installation. FOG disposal systems
- 1015.4 Performance. FOG disposal systems shall produce
- 1015.5 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1015.6 [OSHPD 1, 1R, 2, 3, 4 & 5] Grease interceptors
- 1016.0 Sand Interceptors.1016.1 Discharge. Where the discharge…
- 1016.2 Authority Having Jurisdiction. Sand interceptors
- 1016.3 Construction and Size. Sand interceptors shall be
- 1016.4 Separate Use. Sand and similar interceptors for
- 1017.2 Design of Interceptors. Each manufactured interceptor t…
- 1017.0 Oil and Flammable Liquid Interceptors.1017.1 Intercepto…
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR