Chapter 7 — SANITARY DRAINAGE
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Sections in this part
- 701.2 Drainage Piping. Materials for drainage piping shall
- 701.4 Continuous Wastes. Continuous wastes and fixture
- 701.5 Lead. (See Table 1701.1) Sheet lead shall comply with
- 701.6 Caulking Ferrules.
- 701.7 Soldering Bushings. Soldering bushings shall be
- 701.3 Drainage Fittings. Materials for drainage fittings
- 702.0 Fixture Unit Equivalents.702.1 Trap Size. The unit equivalent of plumbing fixtures
- 702.2 Intermittent Flow.
- 702.3 Continuous Flow. For a continuous flow into a
- 703.2 Maximum Number of Fixture Units. Table 703.2
- 703.3 Sizing per Appendix C. For alternate method of
- 704.2 Single Vertical Drainage Pipe. Two fixtures set
- 704.3 Commercial Sinks.
- 705.1 ABS and ABS Co-Extruded Plastic Pipe andJoints.
- 705.2 Cast-Iron Pipe and Joints. Joining methods for
- 705.3 Copper or Copper Alloy Pipe (DWV) andJoints.
- 705.4 Galvanized Steel Pipe and Joints.
- 705.5 Polyethylene (PE) Sewer Pipe. Polyethylene (PE)
- 705.6 PVC and PVC Co-Extruded Plastic Pipe andJoining Methods.
- 705.7 Stainless Steel Pipe and Joints.
- 705.8 Vitrified Clay Pipe and Joints. Joining methods
- 705.9 Special Joints.
- 705.10 Joints Between Various Materials. Joints
- 706.2 Horizontal to Vertical. Horizontal drainage lines,
- 706.3 Horizontal to Horizontal. Horizontal drainage lines
- 706.4 Vertical to Horizontal.
- 707.0 Cleanouts.707.1 Plug.
- 707.2 Approved. Each cleanout fitting and each cleanout
- 707.3 Watertight and Gastight. Cleanouts shall be
- 707.4 Location.
- 707.5 Cleaning. Each cleanout shall be installed so that it
- 707.6 Extension.
- 707.7 Interceptor. Each cleanout for an interceptor shall be
- 707.8 Access. Each cleanout, unless installed under an
- 707.9 Clearance. Each cleanout in piping 2 inches (50 mm)
- 707.10 Fittings. Cleanout fittings shall be not less in size
- 707.11 Pressure Drainage Systems. Cleanouts shall be
- 707.12 Countersunk Cleanout Plugs. Countersunk
- 707.13 Hubless Blind Plugs. Where a hubless blind plug
- 707.14 Trap Arms. Cleanouts for trap arms shall be installed
- 708.0 Grade of Horizontal Drainage Piping.708.1 General.
- 710.0 Drainage of Fixtures Located Below the Next
- 710.2 Sewage Discharge.
- 710.3 Sewage Ejector and Pumps. A sewage ejector or
- 710.4 Discharge Line.
- 710.5 Size of Building Drains and Sewers. Building
- 710.6 Backwater Valves. Backwater valves, gate valves,
- 710.7 Drainage and Venting Systems. The drainage and
- 710.8 Sump and Receiving Tank Construction. Sumps
- 710.9 Alarm.
- 710.10 Sump and Receiving Tank Covers and Vents.
- 710.11 Air Tanks. Air tanks shall be so proportioned as to be
- 710.12 Grinder Pump Ejector. Grinder pumps shall be
- 710.13 Macerating Toilet Systems and PumpedWaste Systems.
- 712.2 Water Test. The water test shall be applied to the
- 712.3 Air Test. The air test shall be made by attaching an
- 713.2 Private Sewage Disposal System.
- 713.3 Public Sewer.
- 713.4 Public Sewer Availability. The public sewer shall be
- 711.0 Suds Relief.711.1 General. Drainage connections shall not be made into
- 713.5 Permit. No permit shall be issued for the installation,
- 713.6 Lot. On every lot or premises hereafter connected to
- 713.7 Installation. In cities, counties, or both where the
- 714.2 Prohibited Water Discharge. No rain, surface, or
- 714.3 Prohibited Sewer Connection.
- 714.4 Commercial Food Waste Disposer.
- 714.5 Tanks.
- 715.2 Joining Methods and Materials. Joining methods
- 715.3 Existing Sewers. Replacement of existing building
- 717.2 [AGR] Meat and Poultry Processing Plants. The
- 718.2 Support. Building sewer piping shall be laid on a firm
- 718.3 Protection from Damage. No building sewer or
- 719.2 No Additional Cleanouts. Where a building sewer
- 719.3 Building Sewer Cleanouts. Required building
- 719.4 Cleaning. Each cleanout shall be installed so that it
- 719.5 Access. Cleanouts installed under concrete or asphalt
- 719.6 Manholes. Approved manholes shall be permitted to
- 720.0 Sewer and Water Pipes.720.1 General. Building sewers or drainage piping of clay
- 721.0 Location.721.1 Building Sewer. Except as provided in Section
- 721.2 Abutting Lot. Nothing contained in this code shall be
- 724.2 Toilet soil lines shall be separated from house drainage
- 726.2 Toilet soil lines shall be separated from house drainage
- 727.0 [OSHPD 1] Emergency Sanitary Drainage.727.1 For new acute care hospital buildings…
- 722.2 Cesspools, Septic Tanks, and Seepage Pits. A
- 722.3 Filling.
- 722.4 Ownership. No person owning or controlling a
- 722.5 Disposal Facilities. Where disposal facilities are
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
>
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency |
**BSC ** |
BSC- CG |
SFM | 1 | 2 | 1-AC | **AC ** | SS | SS/CC | 1 | 1R | 2 | 3 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
amended (amended sections listed below) |
**X ** | X | X | X | X | **X ** | **X ** | X | X | ||||||||||||||
that are listed below |
|||||||||||||||||||||||
The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2019 CALIFORNIA PLUMBING CODE 173
174 2019 CALIFORNIA PLUMBING CODE
CHAPTER 7
SANITARY DRAINAGE
Part I – Drainage Systems.
701.0 General.701.1 Applicability. This chapter shall govern the materials,¶
design, and installation of sanitary drainage systems and building sewers.
703.0 Size of Drainage Piping.703.1 Minimum Size.¶
The minimum sizes of vertical, horizontal, or both drainage piping shall be determined from the total of fixture units connected thereto, and additionally, in the case of vertical drainage pipes, in accordance with their length.
704.0 Fixture Connections (Drainage).704.1 Inlet Fittings.¶
Drainage piping shall be provided with approved inlet fittings for fixture connections, correctly located according to the size and type of fixture proposed to be connected.
705.0 Joints and Connections.¶
706.0 Changes in Direction of Drainage Flow.706.1 Approved Fittings.¶
Changes in the direction of drainage piping shall be made by the appropriate use of approved fittings and shall be of the angles presented by a one-sixteenth bend, one-eighth bend, or one-sixth bend, or other approved fittings of equivalent sweep.
709.0 Gravity Drainage Required.709.1 General. Where practicable, plumbing fixtures shall¶
be drained to the public sewer or private sewage disposal system by gravity.
712.0 Testing.712.1 Media.¶
The piping of the plumbing, drainage, and venting systems shall be tested with water or air except that plastic pipe shall not be tested with air. The Authority Having Jurisdiction shall be permitted to require the removal of cleanouts, etc., to ascertain whether the pressure has reached all parts of the system. After the plumbing fixtures have been set and their traps filled with water, they shall be submitted to a final test.
713.0 Sewer Required.713.1 Where Required.¶
A building in which plumbing fixtures are installed and premises having drainage piping thereon shall have a connection to a public or private sewer, except as provided in Section 713.2, and Section 713.4.
714.0 Damage to Public Sewer or Private Sewage¶
Disposal System.714.1 Unlawful Practices. It shall be unlawful for a person to deposit, by means whatsoever, into a plumbing fixture, floor drain, interceptor, sump, receptor, or device which is connected to a drainage system, public sewer, private sewer, septic tank, or cesspool, ashes; cinders; solids; rags; flammable, poisonous, or explosive liquids or gases; oils; grease; and whatsoever that is capable of causing damage to the public sewer, private sewer, or private sewage disposal system.
718.0 Grade, Support, and Protection of Building¶
Sewers.718.1 Slope. Building sewers shall be run in practical alignment and at a uniform slope of not less than 1 ⁄4 inch per foot (20.8 mm/m) toward the point of disposal. Exception: Where approved by the Authority Having Jurisdiction and where it is impractical, due to the depth of the
715.0 Building Sewer Materials.715.1 Materials. The building sewer, beginning 2 feet (610¶
mm) from a building or structure, shall be of such materials as prescribed in this code.
716.0 Markings.716.1 General. Pipe, brick, block, prefabricated septic tanks,¶
prefabricated septic tank or seepage pit covers, or other parts or appurtenances incidental to the installation of building sewers or private sewage disposal systems shall be in accordance with the approval requirements of Chapter 3 of this code.
717.0 Size of Building Sewers.717.1 General. The minimum size of a building sewer shall¶
be determined on the basis of the total number of fixture units drained by such sewer, in accordance with Table 717.1. No building sewer shall be smaller than the building drain.
For alternate methods of sizing building sewers, see Appendix C.
719.0 Cleanouts.719.1 Locations.¶
Cleanouts shall be placed inside the building near the connection between the building drain and the building sewer or installed outside the building at the lower end of the building drain and extended to grade.
Additional building sewer cleanouts shall be installed at intervals not to exceed 100 feet (30 480 mm) in straight runs and for each aggregate horizontal change in direction exceeding 135 degrees (2.36 rad).
723.0 Building Sewer Test.723.1 General. Building sewers shall be tested by plugging¶
the end of the building sewer at its points of connection to the public sewer or private sewage disposal system and completely filling the building sewer with water from the lowest to the highest point thereof, or by approved equivalent lowpressure air test. Plastic DWV piping systems shall not be tested by the air test method. The building sewer shall be watertight.
724.0 [AGR] Meat and Poultry Processing Plant¶
Drainage.724.1 The drainage and plumbing systems must permit the quick runoff of all water from plant buildings, and of surface water around the plant buildings, and of surface water around the plant and on the premises; and all such water shall be dis- posed of in such a manner as to prevent a nuisance or health hazard.
725.0 [AGR] Collection Center and FacilitiesDrainage.¶
Drainage and plumbing systems shall meet the requirements of Section 724.1.
726.0 [AGR] Drainage and Plumbing, General.726.1 The outer premises of every official…¶
including docks, areas where cars and other vehicles are loaded, driveways, approaches, yards, pens and alleys, shall be drained.
722.0 Abandoned Sewers and Sewage Disposal¶
Facilities.722.1 Building (House) Sewer. An abandoned building (house) sewer, or part thereof, shall be plugged or capped in an approved manner within 5 feet (1524 mm) of the property line.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
▸Chapter 7 — SANITARY DRAINAGE
Overview- 701.2 Drainage Piping. Materials for drainage piping shall
- 701.4 Continuous Wastes. Continuous wastes and fixture
- 701.5 Lead. (See Table 1701.1) Sheet lead shall comply with
- 701.6 Caulking Ferrules. Caulking ferrules shall be manufactur…
- 701.7 Soldering Bushings. Soldering bushings shall be
- 701.3 Drainage Fittings. Materials for drainage fittings
- 702.0 Fixture Unit Equivalents.702.1 Trap Size. The unit equiv…
- 702.2 Intermittent Flow. Drainage fixture units for intermitte…
- 702.3 Continuous Flow. For a continuous flow into a
- 703.2 Maximum Number of Fixture Units. Table 703.2
- 703.3 Sizing per Appendix C. For alternate method of
- 704.2 Single Vertical Drainage Pipe. Two fixtures set
- 704.3 Commercial Sinks. Pot sinks, scullery sinks, dishwashing…
- 705.1 ABS and ABS Co-Extruded Plastic Pipe andJoints. Joining …
- 705.2 Cast-Iron Pipe and Joints. Joining methods for
- 705.3 Copper or Copper Alloy Pipe (DWV) andJoints. Joining met…
- 705.4 Galvanized Steel Pipe and Joints. Joining methods for ga…
- 705.5 Polyethylene (PE) Sewer Pipe. Polyethylene (PE)
- 705.6 PVC and PVC Co-Extruded Plastic Pipe andJoining Methods.…
- 705.7 Stainless Steel Pipe and Joints. Joining methods for sta…
- 705.8 Vitrified Clay Pipe and Joints. Joining methods
- 705.9 Special Joints. Special joints shall comply with Section…
- 705.10 Joints Between Various Materials. Joints
- 706.2 Horizontal to Vertical. Horizontal drainage lines,
- 706.3 Horizontal to Horizontal. Horizontal drainage lines
- 706.4 Vertical to Horizontal. Vertical drainage lines connecti…
- 707.0 Cleanouts.707.1 Plug. Each cleanout fitting for cast-iro…
- 707.2 Approved. Each cleanout fitting and each cleanout
- 707.3 Watertight and Gastight. Cleanouts shall be
- 707.4 Location. Each horizontal drainage pipe shall be provide…
- 707.5 Cleaning. Each cleanout shall be installed so that it
- 707.6 Extension. Each cleanout extension shall be considered a…
- 707.7 Interceptor. Each cleanout for an interceptor shall be
- 707.8 Access. Each cleanout, unless installed under an
- 707.9 Clearance. Each cleanout in piping 2 inches (50 mm)
- 707.10 Fittings. Cleanout fittings shall be not less in size
- 707.11 Pressure Drainage Systems. Cleanouts shall be
- 707.12 Countersunk Cleanout Plugs. Countersunk
- 707.13 Hubless Blind Plugs. Where a hubless blind plug
- 707.14 Trap Arms. Cleanouts for trap arms shall be installed
- 708.0 Grade of Horizontal Drainage Piping.708.1 General. Horiz…
- 710.0 Drainage of Fixtures Located Below the Next
- 710.2 Sewage Discharge. Drainage piping serving fixtures that …
- 710.3 Sewage Ejector and Pumps. A sewage ejector or
- 710.4 Discharge Line. The discharge line from such ejector, pu…
- 710.5 Size of Building Drains and Sewers. Building
- 710.6 Backwater Valves. Backwater valves, gate valves,
- 710.7 Drainage and Venting Systems. The drainage and
- 710.8 Sump and Receiving Tank Construction. Sumps
- 710.9 Alarm. Such sumps and receiving tanks shall be automatic…
- 710.10 Sump and Receiving Tank Covers and Vents.
- 710.11 Air Tanks. Air tanks shall be so proportioned as to be
- 710.12 Grinder Pump Ejector. Grinder pumps shall be
- 710.13 Macerating Toilet Systems and PumpedWaste Systems. Fixt…
- 712.2 Water Test. The water test shall be applied to the
- 712.3 Air Test. The air test shall be made by attaching an
- 713.2 Private Sewage Disposal System. Where no public sewer in…
- 713.3 Public Sewer. Within the limits prescribed by Section 71…
- 713.4 Public Sewer Availability. The public sewer shall be
- 711.0 Suds Relief.711.1 General. Drainage connections shall no…
- 713.5 Permit. No permit shall be issued for the installation,
- 713.6 Lot. On every lot or premises hereafter connected to
- 713.7 Installation. In cities, counties, or both where the
- 714.2 Prohibited Water Discharge. No rain, surface, or
- 714.3 Prohibited Sewer Connection. No cesspool, septic tank, s…
- 714.4 Commercial Food Waste Disposer. The Authority Having Jur…
- 714.5 Tanks. An approved type, watertight sewage or wastewater…
- 715.2 Joining Methods and Materials. Joining methods
- 715.3 Existing Sewers. Replacement of existing building
- 717.2 [AGR] Meat and Poultry Processing Plants. The
- 718.2 Support. Building sewer piping shall be laid on a firm
- 718.3 Protection from Damage. No building sewer or
- 719.2 No Additional Cleanouts. Where a building sewer
- 719.3 Building Sewer Cleanouts. Required building
- 719.4 Cleaning. Each cleanout shall be installed so that it
- 719.5 Access. Cleanouts installed under concrete or asphalt
- 719.6 Manholes. Approved manholes shall be permitted to
- 720.0 Sewer and Water Pipes.720.1 General. Building sewers or …
- 721.0 Location.721.1 Building Sewer. Except as provided in Sec…
- 721.2 Abutting Lot. Nothing contained in this code shall be
- 724.2 Toilet soil lines shall be separated from house drainage
- 726.2 Toilet soil lines shall be separated from house drainage
- 727.0 [OSHPD 1] Emergency Sanitary Drainage.727.1 For new acut…
- 722.2 Cesspools, Septic Tanks, and Seepage Pits. A
- 722.3 Filling. The top cover or arch over the cesspool, septic…
- 722.4 Ownership. No person owning or controlling a
- 722.5 Disposal Facilities. Where disposal facilities are
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR