506.3 Indoor Opening Size and Location. Openings
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
used to connect indoor spaces shall be sized and located in accordance with the following: (1) Each opening shall have a free area of not less than 1
square inch per 1000 Btu/h (0.002 m 2 /kW) of the total
Each opening shall have a free area of not less than 1
square inch per 1000 Btu/h (0.002 m 2 /kW) of the total input rating of appliances in the space, but not less than 100 square inches (0.065 m 2 ). One opening shall commence within 12 inches (305 mm) of the top of the enclosure, and one opening shall commence within 12 inches (305 mm) of the bottom of the enclosure (see Figure 506.3). The dimension of air openings shall be not less than 3 inches (76 mm).
FIGURE 506.3 COMBUSTION AIR FROM ADJACENT INDOOR SPACES
THROUGH INDOOR COMBUSTION AIR OPENINGS
[NFPA 54: FIGURE A.9.3.2.3(1)]
(2) Where communicating with the outdoors through
horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2000 Btu/h (0.001 m 2 /kW) of total input rating of all appliances in the enclosure. [See Figure 506.4.1(3)] [NFPA 54:9.3.3.1]
2019 CALIFORNIA PLUMBING CODE 83
WATER HEATERS any other purpose or distributed to any other persons or parti es.
» »
FIGURE 506.4.1(1) COMBUSTION AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPACE AND
OUTLET AIR TO VENTILATED ATTIC
[NFPA 54: FIGURE A.9.3.3.1(1)(a)]
FIGURE 506.4.1(2) COMBUSTION AIR FROM OUTDOORS
THROUGH VENTILATED ATTIC
[NFPA 54: FIGURE A.9.3.3.1(1)(b)]
FIGURE 506.4.1(3) COMBUSTION AIR FROM OUTDOORS THROUGH HORIZONTAL DUCTS
[NFPA 54: FIGURE A.9.3.3.1(2)]
FIGURE 506.4.2 COMBUSTION AIR FROM OUTDOORS THROUGH
SINGLE COMBUSTION AIR OPENING
[NFPA 54: FIGURE A.9.3.3.2]
«
84 2019 CALIFORNIA PLUMBING CODE
WATER HEATERS
506.4.2 One Permanent Opening Method. One permanent opening, commencing within 12 inches (305 mm) of the top of the enclosure, shall be provided. The appliance shall have clearances of at least 1 inch (25.4 mm) from the sides and back and 6 inches (152 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors (see Figure 506.4.2) and shall have a minimum free area of the following:
(1) One square inch per 3000 Btu/h (0.0007 m 2 /kW) of
the total input rating of all appliances located in the
(1) One square inch per 3000 Btu/h (0.0007 m 2 /kW) of
the total input rating of all appliances located in the enclosure. (2) Not less than the sum of the areas of all vent con nectors in the space. [NFPA 54:9.3.3.2]
506.7.3 Specified Combustion Air. Where combustion air is provided by the building’s mechanical ventilation system, the system shall provide the specified combustion air rate in addition to the required ventilation air. [NFPA 54:9.3.6.3]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
▸Chapter 5 — WATER HEATERS
Overview- 501.0 General.501.1 Applicability. The regulations of this cha…
- 503.2 Final Water Heater Inspection. This inspection
- 504.2 Vent. Water heaters of other than the direct-vent type
- 504.3 Clearance. The clearance requirements for water
- 504.4 Pressure-Limiting Devices. A water heater installation s…
- 504.5 Temperature-Limiting Devices. A water heater
- 504.6 Temperature, Pressure, and Vacuum Relief
- 505.2 Safety Devices. Storage-type water heaters and hot
- 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
- 505.4 Indirect-Fired Water Heaters. Indirect-fired water
- 506.0 Air for Combustion and Ventilation.506.1 General. Air fo…
- 506.2 Indoor Combustion Air. The required volume of
- 506.4 Outdoor Combustion Air. Outdoor combustion air
- 506.3 Indoor Opening Size and Location. Openings
- 506.8 Louvers, Grilles, and Screens. The required size
- 506.5 Combination Indoor and Outdoor CombustionAir. The use of…
- 506.9 Combustion Air Ducts. Combustion air ducts shall
- 506.6 Engineered Installations. Engineered combustion
- 506.7 Mechanical Combustion Air Supply. Where
- 507.2 Seismic Provisions. Water heaters shall be
- 507.3 Appliance Support. Appliances and equipment shall
- 507.4 Ground Support. A water heater supported from the
- 507.5 Drainage Pan. Where a water heater is located in an
- 507.6 Added or Converted Equipment or Appliances. When additio…
- 507.7 Types of Gases. The appliance shall be connected to
- 507.8 Safety Shutoff Devices for Unlisted LP-GasAppliance Used…
- 507.9 Use of Air or Oxygen Under Pressure. Where air
- 507.10 Protection of Gas Appliances from Fumes orGases other t…
- 507.11 Process Air. In addition to air needed for combustion i…
- 507.12 Flammable Vapors. Appliances shall not be
- 507.13 Installation in Residential Garages. Appliances
- 507.14 Installation in Commercial Garages. Appliances
- 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
- 507.16 Venting of Flue Gases. Appliances shall be vented
- 507.17 Extra Device or Attachment. No device or attachment sha…
- 507.18 Adequate Capacity of Piping. When additional
- 507.19 Avoiding Strain on Gas Piping. Appliances shall
- 507.20 Gas Appliance Pressure Regulators. Where the
- 507.21 Venting of Gas Appliance Pressure Regula-tors. Venting …
- 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
- 507.23 Combination of Appliances and Equipment. A
- 507.24 Installation Instructions. The installing agency
- 507.25 Protection of Outdoor Appliances. Appliances
- 507.26 Accessibility for Service. Appliances shall be
- 507.27 Clearance to Combustible Materials. Appliances and thei…
- 508.0 Appliances on Roofs.508.1 General. Appliances on roofs s…
- 508.2 Installation of Appliances on Roofs. Appliances
- 508.3 Appliances on Roofs. Appliances located on roofs
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.2 Connection to Venting Systems. Except as permitted in Se…
- 509.3 Design and Construction. Venting systems shall
- 509.4 Type of Venting System to be Used. The type of
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents. The installation of gas vents shall meet
- 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
- 509.8 Through-the-Wall Vent Termination. A mechanical draft ve…
- 509.9 Condensation Drain. Provision shall be made to
- 509.11 Vent Connectors for Category II, Category III,
- 509.12 Draft Hoods and Draft Controls. Vented appliances shall…
- 509.15 Obstructions. Devices that retard the flow of vent
- 509.13 Manually Operated Dampers. A manually operated damper s…
- 509.14 Automatically Operated Vent Dampers. An
- 510.1 Single Appliance Vent Table 510.1.2(1) through
- 510.2 Multiple Appliance Vent Table 510.2(1) throughTable 510.…
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR