506.3 Indoor Opening Size and Location. Openings

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

used to connect indoor spaces shall be sized and located in accordance with the following: (1) Each opening shall have a free area of not less than 1

square inch per 1000 Btu/h (0.002 m 2 /kW) of the total

Each opening shall have a free area of not less than 1

square inch per 1000 Btu/h (0.002 m 2 /kW) of the total input rating of appliances in the space, but not less than 100 square inches (0.065 m 2 ). One opening shall commence within 12 inches (305 mm) of the top of the enclosure, and one opening shall commence within 12 inches (305 mm) of the bottom of the enclosure (see Figure 506.3). The dimension of air openings shall be not less than 3 inches (76 mm).

FIGURE 506.3 COMBUSTION AIR FROM ADJACENT INDOOR SPACES

THROUGH INDOOR COMBUSTION AIR OPENINGS

[NFPA 54: FIGURE A.9.3.2.3(1)]

(2) Where communicating with the outdoors through

horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2000 Btu/h (0.001 m 2 /kW) of total input rating of all appliances in the enclosure. [See Figure 506.4.1(3)] [NFPA 54:9.3.3.1]

2019 CALIFORNIA PLUMBING CODE 83

WATER HEATERS any other purpose or distributed to any other persons or parti es.

» »

FIGURE 506.4.1(1) COMBUSTION AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPACE AND

OUTLET AIR TO VENTILATED ATTIC

[NFPA 54: FIGURE A.9.3.3.1(1)(a)]

FIGURE 506.4.1(2) COMBUSTION AIR FROM OUTDOORS

THROUGH VENTILATED ATTIC

[NFPA 54: FIGURE A.9.3.3.1(1)(b)]

FIGURE 506.4.1(3) COMBUSTION AIR FROM OUTDOORS THROUGH HORIZONTAL DUCTS

[NFPA 54: FIGURE A.9.3.3.1(2)]

FIGURE 506.4.2 COMBUSTION AIR FROM OUTDOORS THROUGH

SINGLE COMBUSTION AIR OPENING

[NFPA 54: FIGURE A.9.3.3.2]

«

84 2019 CALIFORNIA PLUMBING CODE

WATER HEATERS

506.4.2 One Permanent Opening Method. One permanent opening, commencing within 12 inches (305 mm) of the top of the enclosure, shall be provided. The appliance shall have clearances of at least 1 inch (25.4 mm) from the sides and back and 6 inches (152 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors (see Figure 506.4.2) and shall have a minimum free area of the following:

(1) One square inch per 3000 Btu/h (0.0007 m 2 /kW) of

the total input rating of all appliances located in the

(1) One square inch per 3000 Btu/h (0.0007 m 2 /kW) of

the total input rating of all appliances located in the enclosure. (2) Not less than the sum of the areas of all vent con nectors in the space. [NFPA 54:9.3.3.2]

506.7.3 Specified Combustion Air. Where combustion air is provided by the building’s mechanical ventilation system, the system shall provide the specified combustion air rate in addition to the required ventilation air. [NFPA 54:9.3.6.3]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
    Overview
    1. 501.0 General.501.1 Applicability. The regulations of this cha…
    2. 503.2 Final Water Heater Inspection. This inspection
    3. 504.2 Vent. Water heaters of other than the direct-vent type
    4. 504.3 Clearance. The clearance requirements for water
    5. 504.4 Pressure-Limiting Devices. A water heater installation s…
    6. 504.5 Temperature-Limiting Devices. A water heater
    7. 504.6 Temperature, Pressure, and Vacuum Relief
    8. 505.2 Safety Devices. Storage-type water heaters and hot
    9. 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
    10. 505.4 Indirect-Fired Water Heaters. Indirect-fired water
    11. 506.0 Air for Combustion and Ventilation.506.1 General. Air fo…
    12. 506.2 Indoor Combustion Air. The required volume of
    13. 506.4 Outdoor Combustion Air. Outdoor combustion air
    14. 506.3 Indoor Opening Size and Location. Openings
    15. 506.8 Louvers, Grilles, and Screens. The required size
    16. 506.5 Combination Indoor and Outdoor CombustionAir. The use of…
    17. 506.9 Combustion Air Ducts. Combustion air ducts shall
    18. 506.6 Engineered Installations. Engineered combustion
    19. 506.7 Mechanical Combustion Air Supply. Where
    20. 507.2 Seismic Provisions. Water heaters shall be
    21. 507.3 Appliance Support. Appliances and equipment shall
    22. 507.4 Ground Support. A water heater supported from the
    23. 507.5 Drainage Pan. Where a water heater is located in an
    24. 507.6 Added or Converted Equipment or Appliances. When additio…
    25. 507.7 Types of Gases. The appliance shall be connected to
    26. 507.8 Safety Shutoff Devices for Unlisted LP-GasAppliance Used…
    27. 507.9 Use of Air or Oxygen Under Pressure. Where air
    28. 507.10 Protection of Gas Appliances from Fumes orGases other t…
    29. 507.11 Process Air. In addition to air needed for combustion i…
    30. 507.12 Flammable Vapors. Appliances shall not be
    31. 507.13 Installation in Residential Garages. Appliances
    32. 507.14 Installation in Commercial Garages. Appliances
    33. 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
    34. 507.16 Venting of Flue Gases. Appliances shall be vented
    35. 507.17 Extra Device or Attachment. No device or attachment sha…
    36. 507.18 Adequate Capacity of Piping. When additional
    37. 507.19 Avoiding Strain on Gas Piping. Appliances shall
    38. 507.20 Gas Appliance Pressure Regulators. Where the
    39. 507.21 Venting of Gas Appliance Pressure Regula-tors. Venting …
    40. 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
    41. 507.23 Combination of Appliances and Equipment. A
    42. 507.24 Installation Instructions. The installing agency
    43. 507.25 Protection of Outdoor Appliances. Appliances
    44. 507.26 Accessibility for Service. Appliances shall be
    45. 507.27 Clearance to Combustible Materials. Appliances and thei…
    46. 508.0 Appliances on Roofs.508.1 General. Appliances on roofs s…
    47. 508.2 Installation of Appliances on Roofs. Appliances
    48. 508.3 Appliances on Roofs. Appliances located on roofs
    49. 508.4 Appliances in Attics and Under-Floor Spaces.
    50. 509.2 Connection to Venting Systems. Except as permitted in Se…
    51. 509.3 Design and Construction. Venting systems shall
    52. 509.4 Type of Venting System to be Used. The type of
    53. 509.5 Masonry, Metal, and Factory-Built Chimneys.
    54. 509.6 Gas Vents. The installation of gas vents shall meet
    55. 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
    56. 509.8 Through-the-Wall Vent Termination. A mechanical draft ve…
    57. 509.9 Condensation Drain. Provision shall be made to
    58. 509.11 Vent Connectors for Category II, Category III,
    59. 509.12 Draft Hoods and Draft Controls. Vented appliances shall…
    60. 509.15 Obstructions. Devices that retard the flow of vent
    61. 509.13 Manually Operated Dampers. A manually operated damper s…
    62. 509.14 Automatically Operated Vent Dampers. An
    63. 510.1 Single Appliance Vent Table 510.1.2(1) through
    64. 510.2 Multiple Appliance Vent Table 510.2(1) throughTable 510.…
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.