509.9 Condensation Drain. Provision shall be made to
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
collect and dispose of condensate from venting systems serving Category II and Category IV appliances and noncategorized condensing appliances in accordance with Section 509.8.3. [NFPA 54:12.10.1] 509.9.1 Local Experience. Where local experience indicates that condensation is a problem, provision shall be made to drain off and dispose of condensate from venting systems serving Category I and Category III appliances in accordance with Section 509.8.3. [NFPA 54:12.10.2] A vent connector shall be used to connect an appliance to a 509.10 Vent Connectors for Category I Appliances. gas vent, chimney, or single-wall metal pipe, except where the gas vent, chimney, or single-wall metal pipe is directly connected to the appliance. [NFPA 54:12.11.1]
(b) Galvanized sheet steel not less than 0.018
of an inch (0.457 mm) thick. (c) Aluminum (1100 or 3003 alloy or equiva lent) sheet not less than 0.027 of an inch
(c) Aluminum (1100 or 3003 alloy or equiva lent) sheet not less than 0.027 of an inch (0.686 mm) thick. (d) Stainless steel sheet not less than 0.012 of
an inch (0.305 mm) thick.
(d) Stainless steel sheet not less than 0.012 of
an inch (0.305 mm) thick. (e) Smooth interior wall metal pipe having
resistance to heat and corrosion equal to or
(e) Smooth interior wall metal pipe having
resistance to heat and corrosion equal to or greater than that of Section 509.10.1.2(1)(b), Section 509.10.1.2(1)(c), or Section 509.10.1.2(1)(d). (f) A listed vent connector. (2) Vent connectors shall not be covered with insu lation.
509.10.1 Materials. A vent connector shall be made of noncombustible, corrosion-resistant material capable of withstanding the vent gas temperature produced by the appliance and of a thickness to withstand physical damage. [NFPA 54:12.11.2.1]
509.10.1.1 Unconditioned Area. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through an unconditioned area, attic or crawl space, that portion of the vent connector shall be listed
(2) Vent connectors shall not be covered with insu lation. Exception: Listed insulated vent connectors shall be installed in accordance with the manufacturer’s installation instructions. [NFPA 54:12.11.2.3] 509.10.1.3 Non-Residential Low-Heat Appli-ances. A vent connector for a non-residential lowheat appliance shall be a factory-built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 509.10.1.3. Factory-built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. [NFPA 54:12.11.2.4] 509.10.1.4 Medium-Heat Appliances. Vent connectors for medium-heat appliances shall be constructed of factory-built, medium-heat chimney sections or steel of a thickness not less than that specified in Table 509.10.1.4 and shall comply with the following: (1) A steel vent connector for an appliance with a
vent gas temperature in excess of 1000°F
A steel vent connector for an appliance with a
vent gas temperature in excess of 1000°F (538°C) measured at the entrance to the connector shall be lined with medium-duty fire brick or the equivalent.
2019 CALIFORNIA PLUMBING CODE 99
WATER HEATERS any other purpose or distributed to any other persons or parti es.
(2) The lining shall be at least 2 1 ⁄2 inches (64 mm)
thick for a vent connector having a diameter or
(2) The lining shall be at least 2 1 ⁄2 inches (64 mm)
thick for a vent connector having a diameter or greatest cross-sectional dimension of 18 inches (457 mm) or less. (3) The lining shall be at least 4 1 ⁄2 inches (114 mm)
thick laid on the 4 1 ⁄2 inches (114 mm) bed for a
(3) The lining shall be at least 4 1 ⁄2 inches (114 mm)
thick laid on the 4 1 ⁄2 inches (114 mm) bed for a vent connector having a diameter or greatest cross-sectional dimension greater than 18 inches (457 mm). (4) Factory-built chimney sections, if employed,
shall be joined together in accordance with the
limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. [NFPA 54:12.11.3.7]
TABLE 509.10.1.3 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT
CONNECTORS FOR LOW-HEAT APPLIANCES
[NFPA 54: TABLE 12.11.2.4]
(4) Factory-built chimney sections, if employed,
shall be joined together in accordance with the chimney manufacturer’s instructions. [NFPA 54:12.11.2.5] 509.10.2 Size of Vent Connector. A vent connector for an appliance with a single draft hood or for a Category I fan-assisted combustion system appliance shall be sized and installed in accordance with Section 510.0 or other approved engineering methods. [NFPA 54:12.11.3.1] 509.10.2.1 Manifold. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternative method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets, and the vent connectors shall have a minimum 1 foot (305 mm) rise. [NFPA 54:12.11.3.2] 509.10.2.2 Size. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 510.0 or other approved engineering methods. [NFPA 54:12.11.3.3]
| DIAMETER OF CONNECTOR (inches) |
MINIMUM THICKNESS (inches) |
|---|---|
| TABLE 509.10.1.4 MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM-HEAT APPLIANCES [NFPA 54: TABLE 12.11.2.5] | ||
|---|---|---|
| VENT CONNECTOR SIZE | VENT CONNECTOR SIZE | VENT CONNECTOR SIZE |
| DIAMETER (inches) |
AREA (square inches) |
MINIMUM THICKNESS (inches) |
As an alternative method applicable where the appliances are draft-hood-equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. [NFPA 54:12.11.3.4] 509.10.2.3 Height. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highest level consistent with available headroom and clearance to combustible material and sized in accordance with Section 510.0 or other approved engineering methods.
[NFPA 54:12.11.3.5]
As an alternative method applicable only where there are two draft hood-equipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 50 percent of the area of the smaller flue collar outlet.
[NFPA 54:12.11.3.6] 509.10.2.4 Size Increase. Where the size of a vent connector is increased to overcome installation
509.10.3 Two or More Appliances Connected to aSingle Vent. Where two or more openings are provided into one chimney flue or vent, either of the following shall apply: (1) The openings shall be at different levels. (2) The connectors shall be attached to the vertical por tion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the vertical. [NFPA 54:12.11.4.1] 509.10.3.1 Height of Connector. Where two or more vent connectors enter a common vent, chimney flue, or single-wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible material. [NFPA 54:12.11.4.2] 509.10.3.2 Pressure. Vent connectors serving Category I appliances shall not be connected to a portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or Category IV appliances. [NFPA 54:12.11.4.3] 509.10.4 Clearance. Minimum clearances from vent connectors to combustible material shall comply with Table 509.7.3.4(1).
100 2019 CALIFORNIA PLUMBING CODE
WATER HEATERS
Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 509.7.3.4(2). [NFPA 54:12.11.5] 509.10.5 Joints. Joints between sections of connector piping and connections to flue collars or draft hood outlets shall be fastened in accordance with one of the following methods: (1) Sheet metal screws. (2) Vent connectors of listed vent material assembled
and connected to flue collars or draft hood outlets in
(2) Vent connectors of listed vent material assembled
and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. (3) Other approved means. [NFPA 54:12.11.6] 509.10.6 Slope. A vent connector shall be installed without any dips or sags and shall slope upward toward the vent or chimney at least 1 ⁄4 inch per foot (20.8 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with appliance and draft system manufacturer’s instructions. [NFPA 54:12.11.7] 509.10.7 Length of Vent Connector. The length of vent connectors shall comply with Section 509.10.7.1 or Section 509.10.7.2.
509.10.11 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace unless the fireplace flue opening is permanently sealed. [NFPA 54:12.11.12] 509.10.12 Passage through Ceilings, Floors, or Walls. A vent connector shall not pass through a ceiling, floor, or fire-resistance-rated wall. A single-wall metal pipe connector shall not pass through an interior wall. Exception: Vent connectors made of listed Type B or Type L vent material and serving listed appliances with draft hoods and other appliances listed for use with Type B gas vents that pass through walls or partitions constructed of combustible material shall be installed with not less than the listed clearance to combustible material.
509.10.7.1 Single Wall Connector. The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent except for engineered systems. [NFPA 54:12.11.8.1] 509.10.7.2 Type B Double Wall Connector. The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent, except for engineered systems. The maximum length of an individual connector for a chimney or vent system serving multiple appliances, from the appliance outlet to the junction with the common vent or another connector, shall be 100 percent of the height of the chimney or vent. [NFPA 54:12.11.8.2] 509.10.8 Support. A vent connector shall be supported for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. [NFPA 54:12.11.9] 509.10.9 Chimney Connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the connector shall be attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue. [NFPA 54:12.11.10] 509.10.10 Inspection. The entire length of a vent connector shall be readily accessible for inspection, cleaning, and replacement. [NFPA 54:12.11.11]
509.10.12.1 Medium-Heat Appliances. Vent connectors for medium-heat appliances shall not pass through walls or partitions constructed of combustible material. [NFPA 54:12.11.13.2]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
▸Chapter 5 — WATER HEATERS
Overview- 501.0 General.501.1 Applicability. The regulations of this cha…
- 503.2 Final Water Heater Inspection. This inspection
- 504.2 Vent. Water heaters of other than the direct-vent type
- 504.3 Clearance. The clearance requirements for water
- 504.4 Pressure-Limiting Devices. A water heater installation s…
- 504.5 Temperature-Limiting Devices. A water heater
- 504.6 Temperature, Pressure, and Vacuum Relief
- 505.2 Safety Devices. Storage-type water heaters and hot
- 505.3 Oil-Fired Water Heaters. Oil-fired water heaters
- 505.4 Indirect-Fired Water Heaters. Indirect-fired water
- 506.0 Air for Combustion and Ventilation.506.1 General. Air fo…
- 506.2 Indoor Combustion Air. The required volume of
- 506.4 Outdoor Combustion Air. Outdoor combustion air
- 506.3 Indoor Opening Size and Location. Openings
- 506.8 Louvers, Grilles, and Screens. The required size
- 506.5 Combination Indoor and Outdoor CombustionAir. The use of…
- 506.9 Combustion Air Ducts. Combustion air ducts shall
- 506.6 Engineered Installations. Engineered combustion
- 506.7 Mechanical Combustion Air Supply. Where
- 507.2 Seismic Provisions. Water heaters shall be
- 507.3 Appliance Support. Appliances and equipment shall
- 507.4 Ground Support. A water heater supported from the
- 507.5 Drainage Pan. Where a water heater is located in an
- 507.6 Added or Converted Equipment or Appliances. When additio…
- 507.7 Types of Gases. The appliance shall be connected to
- 507.8 Safety Shutoff Devices for Unlisted LP-GasAppliance Used…
- 507.9 Use of Air or Oxygen Under Pressure. Where air
- 507.10 Protection of Gas Appliances from Fumes orGases other t…
- 507.11 Process Air. In addition to air needed for combustion i…
- 507.12 Flammable Vapors. Appliances shall not be
- 507.13 Installation in Residential Garages. Appliances
- 507.14 Installation in Commercial Garages. Appliances
- 507.15 Installation in Aircraft Hangars. Heaters in aircraft h…
- 507.16 Venting of Flue Gases. Appliances shall be vented
- 507.17 Extra Device or Attachment. No device or attachment sha…
- 507.18 Adequate Capacity of Piping. When additional
- 507.19 Avoiding Strain on Gas Piping. Appliances shall
- 507.20 Gas Appliance Pressure Regulators. Where the
- 507.21 Venting of Gas Appliance Pressure Regula-tors. Venting …
- 507.22 Bleed Lines for Diaphragm-Type Valves. Bleed
- 507.23 Combination of Appliances and Equipment. A
- 507.24 Installation Instructions. The installing agency
- 507.25 Protection of Outdoor Appliances. Appliances
- 507.26 Accessibility for Service. Appliances shall be
- 507.27 Clearance to Combustible Materials. Appliances and thei…
- 508.0 Appliances on Roofs.508.1 General. Appliances on roofs s…
- 508.2 Installation of Appliances on Roofs. Appliances
- 508.3 Appliances on Roofs. Appliances located on roofs
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.2 Connection to Venting Systems. Except as permitted in Se…
- 509.3 Design and Construction. Venting systems shall
- 509.4 Type of Venting System to be Used. The type of
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents. The installation of gas vents shall meet
- 509.7 Single-Wall Metal Pipe. Single-wall metal pipe
- 509.8 Through-the-Wall Vent Termination. A mechanical draft ve…
- 509.9 Condensation Drain. Provision shall be made to
- 509.11 Vent Connectors for Category II, Category III,
- 509.12 Draft Hoods and Draft Controls. Vented appliances shall…
- 509.15 Obstructions. Devices that retard the flow of vent
- 509.13 Manually Operated Dampers. A manually operated damper s…
- 509.14 Automatically Operated Vent Dampers. An
- 510.1 Single Appliance Vent Table 510.1.2(1) through
- 510.2 Multiple Appliance Vent Table 510.2(1) throughTable 510.…
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR