Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS

422.9 [DPH] Employee Lavatories in Food Establish-ments.

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Employee lavatories installed in food establishments shall be equipped with an approved single spout capable of providing tempered (100ºF - 115ºF) (37.8ºC - 46.1ºC) run- ning water. Note: This requirement applies only to commissaries serv- ing mobile food preparation units.

66 2019 CALIFORNIA PLUMBING CODE

PLUMBING FIXTURES AND FIXTURE FITTINGS

TABLE 422.1 MINIMUM PLUMBING FACILITIES 1

Each building shall be provided with sanitary facilities, including provisions for persons with disabilities as prescribed by the Department Having Jurisdiction 7 . Table 422.1 applies to new buildings, additions to a building, and changes of occupancy or type in an existing building resulting in increased occupant load. For requirements for persons with disabilities, Chapter 11A or 11B of the California Building Code shall be used .

The total occupant load shall be determined in accordance with the [BSC, DSA-SS & DSA-SS/CC] Occupant Load Factor Table A.

Exceptions: (1) [HCD 1-AC & HCD 2] For applications listed in Sections 1.8.2.1.2 and 1.8.2.1.3 regulated by the Department of Housing and Community Development, each building shall be provided with sanitary facilities, including provisions for persons with disabilities as prescribed by the Department. Covered mul- tifamily dwellings required to be accessible to persons with disabilities shall comply with Chapter 11A of the California Building Code. Permanent build- ings in mobilehome parks and special occupancy parks required to be accessible by persons with disabilities, shall comply with Chapter 11B of the California Building Code.

ons with disabilities as prescribed by the Department. Covered mul-_ tifamily dwellings required to be accessible to persons with disabilities shall comply with Chapter 11A of the California Building Code. Permanent build- ings in mobilehome parks and special occupancy parks required to be accessible by persons with disabilities, shall comply with Chapter 11B of the California Building Code.

(2) [HCD 1] For limited dens health official shall be pro sity owner-built rural dwelling sa ovided to the dwelling sites. It sh anitary facilities hall not be requi s, the type, design and number of ired that such facilities be locate f facilities as req ed within the dw quired and appro welling. oved by the local
TYPE OF
OCCUPANCY2

WATER CLOSETS
(FIXTURES PER PERSON)3
WATER CLOSETS
(FIXTURES PER PERSON)3
URINALS
(FIXTURES
PER
PERSON)4
LAVATORIES
(FIXTURES PER PERSON)5, 6
LAVATORIES
(FIXTURES PER PERSON)5, 6
BATHTUBS
OR
SHOWERS
(FIXTURES
PER
PERSON)
DRINKING
FOUNTAINS/
FACILITIES
(FIXTURES
PER
PERSON)
OTHER
A-1 Assembly occupancy
(fixed or permanent seat-
ing)- theaters, concert
halls, and auditoriums

Male
1: 1-100
2: 101-200
3: 201-400
Female
1: 1-25
2: 26-50
3: 51-100
4: 101-200
6: 201-300
8: 301-400
Male
1: 1-200
2: 201-300
3: 301-400
4: 401-600
Male
1: 1-200
2: 201-400
3: 401-600
4: 601-750
Female
1: 1-100
2: 101-200
4: 201-300
5: 301-500
6: 501-750
–– 1: 1-250
2: 251-500
3: 501-750
1 service
sink or
laundry tray
A-1 Assembly occupancy
(fixed or permanent seat-
ing)- theaters, concert
halls, and auditoriums

Over 400, add 1 fixture for
each additional 500 males
and 1 fixture for each
additional 125 females.
Over 400, add 1 fixture for
each additional 500 males
and 1 fixture for each
additional 125 females.
Over 600,
add 1 fixture
for each
additional
300 males.
Over 750, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females.
Over 750, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females.
Over 750, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females.
Over 750,
add 1 fixture
for each
additional
500 persons.
Over 750,
add 1 fixture
for each
additional
500 persons.
A-2 Assembly occupancy-
restaurants, pubs, lounges,
nightclubs and banquet
halls
Male
1: 1-50
2: 51-150
3: 151-300
4: 301-400
Female
1: 1-25
2: 26-50
3: 51-100
4: 101-200
6: 201-300
8: 301-400

Male
1: 1-200
2: 201-300
3: 301-400
4: 401-6000
Male
1: 1-150
2: 151-200
3: 201-400
Female
1: 1-150
2: 151-200
4: 201-400
––
1: 1-250
2: 251-500
3: 501-750
1 service
sink or
laundry tray
A-2 Assembly occupancy-
restaurants, pubs, lounges,
nightclubs and banquet
halls
Over 400, add 1 fixture for
each additional 250 males
and 1 fixture for each 125
females.
Over 400, add 1 fixture for
each additional 250 males
and 1 fixture for each 125
females.
Over 600,
add 1 fixture
for each
additional
300 males.
Over 400, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females
Over 400, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females
Over 400, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females
Over 750,
add 1 fixture
for each
additional
500 persons.
Over 750,
add 1 fixture
for each
additional
500 persons.
A-3 Assembly occupancy
(typical without fixed or
permanent seating)-
arcades, places of wor-
ship, museums, libraries,
lecture halls, gymnasiums
(without spectator seat-
ing), indoor pools (with-
out spectator seating)
Male
1: 1-100
2: 101-200
3: 201-400
Female
1: 1-25
2: 26-50
3: 51-100
4: 101-200
6: 201-300
8: 301-400
Male
1: 1-100
2: 101-200
3: 201-400
4: 401-600
Male
1: 1-200
2: 201-400
3: 401-600
4: 601-750
Female
1: 1-100
2: 101-200
4: 201-300
5: 301-500
6: 501-750
–– 1: 1-250
2: 251-500
3: 501-750
1 service
sink or
laundry tray
A-3 Assembly occupancy
(typical without fixed or
permanent seating)-
arcades, places of wor-
ship, museums, libraries,
lecture halls, gymnasiums
(without spectator seat-
ing), indoor pools (with-
out spectator seating)
Over 400, add 1 fixture for
each additional 500 males
and 1 fixture for each
additional 125 females.
Over 400, add 1 fixture for
each additional 500 males
and 1 fixture for each
additional 125 females.
Over 600,
add 1 fixture
for each
additional
300 males.
Over 750, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females.
Over 750, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females.
Over 750, add 1 fixture for
each additional 250 males
and 1 fixture for each
additional 200 females.
Over 750,
add 1 fixture
for each
additional
500 persons.
Over 750,
add 1 fixture
for each
additional
500 persons.

2019 CALIFORNIA PLUMBING CODE 67

PLUMBING FIXTURES AND FIXTURE FITTINGS any other purpose or distributed to any other persons or parti es.

TABLE 422.1 MINIMUM PLUMBING FACILITIES 1 (continued)

TYPE OF
OCCUPANCY2
WATER CLOSETS
(FIXTURES PER PERSON)3
URINALS
(FIXTURES
PER
PERSON)4
LAVATORIES
(FIXTURES PER PERSON)5, 6
BATHTUBS
OR
SHOWERS
(FIXTURES
PER
PERSON)
DRINKING
FOUNTAINS/
FACILITIES
(FIXTURES
PER
PERSON)
OTHER
A-4 Assembly occupancy
(indoor activities or sport-
ing events with spectator
seating)- swimming pools,
skating rinks, arenas, and
gymnasiums

Male
1: 1-100
2: 101-200
3: 201-400
Female
1: 1-25
2: 26-50
3: 51-100
4: 101-200
6: 201-300
8: 301-400
Male
1: 1-100
2: 101-200
3: 201-400
4: 401-600
Male
1: 1-200
2: 201-400
3: 401-750
Female
1: 1-100
2: 101-200
4: 201-300
5: 301-500
6: 501-750
–– 1: 1-250
2: 251-500
3: 501-750
1 service
sink or laun-
dry tray
A-4 Assembly occupancy
(indoor activities or sport-
ing events with spectator
seating)- swimming pools,
skating rinks, arenas, and
gymnasiums


Over 400, add 1 fixture for
each additional 500 males
and 1 fixture for each
additional 125 females.

Over 400, add 1 fixture for
each additional 500 males
and 1 fixture for each
additional 125 females.
Over 600,
add 1 fixture
for each
additional
300 males.
Over 750, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.
Over 750, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.
Over 750, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.
Over 750,
add 1 fixture
for each
additional
500 persons.
Over 750,
add 1 fixture
for each
additional
500 persons.
A-5Assembly occupancy
(outdoor activities or
sporting events)- amuse-
ment parks, grandstands
and stadiums

Male
1: 1-100
2: 101-200
3: 201-400

Female
1: 1-25
2: 26-50
3: 51-100
4: 101-200
6: 201-300
8: 301-400


Male
1: 1-100
2: 101-200
3: 201-400
4: 401-600

Male
1: 1-200
2: 201-400
3: 401-750

Female
1: 1-100
2: 101-200
4: 201-300
5: 301-500
6: 501-750

––
1: 1-250
2: 251-500
3: 501-750

1 service
sink or
laundry tray
A-5Assembly occupancy
(outdoor activities or
sporting events)- amuse-
ment parks, grandstands
and stadiums


Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each additional 125
females.

Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each additional 125
females.
Over 600,
add 1 fixture
for each
additional
300 males.
Over 750, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.

Over 750, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.

Over 750, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.

Over 750,
add 1 fixture
for each
additional
500 persons.
Over 750,
add 1 fixture
for each
additional
500 persons.
B Business occupancy
(office, professional or
service type transactions)-
banks, vet clinics, hospi-
tals, car wash, banks,
beauty salons, ambulatory
health care facilities, laun-
dries and dry cleaning,
educational institutions
(above high school), or
training facilities not
located within school, post
offices and printing shops

Male
1: 1-50
2: 51-100
3: 101-200
4: 201-400
Female
1: 1-15
2: 16-30
3: 31-50
4: 51-100
8: 101-200
11: 201-400

Male
1: 1-100
2: 101-200
3: 201-400
4: 401-600
Male
1: 1-75
2: 76-150
3: 151-200
4: 201-300
5: 301-400
Female
1: 1-50
2: 51-100
3: 101-150
4: 151-200
5: 201-300
6: 301-400
––

1 per 150
1 service
sink or
laundry tray

B Business occupancy
(office, professional or
service type transactions)-
banks, vet clinics, hospi-
tals, car wash, banks,
beauty salons, ambulatory
health care facilities, laun-
dries and dry cleaning,
educational institutions
(above high school), or
training facilities not
located within school, post
offices and printing shops


Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each additional 150
females.


Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each additional 150
females.

Over 600,
add 1 fixture
for each
additional
300 males.

Over 400, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.


Over 400, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.


Over 400, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.


Over 400, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.


Over 400, add 1 fixture
for each additional 250
males and 1 fixture for
each additional 200
females.

E Educational occupancy-
private or public schools

Male
1 per 50
Female
1 per 30
Male
1 per 100
Male
1 per 40
Female
1 per 40
––
1 per 150 1 service
sink or
laundry tray
TYPE OF
OCCUPANCY2
WATER CLOSETS
(FIXTURES PER PERSON)3
URINALS
(FIXTURES
PER
PERSON)4
LAVATORIES
(FIXTURES PER PERSON)5, 6
BATHTUBS
OR
SHOWERS
(FIXTURES
PER
PERSON)
DRINKING
FOUNTAINS/
FACILITIES
(FIXTURES
PER
PERSON)
OTHER
F1, F2 Factory or Indus-
trial occupancy-fabricat-
ing or assembly work
Male
1: 1-50
2: 51-75
3: 76-100
Female
1: 1-50
2: 51-75
3: 76-100
–– Male
1: 1-50
2: 51-75
3: 76-100
Female
1: 1-50
2: 51-75
3: 76-100
1 shower for
each 15
persons
exposed to
excessive
heat or to
skin contam-
ination with
poisonous,
infectious or
irritating
material
1: 1-250
2: 251-500
3: 501-750

1 service
sink or
laundry tray
F1, F2 Factory or Indus-
trial occupancy-fabricat-
ing or assembly work
Over 100, add 1 fixture
for each additional 40 per-
sons.
Over 100, add 1 fixture
for each additional 40 per-
sons.
–– Over 100, add 1 fixture
for each additional 40
persons.
Over 100, add 1 fixture
for each additional 40
persons.
Over 100, add 1 fixture
for each additional 40
persons.
Over 750,
add 1 fixture
for each
additional
500 persons.
Over 750,
add 1 fixture
for each
additional
500 persons.

68 2019 CALIFORNIA PLUMBING CODE

PLUMBING FIXTURES AND FIXTURE FITTINGS

TABLE 422.1 MINIMUM PLUMBING FACILITIES 1 (continued)

TYPE OF
OCCUPANCY2
WATER CLOSETS
(FIXTURES PER PERSON)3
URINALS
(FIXTURES
PER
PERSON)4
LAVATORIES
(FIXTURES PER PERSON)5, 6
BATHTUBS
OR
SHOWERS
(FIXTURES
PER
PERSON)
DRINKING
FOUNTAINS/
FACILITIES
(FIXTURES
PER
PERSON)
OTHER
I-1 Institutional occu-
pancy (houses more than
16 persons on a 24-hour
basis)- substance abuse
centers, assisted living,
group homes, or residen-
tial facilities


I-1 Institutional occu-
pancy (houses more than
16 persons on a 24-hour
basis)- substance abuse
centers, assisted living,
group homes, or residen-
tial facilities


Female
1 per 15
–– Male
1 per 15
Female
1 per 15
1 per 8 1 per 150 1 service
sink or
laundry tray

I-2 Institu-
tional occu-
pancy-medi
cal, psychi-
atric, surgi-
cal or
nursing
homes

Hospitals
and nursing
homes-indi-
vidual
rooms and
ward room
1 per room 1 per room –– 1 per room 1 per room 1 per room
1 per 150 1 service
sink or
laundry tray

I-2 Institu-
tional occu-
pancy-medi
cal, psychi-
atric, surgi-
cal or
nursing
homes

Hospitals
and nursing
homes-indi-
vidual
rooms and
ward room
1 per 8 patients 1 per 8 patients –– 1 per 10 patients 1 per 10 patients 1 per 20
patients
1 per 20
patients
1 per 20
patients

I-2 Institu-
tional occu-
pancy-medi
cal, psychi-
atric, surgi-
cal or
nursing
homes


Hospital
Waiting or
Visitor
Rooms
1 per room

1 per room

–– 1 per room 1 per room –– 1 per room ––

I-2 Institu-
tional occu-
pancy-medi
cal, psychi-
atric, surgi-
cal or
nursing
homes

Employee
Use
Male
1: 1-15
2: 16-35
3: 36-55
Female
1: 1-15
3: 16-35
4: 36-55
––
Male
1 per 40
Female
1 per 40
––
––
––

I-2 Institu-
tional occu-
pancy-medi
cal, psychi-
atric, surgi-
cal or
nursing
homes

Employee
Use


Over 55, add 1 fixture for
each additional 40 persons.


Over 55, add 1 fixture for
each additional 40 persons.


Over 55, add 1 fixture for
each additional 40 persons.


Over 55, add 1 fixture for
each additional 40 persons.


Over 55, add 1 fixture for
each additional 40 persons.


Over 55, add 1 fixture for
each additional 40 persons.


Over 55, add 1 fixture for
each additional 40 persons.


Over 55, add 1 fixture for
each additional 40 persons.
I-3Institu-
tional occu-
pancy
(houses
more than 5
people)

Prisons

1 per cell

1 per cell
–– 1 per cell 1 per cell 1 per 20 1 per cell
block/floor
––
I-3Institu-
tional occu-
pancy
(houses
more than 5
people)

Correctional
facilities or
juvenile
center
1 per 8

1 per 8

–– 1 per 10 1 per 10 1 per 8 1 per floor 1 service
sink or laun-
dry tray
I-3Institu-
tional occu-
pancy
(houses
more than 5
people)

Employee
Use

Male
1: 1-15
2: 16-35
3: 36-55
Female
1: 1-15
3: 16-35
4: 36-55
–– Male
1 per 40
Female
1 per 40
–– 1 per 150 ––
I-3Institu-
tional occu-
pancy
(houses
more than 5
people)

Employee
Use



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.

I-4Institutional occu-
pancy (any age that
receives care for less than
24 hours)

I-4Institutional occu-
pancy (any age that
receives care for less than
24 hours)


Male
1: 1-15
2: 16-35
3: 36-55

Female
1: 1-15
3: 16-35
4: 36-55
–– Male
1 per 40
Female
1 per 40
–– 1 per 150 1 service
sink or
laundry tray
I-4Institutional occu-
pancy (any age that
receives care for less than
24 hours)

I-4Institutional occu-
pancy (any age that
receives care for less than
24 hours)



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.



Over 55, add 1 fixture for
each additional 40 persons.

TYPE OF
OCCUPANCY2
WATER CLOSETS
(FIXTURES PER PERSON)3
URINALS
(FIXTURES
PER
PERSON)4
LAVATORIES
(FIXTURES PER PERSON)5, 6
BATHTUBS
OR
SHOWERS
(FIXTURES
PER
PERSON)
DRINKING
FOUNTAINS/
FACILITIES
(FIXTURES
PER
PERSON)
OTHER
M Mercantile occupancy
(the sale of merchandise
and accessible to the pub-
lic)
M Mercantile occupancy
(the sale of merchandise
and accessible to the pub-
lic)

Male
1: 1-100
2: 101-200
3: 201-400

Female
1: 1-100
2: 101-200
4: 201-300
6: 301-400
Male
0: 1-200
1: 201-400
Male
1: 1-200
2: 201-400
Female
1: 1-200
2: 201-300
3: 301-400
–– 1: 1-250
2: 251-500
3: 501-750
1 service
sink or
laundry tray
M Mercantile occupancy
(the sale of merchandise
and accessible to the pub-
lic)
M Mercantile occupancy
(the sale of merchandise
and accessible to the pub-
lic)

Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each 200 females.

Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each 200 females.
Over 400,
add 1 fixture
for each
additional
500 males.
Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each 400 females.
Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each 400 females.
–– Over 750,
add 1 fixture
for each
additional
500 persons.
––

2019 CALIFORNIA PLUMBING CODE 69

PLUMBING FIXTURES AND FIXTURE FITTINGS any other purpose or distributed to any other persons or parti es.

TABLE 422.1 MINIMUM PLUMBING FACILITIES 1 (continued)

TYPE OF
OCCUPANCY2
R-1 Residential occupancy
WATER CLOSETS
(FIXTURES PER PERSON)3
URINALS
(FIXTURES
PER
PERSON)4
LAVATORIES
(FIXTURES PER PERSON)5, 6
BATHTUBS
OR
SHOWERS
(FIXTURES
PER
PERSON)
DRINKING
FOUNTAINS/
FACILITIES
(FIXTURES
PER
PERSON)
OTHER

(minimal stay)- hotels,
motels, bed and breakfast
homes


(minimal stay)- hotels,
motels, bed and breakfast
homes

1 per sleeping room

1 per sleeping room

––
1 per sleeping room

1 per sleeping room

1 per sleep-
ing room
–– 1 service sink
or
laundry tray
R-2 Resi-
dential
occupancy
(long-term
or perma-
nent)

Dormitories Male
1 per 10
Female
1 per 8
1 per 25
Male
1 per 12
Female
1 per 12
1 per 8 1 per 150 1 service sink
or laundry tray
R-2 Resi-
dential
occupancy
(long-term
or perma-
nent)

Dormitories

Add 1 fixture for each
additional 25 males and 1
fixture for each additional
20 females.



Add 1 fixture for each
additional 25 males and 1
fixture for each additional
20 females.

Over 150,
add 1 fixture
for each
additional
50 males.


Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.


Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.


Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.


Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.


Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.
R-2 Resi-
dential
occupancy
(long-term
or perma-
nent)

Employee
Use
Male
1: 1-15
2: 16-35
3: 36-55
Female
1: 1-15
3: 16-35
4: 36-55
–– Male
1 per 40
Female
1 per 40
–– –– ––
R-2 Resi-
dential
occupancy
(long-term
or perma-
nent)

Employee
Use
Over 55, add 1 fixture for
each additional 40 persons
Over 55, add 1 fixture for
each additional 40 persons
Over 55, add 1 fixture for
each additional 40 persons
Over 55, add 1 fixture for
each additional 40 persons
Over 55, add 1 fixture for
each additional 40 persons
Over 55, add 1 fixture for
each additional 40 persons
Over 55, add 1 fixture for
each additional 40 persons
Over 55, add 1 fixture for
each additional 40 persons
R-2 Resi-
dential
occupancy
(long-term
or perma-
nent)

Apartment
house/unit


1 per apartment


1 per apartment

–– 1 per apartment

1 per apartment

1 per
apartment
–– 1 kitchen sink
per apartment.
1 laundry tray
or 1 automatic
clothes washer
connection per
unit or 1 laun-
dry tray or 1
automatic
clothes washer
connection for
each 12 units
R-3 Residential occu-
pancy (long-term or per-
manent in nature) for
more than 5 but does not
exceed 16 occupants)

R-3 Residential occu-
pancy (long-term or per-
manent in nature) for
more than 5 but does not
exceed 16 occupants)

Male
1 per 10
Female
1 per 8
–– Male
1 per 12
Female
1 per 12
1 per 8 1 per 150 1 service sink
or laundry tray
R-3 Residential occu-
pancy (long-term or per-
manent in nature) for
more than 5 but does not
exceed 16 occupants)

R-3 Residential occu-
pancy (long-term or per-
manent in nature) for
more than 5 but does not
exceed 16 occupants)

Add 1 fixture for each
additional 25 males and 1
fixture for each additional
20 females.
Add 1 fixture for each
additional 25 males and 1
fixture for each additional
20 females.
Add 1 fixture for each
additional 25 males and 1
fixture for each additional
20 females.
Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.
Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.
Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.
Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.
Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.
R-3 Residential occu-
pancy (one and two fam-
ily dwellings)
R-3 Residential occu-
pancy (one and two fam-
ily dwellings)
1 per one and two family
dwelling
1 per one and two family
dwelling
–– 1 per one and two family
dwelling
1 per one and two family
dwelling
1 per one
and two
family
dwelling
–– 1 kitchen
sink and 1
automatic
clothes washer
connection per
one and two
family
dwelling

70 2019 CALIFORNIA PLUMBING CODE

any other purpose or distributed to any other persons or parti es. PLUMBING FIXTURES AND FIXTURE FITTINGS

TABLE 422.1 MINIMUM PLUMBING FACILITIES 1 (continued)

TYPE OF
OCCUPANCY2
WATER CLOSETS
(FIXTURES PER PERSON)3
URINALS
(FIXTURES
PER
PERSON)4
LAVATORIES
(FIXTURES PER PERSON)5, 6
BATHTUBS
OR
SHOWERS
(FIXTURES
PER
PERSON)
DRINKING
FOUNTAINS/
FACILITIES
(FIXTURES
PER
PERSON)
OTHER
R-4 Residential occu-
pancy (residential care or
assisted living)

Male
1 per 10
Female
1 per 8
–– Male
1 per 12
Female
1 per 12
1 per 8 1 per 150
1 service sink
or laundry tray
R-4 Residential occu-
pancy (residential care or
assisted living)

Add 1 fixture for each
additional 25 males and 1
fixture for each additional
20 females.

Add 1 fixture for each
additional 25 males and 1
fixture for each additional
20 females.

Add 1 fixture for each
additional 25 males and 1
fixture for each additional
20 females.

Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.

Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.

Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.

Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.

Add 1 fixture for each
additional 20 males and 1
fixture for each additional
15 females.

S-1, S-2 Storage occu-
pancy-storage of goods,
warehouse, aircraft
hanger, food products,
appliances
Male
1: 1-100
2: 101-200
3: 201-400
Female
1: 1-100
2: 101-200
3: 201-400
–– Male
1: 1-200
2: 201-400
3: 401-750
Female
1: 1-200
2: 201-400
3: 401-750
–– 1: 1-250
2: 251-500
3: 501-750
1 service sink
or laundry tray
S-1, S-2 Storage occu-
pancy-storage of goods,
warehouse, aircraft
hanger, food products,
appliances


Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each additional 150
females.


Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each additional 150
females.


Over 400, add 1 fixture
for each additional 500
males and 1 fixture for
each additional 150
females.


Over 750, add 1 fixture
for each additional 500
persons.


Over 750, add 1 fixture
for each additional 500
persons.


Over 750, add 1 fixture
for each additional 500
persons.
Over 750,
add 1 fix-
ture for
each addi-
tional 500
persons.
Over 750,
add 1 fix-
ture for
each addi-
tional 500
persons.

1

1 The figures shown are based upon one fixture being the minimum required for the number of persons indicated or any fraction thereof. 2 A restaurant is defined as a business that sells food to be consumed on the premises. a. The number of occupants for a drive-in restaurant shall be considered as equal to the number of parking stalls. b. Hand-washing facilities shall be available in the kitchen for employees. 3 The total number of required water closets for females shall be not less than the total number of required water closets and urinals for males. 4 For each urinal added in excess of the minimum required, one water closet shall be permitted to be deducted. The number of water closets shall not be reduced to less than two-thirds of the minimum requirement. 5 Group lavatories that are 24 lineal inches (610 mm) of wash sink or 18 inches (457 mm) of a circular basin, where provided with water outlets for such space, shall be considered equivalent to one lavatory. 6 Metering or self-closing faucets shall be installed on lavatories intended to serve the transient public. 7 [BSC, DSA-AC, DSA-SS, DSA-SS/CC, HCD 1 & HCD 2, OSHPD 1, 1R, 2, 3, 4 & 5] In accordance with Sections 1.8.7 and 301.3, the Authority Hav- ing Jurisdiction may approve alternative design criteria when determining the minimum number of plumbing fixtures.

2019 CALIFORNIA PLUMBING CODE 71

PLUMBING FIXTURES AND FIXTURE FITTINGS any other purpose or distributed to any other persons or parti es.

TABLE A OCCUPANT LOAD FACTOR:

[BSC, DSA-SS & DSA-SS/CC]

OCCUPANCY*, ** OCCUPANT LOAD FACTOR
(square feet)
Group A
1.
Auditoriums, convention halls, dance floors, lodge rooms, stadiums,
and casinos (where no fixed seating is provided).
(Where fixed seating is provided use one-half the number of fixed seat-
ing.)
2.
Conference rooms, dining rooms, drinking establishments, exhibit
rooms, gymnasiums, lounges, stages, and similar uses, including restau-
rants classified as Group B occupancies.
3.
Worship places; principal assembly area, educational and activity unit
(where no fixed seating is provided).
(Where fixed seating is provided use one-half the number of fixed seat-
ing.)
15
30
30
Group B
Office or public buildings (area accessible to the public)
200

Group E
Schools for day care, elementary, secondary
50

Educational Facilities Other than Group E
Colleges, universities, adult centers, etc.
50

Group F
Workshops, foundries and similar establishments
2,000

Group H
Hazardous materials fabrication and storage
2,000

Group I
Hospital general use area, health care facilities
200

Group M
Retail or wholesale stores
200

Group R
Congregate residence, Group R-1
200


Group S
Warehouse
5,000

** For building or space with mixed occupancies, use appropriate occupancy group for each area (for example, a school may have an “A” occupancy for the gymnasium, a “B” occupancy for the office, an “E” occupancy for the classrooms, etc.). Accessory areas may be excluded (for example: hallway, restroom, stair enclosure).

72 2019 CALIFORNIA PLUMBING CODE

PLUMBING FIXTURES AND FIXTURE FITTINGS

TABLE 4-2

[OSHPD 1, 1R, 2, 3, 4 & 5] 24 MINIMUM PLUMBING FACILITIES

SPACE HANDWASHING
FIXTURE
SCRUB
SINKS3
TOILETS BATHTUBS OR
SHOWERS
SERVICE
SINKS1
CLINIC
SINKS
Administration Lobby

Public Toilet - Male
1
1

Public Toilet - Female
1
1

Airborne infection isolation room
1

Airborne infection isolation treatment/exam room
1

Airborne infection isolation anteroom
120

Airborne infection isolation toilet room
12 15 15

Cardiac Catheterization procedure room
14, 33

Central Sterile Supply
115

Cesarean/Delivery Service Space

Labor Rooms
133
19 19

Recovery Room
133
1

Drug distribution station
1

Cesarean operating room
210, 33

Delivery room
110, 33

Staff lounge

Staff Toilet - Male
12
1:1-15

Staff Toilet - Female
12
1:1-15

LDR or LDRP room
133 1 1

Waiting area/room

Public Toilet - Male
12
1

Public Toilet - Female
12
1

Clinical Laboratory Service Space11
1

Dietetic Service Space
1

Kitchen
133
Food serving area
133

Food Preparation
133

Dietary Staff Toilet - Male
12
1:1-15

Dietary Staff Toilet - Female
12
1:1-15

Emergency Service
1

Open plan
1:4 cubicles
1

Observation unit(s)


1:4 cubicles
1:6 beds

Trauma/Cardiac, Emergency surgery, Cystoscopy,
Cast Room
14,33

Intensive Care Units7
1 1

Open plan
1:3 beds33

Patient rooms28

133

Newborn Intensive Care Unit (NICU)
1:4 bassinets17, 33
1 1

Treatment area/room

1

Control station
133

Staff lounge

Staff Toilet - Male
12
1:1-15

Staff Toilet - Female
12 1:1-15

2019 CALIFORNIA PLUMBING CODE 73

PLUMBING FIXTURES AND FIXTURE FITTINGS any other purpose or distributed to any other persons or parti es.

TABLE 4-2

[OSHPD 1, 2, 3 & 4] 24 MINIMUM PLUMBING FACILITIES (continued)

>
SPACE HANDWASHING
FIXTURE
SCRUB
SINKS3
TOILETS BATHTUBS OR
SHOWERS
SERVICE
SINKS1
CLINIC
SINKS
Employee dressing rooms and lockers
Staff Toilet - Male
12
1:1-15

Staff Toilet - Female
12
1:1-15



Housekeeping room~~~~1
1

Laboratories
115


Medicine preparation room
119



Nourishment area
1+12







Patient toilet and bath facilities13
12
1:4 beds
1:1216

Central bathing facility16
1
1
1

Special bathing facility16
1

Nurse Station27
1
112

Newborn/well baby nursery
1:6 bassinets33

Workroom

133
Gastrointestinal endoscopy procedure room
133

Outpatient observation35
1
1

Pediatric and Adolescent Unit toilet room
12,26
126

Pharmacy
125
Staff Toilet - Male
12
1:1-15

Staff Toilet - Female
12
1:1-15

Compounding area for parenteral solutions
133



Open plan
1:4 gurney
spaces33
Individual rooms
133

Protective environment room
133

Protective environment anteroom
120,33

Protective environment toilet room
12
15
15



Radiological/Imaging Services Space
1
129


Interventional imaging
1

Ultrasound8
130
Angiography
14, 31
Fluoroscopy8
130
Staff Toilet18 - Male
12
1:1-15

Staff Toilet18 - Female
12 1:1-15







74 2019 CALIFORNIA PLUMBING CODE

PLUMBING FIXTURES AND FIXTURE FITTINGS

TABLE 4-2

[OSHPD 1, 2, 3 & 4] 24 MINIMUM PLUMBING FACILITIES (continued)

SPACE HANDWASHING
FIXTURE
SCRUB
SINKS3
TOILETS BATHTUBS OR
SHOWERS
SERVICE
SINKS1
CLINIC
SINKS

















Repair room11
1
1

Dialysis patient toilet
12 1









Surgical Service Space
233 1



Staff Toilet - Male
12
1
1 shower

Staff Toilet - Female
12
1
1 shower







Soiled workroom or soiled holding
1
134






Clean21
1
Soiled22
1
114
Patient beds [Skilled Nursing/Intermediate Care
Facilities][medical model]

1:82
1:6
1:20

Patient toilet and bath facilities13[Correctional
Treatment Center]

1:82
1:6
1:12

Airborne infection isolation anteroom6 [Correctional
Treatment Center]

16
16 16

Airborne infection isolation anteroom [Correctional
Treatment Center]

1

Protective environment room6 [Correctional Treat-
ment Center]

16
16 16


Protective environment anteroom [Correctional
Treatment Center]
1

departmental services are compatible. A dedicated housekeeping room shall be provided for the following services: Surgical/Catherization, ICU, NICU, nursery, dietary, renal dialysis and outpatient surgery. 2 Conventional spouts and controls on hot-and cold-water supplies are acceptable. Aerators are not permitted. Non-aerating laminar flow devices are permitted. Nourishment areas shall have a handwashing fixture in or immediately accessible from the nourishment area, in addition to a nourishment sink. 3 Scrub sinks shall be located outside of sterile procedure rooms. A minimum of two scrub sinks shall be provided in a surgical unit containing one operating room. Four scrub sinks shall be provided in surgical units containing two operating rooms. One additional scrub sink shall be provided per each additional operating room. 4 The scrub sink is in addition to the required number for surgeries. 5 The following fixtures shall be provided in airborne infection or protective environment rooms of hospitals only: a.Within an adjoining toilet room, a lavatory, a shower containing a seat or a space for a shower chair, and toilet equipped with bedpan flushing attachment

with a vacuum breaker.

a.Within an adjoining toilet room, a lavatory, a shower containing a seat or a space for a shower chair, and toilet equipped with bedpan flushing attachment

with a vacuum breaker. b.A handwashing fixture within a separate anteroom. 6 The following fixtures shall be provided in isolation rooms of correctional treatment centers only: a.Within an adjoining toilet area, a handwashing fixture, a shower containing a seat or a space for a shower chair, and water closet equipped with bedpan

flushing attachment with a vacuum breaker.

flushing attachment with a vacuum breaker. b.A handwashing fixture within a separate anteroom. 7 Includes burn center spaces, acute respiratory-care service spaces, and coronary-care service spaces.

2019 CALIFORNIA PLUMBING CODE 75

PLUMBING FIXTURES AND FIXTURE FITTINGS any other purpose or distributed to any other persons or parti es.

8 A toilet room with handwashing fixture shall directly adjoin each procedure room. 9 One toilet with lavatory and one shower may serve two labor rooms. 10 One additional scrub sink for each additional cesarean or delivery operating room. 11 Provide emergency eye-wash and shower. 12 Conveniently located for staff use. 13 Fixtures serving individual patient rooms shall not be considered as meeting the required ratios for bedrooms not served by individual adjoining toilet or bath- rooms. 14 The clinic sink may be deleted if all bedrooms in the nursing unit are provided with adjoining toilets with bedpan flushing devices. 15 Conventional controls on hot-and cold-water supplies are acceptable. The water discharge points shall be 5 inches (127 millimeters) above the fixture rim. Aerators are not permitted. Non-aerating laminar flow devices are permitted. 16 A minimum of one bathtub is required on each floor of an acute care or acute psychiatric hospital providing skilled nursing or intermediate care services. Special bathing facilities/gurney shower shall be provided at a minimum ratio of one per 100 beds for acute care facilities. 17 In a multiple-bed room, every bed position shall be within 20 feet (6 meters) of a hands-free handwashing fixture. Where an individual room concept is used, a handwashing fixture shall be provided within each infant care room. 18 When three or more procedure rooms are provided. 19 If a separate medicine room is provided, the room shall be equipped with a sink in addition to the nurses' station handwashing fixture. Hot-water supplies are optional. 20 Not required when there is a handwash fixture in the patient bed room. 21 Handwashing fixtures may be deleted if room is used for storage and holding only. 22 If room is used only for temporary holding of soiled materials, clinic sink and work counter may be omitted. If the flushing-rim clinical sink is eliminated, facilities for cleaning bedpans shall be provided elsewhere. 23 Toilet shall be equipped with a bedpan flushing attachment. 24 Optional services approved by the licensing agency shall comply with the applicable space requirements of OSHPD 1 and 2. 25 Shall be provided in each separate room where open medication is handled. 26 Conveniently accessible throughout the unit. 27 Includes rooms or areas within coronary and intensive-care units and postanethesia recovery rooms. 28 Modular toilet/sink combination units located within a privacy curtain may be used within individual patient space or private room. The toilet fixture shall be completely contained within cabinetry when not in use, and shall be enclosed when flushed. Bedpan washers shall not be permitted in patient bedrooms. 29 In service spaces with procedure rooms that do not have dedicated patient toilets, provide a minimum of one patient toilet room with a separate handwash- ing fixture within the service space. 30 Toilet room shall be accessible from the procedure room. 31 Scrub sink shall be located outside the staff entrance to the procedure room. 32 Not used. 33 Handwashing and scrub sink fixtures shall not be equipped with wrist or elbow blades but shall be equipped with sensor controls, or controls that do not involve contact with the upper extremities. 34 If room is used only for temporary holding of soiled material, clinic sink and work counter may be omitted. 35 A minimum of one separate accessible toilet room shall be provided for the use of patients. Patient toilet room(s) shall be equipped with a handwashing fix- ture and shall be accessible to the observation units(s) from the corridor. Reference CBC, Part 2, Section 1224.39.6.

ies._ 34 If room is used only for temporary holding of soiled material, clinic sink and work counter may be omitted. 35 A minimum of one separate accessible toilet room shall be provided for the use of patients. Patient toilet room(s) shall be equipped with a handwashing fix- ture and shall be accessible to the observation units(s) from the corridor. Reference CBC, Part 2, Section 1224.39.6.

76 2019 CALIFORNIA PLUMBING CODE

PLUMBING FIXTURES AND FIXTURE FITTINGS

TABLE 4-3
TYPE OF BUILDING
OR OCCUPANCY

WATER CLOSETS
(FIXTURES PER PERSON)7
URINALS (TROUGH URINAL
TO INDIVIDUAL
URINAL EQUIVALENCE)
MALE



LAVATORIES
(FIXTURES
PER PERSON)

BATHTUBS OR SHOWERS
(FIXTURES PER PERSON)

DRINKING
FOUNTAINS
(FIXTURES
PER PERSON)3
TYPE OF BUILDING
OR OCCUPANCY

MALE FEMALE



MALE FEMALE



MALE FEMALE



MALE FEMALE



MALE FEMALE



Nonindustrial—office
buildings, public build-
ings and similar estab-
lishments

1 1-15
1 1-15
2 16-35
2 16-35
3 36-55
3 36-55
4 56-80
4 56-80
5 81-110
5 81-110
6 111-150
6 111-150
1 additional for each
additional 40 employees
or fraction thereof



Length of
Number of
trough urinal
individual
urinals
24" (610 mm)
1
36" (914 mm)
2
48" (1219 mm)
2
60" (1524 mm)
3



1 1-15
2 16-35
3 36-60
4 61-90
5 91-125
1 additional for each
additional 4 employ-
ees or fraction thereof

1:10 persons per shift
required to shower



Industrial–factories,
warehouses, loft build-
ings and similar estab-
lishments

1 1-15
1 1-15
2 16-35
2 16-35
3 36-55
3 36-55
4 56-80
4 56-80
5 81-110
5 81-110
6 111-150
6 111-150
1 additional for each
additional 40 employees
or fraction thereof
24" (610 mm)
1
36" (914 mm)
2
48" (1219 mm)
2
60" (1524 mm)
3
72" (1829 mm)
4
1 to 100
employees
1 per 10
Over 100 employees 1
additional for each
additional 15 employ-
ees or fraction thereof
1:10 persons per shift
required to shower

2 Each water closet shall occupy a separate compartment which shall be equipped with a door, door latch and clothes hook. The door and the walls or partitions between fixtures shall be sufficient to assure privacy. 3 Drinking fountains shall not be located in toilet rooms. 4 Washing facilities shall be reasonably accessible to all employees. 5 Toilet facilities shall be accessible to the employees at all times. Where practicable, toilet facilities should be within 200 feet (61 m) of locations at which workers are reg- ularly employed and should not be more than one floor-to-floor flight of stairs from working areas. 6 Urinals may be installed instead of water closets in toilet rooms to be used only by men provided that the number of water closets shall not be less than two thirds of the minimum number of toilet facilities specified. The length of trough urinals to the equivalent number of individual urinals shall be based on the above table. 7 When there are less than five employees, separate toilet rooms for each sex are not required provided toilet rooms can be locked from the inside and contain at least one water closet. 8 Twenty-four linear inches of wash sink or 18 inches of circular basin, when provided with water outlets for such space, shall be considered equivalent to one lavatory. Exception: The requirements of Table 4-3 do not apply to mobile crews or to normally unattended work locations provided employees at these locations have immediately available transportation to nearby toilet facilities which meet the requirements of Table 4-3.

TABLE 4-4

TYPE OF BUILDING
OR OCCUPANCY2
WATER CLOSETS
(FIXTURES PER PERSON)
URINALS
(FIXTURES PER MALE)
LAVATORIES
(FIXTURES PER PERSON)
BATHTUBS OR SHOWERS
(FIXTURES PER PERSON)
DRINKING FOUNTAINS
(FIXTURES PER PERSON)
Day Use Public
Beaches1,2
Male
Female
1 1-100
1 1-100
No sex designated
1 1-500
Minimum of 2

May be substituted for
up to two-thirds of the
water closets required
Picnic Areas


Male
Female
1 1-50
1 1-50


Overnight Use
Public Beaches2


1 1-7.5 campsites3
1 1-7.5 campsites3
May be substituted for
up to one-third of the
water closets required3
1 1-12.5 campsites4

_Organized Camps _
1 1-153 1 1-15 1 1-156 Minimum 1 per camp

age daily use during periods of peak use. The health officer may determine how many days the population standard may be exceeded. 2 Laundry facilities are not required, but if they are provided, must be a minimum of two laundry trays or a washing machine. 3 Toilet facilities shall not be farther than 400 feet from any lot or campsite. 4 Showers are not required, but it provided, they shall be provided on the indicated ratio. Outdoor rinse-off showers may be cold water only. 5 Toilets shall be located within 300 feet from the living accommodations they serve. 6 Showers shall be provided in the living area or in a centrally located structure. Exception: Intermittent short-term organized camps are not required to provide shower facilities, but it provided, they shall comply with this part.

2019 CALIFORNIA PLUMBING CODE 77

any other purpose or distributed to any other persons or parti es.

78 2019 CALIFORNIA PLUMBING CODE

CALIFORNIA PLUMBING CODE – MATRIX ADOPTION TABLE

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
    Overview
    1. 401.2 Quality of Fixtures. Plumbing fixtures shall be construc…
    2. 401.3 Water-Conserving Fixtures and Fittings.Note 1: [BSC, DSA…
    3. 402.2 Joints. Where a fixture comes in contact with the wall
    4. 402.3 Securing Fixtures. Floor-outlet or floor-mounted
    5. 402.4 Wall-Hung Fixtures. Wall-hung fixtures shall be
    6. 402.5 Setting. Fixtures shall be set level and in proper align…
    7. 402.6 Flanged Fixture Connections. Fixture connections between…
    8. 403.2 Fixtures and Fixture Fittings for Persons with
    9. 403.3 Exposed Pipes and Surfaces. Water supply and
    10. 404.2 Overflows. Where a fixture is provided with an overflow,…
    11. 405.2 Prohibited Urinals. Trough urinals and urinals with
    12. 405.3 Miscellaneous Fixtures. Fixed wooden, or tile
    13. 402.7 Supply Fittings. The supply lines and fittings for
    14. 402.8 Installation. Fixtures shall be installed in accordance
    15. 402.9 Design and Installation of Plumbing Fixtures. Plumbing f…
    16. 402.10 Slip Joint Connections. Fixtures having concealed slip …
    17. 402.11 Future Fixtures. Where provisions are made for the
    18. 406.2 Special Use Sinks. Restaurant kitchen and other
    19. 406.3 Special Use Fixtures. Special use fixtures shall be
    20. 406.4 Zinc Alloy Components. Zinc alloy components
    21. 407.2 Water Consumption. The maximum water flow rate of
    22. 407.4 Transient Public Lavatories. Self-closing or metering fa…
    23. 407.5 Waste Outlet. Lavatories shall have a waste outlet
    24. 407.6 Overflow. Where overflows are provided, they shall
    25. 408.2 Water Consumption. Showerheads shall have a
    26. 408.3 Individual Shower and Tub-Shower Combina-tion Control Va…
    27. 407.3 Limitation of Hot Water Temperature for PublicLavatories…
    28. 408.4 Waste Outlet. Showers shall have a waste outlet and
    29. 408.5 Finished Curb or Threshold. Where a shower
    30. 408.7 Lining for Showers and Receptors. Shower
    31. 408.6 Shower Compartments. Shower compartments,
    32. 408.8 Public Shower Floors. Floors of public shower
    33. 408.9 Location of Valves and Heads. Control valves and
    34. 408.10 Water Supply Riser. A water supply riser from the
    35. 409.2 Waste Outlet. Bathtubs and whirlpool bathtubs shall
    36. 409.3 Overflow. Where overflows are provided, they shall
    37. 409.4 Limitation of Hot Water in Bathtubs and
    38. 409.5 Backflow Protection. The water supply to a bathtub
    39. 409.6 Installation and Access. Bathtubs and whirlpool
    40. 410.2 Backflow Protection. The water supply to the bidet
    41. 410.3 Limitation of Water Temperature in Bidets. The
    42. 411.0 Water Closets.411.1 Application. Water closets shall com…
    43. 411.2 Water Consumption. The effective flush volume of
    44. 411.3 Water Closet Seats. Water closet seats shall be properly…
    45. 411.4 Personal Hygiene Devices. Water closets with integral pe…
    46. 412.0 Urinals.412.1 Application. Urinals shall comply with ASME
    47. 412.2 Backflow Protection. A water supply to a urinal
    48. 413.2 Flushometer Valves. Flushometer valves and
    49. 413.3 Flush Tanks. Flush tanks for manual flushing shall
    50. 413.4 Water Supply for Flush Tanks. An adequate quantity of wa…
    51. 413.5 Overflows in Flush Tanks. Flush tanks shall be provided …
    52. 414.2 Backflow Protection. The water supply connection
    53. 414.3 Drainage Connection. Domestic dishwashing
    54. 415.0 Drinking Fountains.415.1 Application. Drinking fountains…
    55. 415.2 Drinking Fountain Alternatives. Where food is
    56. 415.3 Drainage Connection. Drinking fountains shall be
    57. 415.4 Location. Drinking fountains shall not be installed in
    58. 416.2 Water Supply. Emergency eyewash and shower
    59. 416.3 Installation. Emergency eyewash and shower equipment sha…
    60. 416.4 Location. Emergency eyewash and shower equipment shall b…
    61. 416.5 Drain. A drain shall not be required for emergency
    62. 417.0 Faucets and Fixture Fittings.417.1 Application. Faucets …
    63. 417.2 Deck Mounted Bath/Shower Valves. Deck
    64. 417.3 Handheld Showers. Handheld showers shall comply
    65. 417.4 Faucets and Fixture Fittings with Hose Con-nected Outlet…
    66. 417.5 Separate Controls for Hot and Cold Water. Where two sepa…
    67. 418.2 Strainer. Floor drains shall be considered plumbing
    68. 418.3 Location of Floor Drains. Floor drains shall be
    69. 418.4 Food Storage Areas. Where drains are provided in
    70. 418.5 Floor Slope. Floors shall be sloped to floor drains.
    71. 419.2 Drainage Connection. Approved wye or other
    72. 419.3 Water Supply. A cold water supply shall be provided
    73. 420.2 Water Consumption. Sink faucets shall have a maximum flo…
    74. 420.3 Pre-Rinse Spray Valve. Commercial food service
    75. 420.4 Waste Outlet. Kitchen and laundry sinks shall have
    76. 421.2 Strainers. The waste outlet of a floor sink shall be
    77. 422.2 Separate Facilities. Separate toilet facilities shall
    78. 422.0 Minimum Number of Required Fixtures.422.1 Fixture Count.…
    79. 422.3 Fixture Requirements for Special Occupan-cies. Additiona…
    80. 422.4 Toilet Facilities Serving Employees and Cus-
    81. 422.5 Toilet Facilities for Workers. Toilet facilities shall
    82. 422.6 [CA] Cosmetology. Each school shall provide pub-
    83. 422.7 [CA] Cosmetology Establishments. Each estab-
    84. 422.8 [DPH] Commissaries Serving Mobile FoodPreparation Units.…
    85. 422.9 [DPH] Employee Lavatories in Food Establish-ments. Emplo…
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES