402.6 Flanged Fixture Connections.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Fixture connections between drainage pipes and water closets, floor outlet service sinks and urinals shall be made using an approved copper alloy, hard lead, ABS, PVC, or iron flanges caulked, soldered, solvent cemented; rubber compression gaskets; or screwed to the drainage pipe. The connection shall be bolted with an approved gasket, washer, or setting compound between the fixture and the connection. The bottom of the flange shall be set on an approved firm base.
Wall-mounted water closet fixtures shall be securely bolted to an approved carrier fitting. The connecting pipe between the carrier fitting and the fixture shall be an approved material and designed to accommodate an adequately sized gasket. Gasket material shall be neoprene, felt, or similar approved types.
402.6.1 Closet Rings (Closet Flanges). Closet rings (closet flanges) for water closets or similar fixtures shall be of an approved type and shall be copper alloy, copper, hard lead, cast-iron, galvanized malleable iron, ABS, PVC, or other approved materials. Each such closet ring (closet flange) shall be approximately 7 inches (178 mm) in diameter and, where installed, shall, together with the soil pipe, present a 1 1 ⁄2 inch (38 mm) wide flange or face to receive the fixture gasket or closet seal.
2019 CALIFORNIA PLUMBING CODE 57
PLUMBING FIXTURES AND FIXTURE FITTINGS any other purpose or distributed to any other persons or parti es.
Caulked-on closet rings (closet flanges) shall be not less than 1 ⁄4 of an inch (6.4 mm) thick and not less than 2 inches (51 mm) in overall depth.
Closet rings (closet flanges) shall be burned or soldered to lead bends or stubs, shall be caulked to cast-iron soil pipe, shall be solvent cemented to ABS and PVC, and shall be screwed or fastened in an approved manner to other materials.
Closet bends or stubs shall be cut-off to present a smooth surface even with the top of the closet ring before the rough inspection is called.
Closet rings (closet flanges) shall be adequately designed and secured to support fixtures connected thereto. 402.6.2 Securing Closet Flanges. Closet screws, bolts, washers, and similar fasteners shall be of copper alloy, copper, or other listed equally corrosion-resistant materials. Screws and bolts shall be of a size and number to properly support the fixture installed. 402.6.3 Securing Floor-Mounted, Back-Outlet Water Closet Bowls. Floor-mounted, back-outlet water closet bowls shall be set level with an angle of 90 degrees (1.57 rad) between the floor and wall at the centerline of the fixture outlet. The floor and wall shall have a flat mounting surface not less than 5 inches (127 mm) to the right and left of the fixture outlet centerline. The fixture shall be secured to the wall outlet flange or drainage connection and the floor by corrosion-resistant screws or bolts. The closet flange shall be secured to a firm base.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
▸Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
Overview- 401.2 Quality of Fixtures. Plumbing fixtures shall be construc…
- 401.3 Water-Conserving Fixtures and Fittings.Note 1: [BSC, DSA…
- 402.2 Joints. Where a fixture comes in contact with the wall
- 402.3 Securing Fixtures. Floor-outlet or floor-mounted
- 402.4 Wall-Hung Fixtures. Wall-hung fixtures shall be
- 402.5 Setting. Fixtures shall be set level and in proper align…
- 402.6 Flanged Fixture Connections. Fixture connections between…
- 403.2 Fixtures and Fixture Fittings for Persons with
- 403.3 Exposed Pipes and Surfaces. Water supply and
- 404.2 Overflows. Where a fixture is provided with an overflow,…
- 405.2 Prohibited Urinals. Trough urinals and urinals with
- 405.3 Miscellaneous Fixtures. Fixed wooden, or tile
- 402.7 Supply Fittings. The supply lines and fittings for
- 402.8 Installation. Fixtures shall be installed in accordance
- 402.9 Design and Installation of Plumbing Fixtures. Plumbing f…
- 402.10 Slip Joint Connections. Fixtures having concealed slip …
- 402.11 Future Fixtures. Where provisions are made for the
- 406.2 Special Use Sinks. Restaurant kitchen and other
- 406.3 Special Use Fixtures. Special use fixtures shall be
- 406.4 Zinc Alloy Components. Zinc alloy components
- 407.2 Water Consumption. The maximum water flow rate of
- 407.4 Transient Public Lavatories. Self-closing or metering fa…
- 407.5 Waste Outlet. Lavatories shall have a waste outlet
- 407.6 Overflow. Where overflows are provided, they shall
- 408.2 Water Consumption. Showerheads shall have a
- 408.3 Individual Shower and Tub-Shower Combina-tion Control Va…
- 407.3 Limitation of Hot Water Temperature for PublicLavatories…
- 408.4 Waste Outlet. Showers shall have a waste outlet and
- 408.5 Finished Curb or Threshold. Where a shower
- 408.7 Lining for Showers and Receptors. Shower
- 408.6 Shower Compartments. Shower compartments,
- 408.8 Public Shower Floors. Floors of public shower
- 408.9 Location of Valves and Heads. Control valves and
- 408.10 Water Supply Riser. A water supply riser from the
- 409.2 Waste Outlet. Bathtubs and whirlpool bathtubs shall
- 409.3 Overflow. Where overflows are provided, they shall
- 409.4 Limitation of Hot Water in Bathtubs and
- 409.5 Backflow Protection. The water supply to a bathtub
- 409.6 Installation and Access. Bathtubs and whirlpool
- 410.2 Backflow Protection. The water supply to the bidet
- 410.3 Limitation of Water Temperature in Bidets. The
- 411.0 Water Closets.411.1 Application. Water closets shall com…
- 411.2 Water Consumption. The effective flush volume of
- 411.3 Water Closet Seats. Water closet seats shall be properly…
- 411.4 Personal Hygiene Devices. Water closets with integral pe…
- 412.0 Urinals.412.1 Application. Urinals shall comply with ASME
- 412.2 Backflow Protection. A water supply to a urinal
- 413.2 Flushometer Valves. Flushometer valves and
- 413.3 Flush Tanks. Flush tanks for manual flushing shall
- 413.4 Water Supply for Flush Tanks. An adequate quantity of wa…
- 413.5 Overflows in Flush Tanks. Flush tanks shall be provided …
- 414.2 Backflow Protection. The water supply connection
- 414.3 Drainage Connection. Domestic dishwashing
- 415.0 Drinking Fountains.415.1 Application. Drinking fountains…
- 415.2 Drinking Fountain Alternatives. Where food is
- 415.3 Drainage Connection. Drinking fountains shall be
- 415.4 Location. Drinking fountains shall not be installed in
- 416.2 Water Supply. Emergency eyewash and shower
- 416.3 Installation. Emergency eyewash and shower equipment sha…
- 416.4 Location. Emergency eyewash and shower equipment shall b…
- 416.5 Drain. A drain shall not be required for emergency
- 417.0 Faucets and Fixture Fittings.417.1 Application. Faucets …
- 417.2 Deck Mounted Bath/Shower Valves. Deck
- 417.3 Handheld Showers. Handheld showers shall comply
- 417.4 Faucets and Fixture Fittings with Hose Con-nected Outlet…
- 417.5 Separate Controls for Hot and Cold Water. Where two sepa…
- 418.2 Strainer. Floor drains shall be considered plumbing
- 418.3 Location of Floor Drains. Floor drains shall be
- 418.4 Food Storage Areas. Where drains are provided in
- 418.5 Floor Slope. Floors shall be sloped to floor drains.
- 419.2 Drainage Connection. Approved wye or other
- 419.3 Water Supply. A cold water supply shall be provided
- 420.2 Water Consumption. Sink faucets shall have a maximum flo…
- 420.3 Pre-Rinse Spray Valve. Commercial food service
- 420.4 Waste Outlet. Kitchen and laundry sinks shall have
- 421.2 Strainers. The waste outlet of a floor sink shall be
- 422.2 Separate Facilities. Separate toilet facilities shall
- 422.0 Minimum Number of Required Fixtures.422.1 Fixture Count.…
- 422.3 Fixture Requirements for Special Occupan-cies. Additiona…
- 422.4 Toilet Facilities Serving Employees and Cus-
- 422.5 Toilet Facilities for Workers. Toilet facilities shall
- 422.6 [CA] Cosmetology. Each school shall provide pub-
- 422.7 [CA] Cosmetology Establishments. Each estab-
- 422.8 [DPH] Commissaries Serving Mobile FoodPreparation Units.…
- 422.9 [DPH] Employee Lavatories in Food Establish-ments. Emplo…
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR