610.8 Size of Meter and Building Supply Pipe UsingTable 610.4.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
The size of the meter and the building supply pipe shall be determined as follows: (1) Determine the available pressure at the water meter or
other source of supply.
(1) Determine the available pressure at the water meter or
other source of supply. (2) Add or subtract depending on positive or negative ele vation change, 1 ⁄2 psi (3.4 kPa) for each foot (305 mm) of
| INDIVIDUAL | FIXTURE UNITS | |
|---|---|---|
| NUMBER OF | FIXTURE UNITS | ASSIGNED FOR WATER |
| FLUSHOMETER VALVES 5 or more |
ASSIGNED IN DECREASING VALUE 10 each |
CLOSETS AND SIMILAR 10-UNIT FIXTURES IN ACCUMULATIVE VALUES additional fixture in excess of 5 |
| FIXTURE CATEG | ** ORY: URINALS WITH F** | ** LUSHOMETER VALVES** |
(2) Add or subtract depending on positive or negative ele vation change, 1 ⁄2 psi (3.4 kPa) for each foot (305 mm) of difference in elevation between such source of supply and the highest water supply outlet in the building or on the premises. (3) Use the “pressure range” group within which this pres sure will fall using Table 610.4.
(3) Use the “pressure range” group within which this pres sure will fall using Table 610.4. (4) Select the “length” column that is equal to or longer than
the required length.
(4) Select the “length” column that is equal to or longer than
the required length. (5) Follow down the column to a fixture unit value equal to
or exceeding the total number of fixture units required
(5) Follow down the column to a fixture unit value equal to
or exceeding the total number of fixture units required by the installation. (6) Having located the proper fixture unit value for the
required length, sizes of meter and building supply pipe
Having located the proper fixture unit value for the
required length, sizes of meter and building supply pipe as found in the two left-hand columns shall be applied.
| NUMBER OF FLUSHOMETER VALVES |
INDIVIDUAL FIXTURE UNITS ASSIGNED IN DECREASING |
FIXTURE UNITS ASSIGNED FOR URINALS AND SIMILAR 5-UNIT FIXTURES IN |
|---|---|---|
5 or more |
VALUE 5 each |
ACCUMULATIVE VALUES tional fixture in excess of 5 |
156 2019 CALIFORNIA PLUMBING CODE
WATER SUPPLY AND DISTRIBUTION
In the example below, fixture units assigned to each section of pipe are computed. Each capital letter refers to the section of pipe above it unless otherwise shown.
LAV LAV UR UR WC WC
610.12.1 Copper Tube Systems. Maximum velocities in copper and copper alloy tube and fitting systems shall not exceed 8 feet per second (ft/s) (2.4 m/s) in cold water and 5 ft/s (1.5 m/s) in hot water. 610.12.2 Tubing Systems Using Copper Fittings. Maximum velocities through copper fittings in tubing other than copper shall not exceed 8 ft/s (2.4 m/s) in cold water and 5 ft/s (1.5 m/s) in hot water.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
▸Chapter 6 — WATER SUPPLY AND DISTRIBUTION
Overview- 601.2 Hot and Cold Water Required. Except where not
- 601.3 Identification of a Potable and NonpotableWater System. …
- 601.5 [AGR] Meat and Poultry Processing Plants. Except as prov…
- 601.4 [CA] Schools of Cosmetology and Cosmeto-
- 601.6 [AGR] Collection Centers and Facilities.601.6.1 The wate…
- 601.7 [AGR] Renderers. This area shall be provided with
- 601.8 [AGR] Horse Meat and Pet Food Establishments.601.8.1 The…
- 602.3 Backflow Prevention. No plumbing fixture, device,
- 602.4 Approval by Authority. No water piping supplied
- 603.0 Cross-Connection Control.603.1 General. Cross-connection…
- 603.2 Approval of Devices or Assemblies. Before a
- 602.0 Unlawful Connections.602.1 Prohibited Installation. No i…
- 602.2 Cross-Contamination. No person shall make a connection o…
- 603.3 Backflow Prevention Devices, Assemblies, andMethods. Bac…
- 603.4 General Requirements. Assemblies shall comply
- 603.5 Specific Requirements. Specific requirements for
- 604.0 Materials.604.1 Pipe, Tube, and Fittings. Pipe, tube, fi…
- 604.2 Lead Content. The maximum allowable lead content in pipe…
- 604.3 Copper or Copper Alloy Tube. Copper or copper
- 604.4 Hard-Drawn Copper or Copper Alloy Tubing. Hard-drawn cop…
- 604.5 Flexible Connectors. Flexible water connectors
- 604.6 Cast-Iron Fittings. Cast-iron fittings up to and
- 604.7 Malleable Iron Fittings. Malleable iron water fittings s…
- 604.8 Previously Used Piping and Tubing. Piping and
- 604.9 Epoxy Coating. The epoxy coating used on existing, under…
- 604.10 Plastic Materials. Approved plastic materials shall
- 605.0 Joints and Connections.
- 604.11 Solder. Solder shall comply with the requirements of
- 604.12 Flexible Corrugated Connectors. Flexible corrugated con…
- 604.13 Water Heater Connectors. Flexible metallic (copper and …
- 605.2 CPVC Plastic Pipe and Joints. CPVC plastic pipe
- 605.3 CPVC/AL/CPVC Plastic Pipe and Joints. Chlorinated polyvi…
- 605.4 Ductile Iron Pipe and Joints. Ductile iron pipe
- 605.5 Galvanized Steel Pipe and Joints. Galvanized
- 605.6 PE Plastic Pipe/Tubing and Joints. PE plastic
- 605.7 PE-AL-PE Plastic Pipe/Tubing and Joints. PEAL-PE plastic…
- 605.8 PE-RT. Polyethylene of raised temperature (PE-RT)
- 605.9 PEX Plastic Tubing and Joints. PEX plastic tubing and fi…
- 605.11 Polypropylene (PP) Piping and Joints. PP pipe
- 605.10 PEX-AL-PEX Plastic Tubing and Joints. PEXAL-PEX plastic…
- 605.12 PVC Plastic Pipe and Joints. PVC plastic pipe
- 605.13 Stainless Steel Pipe and Joints. Joining methods for st…
- 605.14 Slip Joints. In water piping, slip joints shall be perm…
- 605.15 Dielectric Unions. Dielectric unions where
- 605.16 Joints Between Various Materials. Joints
- 606.0 Valves.606.1 General. Valves up to and including 2 inche…
- 606.2 Fullway Valve. A fullway valve controlling outlets
- 606.3 Multidwelling Units. In multidwelling units, one or
- 606.4 Multiple Openings. Valves used to control two or
- 606.5 Control Valve. A control valve shall be installed
- 606.6 Accessible. Required shutoff or control valves shall
- 606.7 Multiple Fixtures. A single control valve shall be
- 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5] Each riser or branch
- 607.2 Potable Water Tanks. Potable water supply tanks,
- 607.3 Venting. Tanks used for potable water shall be tightly
- 607.4 Overflow. Tanks shall have not less than a 16 square
- 607.5 Valves. Pressurized tanks shall be provided with a
- 608.0 Water Pressure, Pressure Regulators, Pres-
- 608.2 Excessive Water Pressure. Where static water
- 608.3 Expansion Tanks, and Combination Tempera-ture and Pressu…
- 608.4 Pressure Relief Valves. Each pressure relief valve
- 608.5 Discharge Piping. The discharge piping serving a
- 609.3 Under Concrete Slab. Water piping installed within
- 608.6 Water-Heating Devices. A water-heating device
- 608.7 Vacuum Relief Valves. Where a hot-water storage
- 609.0 Installation, Testing, Unions, and Location.609.1 Instal…
- 609.2 Trenches. Water pipes shall not be run or laid in the
- 609.4 Testing. Upon completion of a section or of the entire
- 609.5 Unions. Unions shall be installed in the water supply
- 609.6 Location. Except as provided in Section 609.7, no
- 609.7 Abutting Lot. Nothing contained in this code shall
- 609.8 Low-Pressure Cutoff Required on BoosterPumps for Water D…
- 609.9 Disinfection of Potable Water System. New or
- 609.11 Pipe Insulation. Insulation of domestic hot water
- 610.2 Pressure Loss. Where a water filter, water softener,
- 609.10 Water Hammer. [Not adopted by HCD] Building water suppl…
- 610.3 Quantity of Water. The quantity of water required
- 610.4 Sizing Water Supply and Distribution Systems. Systems wi…
- 610.5 Sizing per Appendices A and C. Except as provided in Sec…
- 610.6 Friction and Pressure Loss. Except where the type
- 610.7 Conditions for Using Table 610.4. On a proposed
- 610.9 Size of Branches. Where Table 610.4 is used, the minimum…
- 610.10 Sizing for Flushometer Valves. Where using
- 610.8 Size of Meter and Building Supply Pipe UsingTable 610.4.…
- 610.13 Exceptions. The provisions of this section relative
- 610.12 Sizing for Velocity. Water piping systems shall not
- 610.11 Sizing Systems for Flushometer Tanks. The
- 611.2 Air Gap Discharge. Discharge from drinking water
- 611.3 Connection Tubing. The tubing to and from drinking water…
- 611.4 Sizing of Residential Softeners. Residential-use
- 612.0 Residential Fire Sprinkler Systems.612.1 Where Required.…
- 612.2 Types of Systems. This section shall apply to standalone…
- 612.3 Sprinklers. Sprinklers shall be installed in accordance …
- 612.4 Sprinkler Piping System. Sprinkler piping systems
- 612.5 Sprinkler Piping Design. Sprinkler piping systems
- 612.6 Instructions and Signs. An owner’s manual for the
- 612.7 Inspection and Testing. The inspection and testing of sp…
- 613.0 [OSHPD 1, 1R, 2, 3, 4 & 5] Domestic Hot-Water
- 613.2 At least two pieces of hot-water-heating equipment shall
- 613.3 Instantaneous heaters are permitted for supplying hot
- 613.4 Water storage tanks shall be fabricated of corrosion-
- 613.5 Temperature control valves shall be provided to auto-
- 613.6 Hot-water distribution system serving patient care
- 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
- 613.8 Sectionalizing valves shall be provided as required by
- 614.2 All piping for multistation or central dialysis units sh…
- 614.3 All valves shall be located in accessible locations.
- 614.4 Piping and valves shall be identified according to their
- 614.5 A means of preventing backwashing or flushing of the
- 614.6 A continuous audible alarm shall sound at the nurses’
- 614.7 Water used for dialysis treatment shall meet the latest
- 614.8 A diagram of all piping as installed shall be posted at …
- 615.1 Uses Not Permitted.615.1.1 [OSHPD 1, 1R, 2, 3, 4 & 5] No…
- 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5] Non-potable water sys-
- 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5] Outlets for non-potable
- 615.4 [OSHPD 1] Emergency Water Supply.615.4.1 For new acute c…
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR