1212.1 Connecting Appliances and Equipment.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Appliances and equipment shall be connected to the building piping in compliance with Section 1212.5 through Section 1212.8 by one of the following: (1) Rigid metallic pipe and fittings. (2) Semirigid metallic tubing and metallic fittings. Aluminum
alloy tubing shall not be used in exterior locations.
(1) An appliance shutoff valve shall be installed where
the connector is attached to the building piping. (2) The connector shall be of minimum length and shall
not exceed 6 feet (1829 mm).
(2) The connector shall be of minimum length and shall
not exceed 6 feet (1829 mm). (3) The connector shall not be concealed and shall not
extend from one room to another or pass through
(2) Semirigid metallic tubing and metallic fittings. Aluminum
alloy tubing shall not be used in exterior locations. (3) A listed connector in compliance with CSA Z21.24. The
connector shall be used in accordance with the manu
(3) A listed connector in compliance with CSA Z21.24. The
connector shall be used in accordance with the manufacturer’s installation instructions and shall be in the same room as the appliance. Only one connector shall be used per appliance. (4) A listed connector in compliance with CSA Z21.75. Only
one connector shall be used per appliance.
(3) The connector shall not be concealed and shall not
extend from one room to another or pass through wall partitions, ceilings, or floors. [NFPA 54:9.6.2(1)] 1212.3.2 Outdoor. Where outdoor gas hose connectors are used to connect portable outdoor appliances, the connector shall be listed in accordance with CSA Z21.54 and installed in accordance with the following: (1) An appliance shutoff valve, a listed quick-discon nect device, or a listed gas convenience outlet shall
(4) A listed connector in compliance with CSA Z21.75. Only
one connector shall be used per appliance. (5) CSST where installed in accordance with the manufac turer’s installation instructions.
(1) An appliance shutoff valve, a listed quick-discon nect device, or a listed gas convenience outlet shall be installed where the connector is attached to the supply piping and in such a manner to prevent the accumulation of water or foreign matter. (2) This connection shall be made only in the outdoor
area where the appliance is to be used. [NFPA
(5) CSST where installed in accordance with the manufac turer’s installation instructions. (6) Listed nonmetallic gas hose connectors in accordance
with Section 1212.3.
(6) Listed nonmetallic gas hose connectors in accordance
with Section 1212.3. (7) Unlisted gas hose connectors for use in laboratories and
educational facilities in accordance with Section 1212.4.
Unlisted gas hose connectors for use in laboratories and
educational facilities in accordance with Section 1212.4.
[NFPA 54:9.6.1]
(2) This connection shall be made only in the outdoor
area where the appliance is to be used. [NFPA 54:9.6.2(2)] The connector length shall not exceed 15 feet (4572 mm).
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
▸Chapter 12 — FUEL GAS PIPING
Overview- 1201.0 General.1201.1 Applicability. The regulations of this c…
- 1202.0 Coverage of Piping System.1202.1 General. Coverage of p…
- 1202.2 Piping System Requirements. Requirements for
- 1202.3 Applications. This code shall not apply to the followin…
- 1203.2 Excavation. Excavations required for the installation o…
- 1203.3 Type of Inspections. The Authority Having Jurisdiction …
- 1203.4 Inspection Waived. In cases where the work
- 1204.2 Gas Supplier. A copy of the certificate of such final
- 1204.3 Unlawful. It shall be unlawful for a serving gas suppli…
- 1205.2 Outlets. It shall be unlawful to turn on or connect gas
- 1206.2 Notice. Where such disconnection has been made, a
- 1206.3 Capped Outlets. It shall be unlawful to remove or
- 1208.0 Gas Piping System Design, Materials, and
- 1208.2 Provision for Location of Point of Delivery. The locati…
- 1208.3 Interconnections Between Gas Piping Sys-tems. Where two…
- 1208.4 Sizing of Gas Piping Systems. Gas piping systems shall …
- 1208.5 Maximum Design Operating Pressure. The
- 1208.6 Acceptable Piping Materials and JoiningMethods. Materia…
- 1208.7 Gas Meters. Gas meters shall be selected for the
- 1208.8 Gas Pressure Regulators. A line pressure regulator or g…
- 1208.9 Overpressure Protection Devices. Where the
- 1208.10 Pressure Limitation Requirements. Where
- 1208.11 Backpressure Protection. Protective devices
- 1208.12 Low-Pressure Protection. A protective device
- 1208.13 Shutoff Valves. Shutoff valves shall be approved
- 1208.14 Expansion and Flexibility. Piping systems shall
- 1210.0 Gas Piping Installation.1210.1 Piping Underground. Unde…
- 1210.2 Installation of Piping. Piping installed aboveground sh…
- 1210.3 Concealed Piping in Buildings. Gas piping in
- 1210.4 Piping in Vertical Chases. Where gas piping
- 1210.6 Drips and Sediment Traps. For other than dry gas
- 1210.7 Outlets. Outlets shall be located and installed in
- 1210.5 Gas Pipe Turns. Changes in direction of gas pipe
- 1210.10 Prohibited Devices. No device shall be placed
- 1210.11 Systems Containing Gas-Air Mixtures Out-side the Flamm…
- 1210.12 Systems Containing Flammable Gas-AirMixtures. Systems …
- 1210.8 Branch Pipe Connection. Where a branch outlet
- 1210.9 Manual Gas Shutoff Valves. An accessible gas
- 1211.2 Bonding of CSST Gas Piping. CSST gas piping
- 1211.3 Prohibited Use. Gas piping shall not be used as a
- 1211.4 Lightning Protection System. Where a lightning
- 1211.5 Electrical Circuits. Electrical circuits shall not util…
- 1211.6 Electrical Connections. All electrical connections
- 1211.7 Earthquake-Actuated Gas Shutoff Valves. Earth-
- 1212.2 Suspended Low-Intensity Infrared TubeHeaters. Suspended…
- 1212.3 Use of Nonmetallic Gas Hose Connectors. Listed gas hose…
- 1212.1 Connecting Appliances and Equipment.
- 1212.4 Injection (Bunsen) Burners. Injection (Bunsen)
- 1212.5 Connection of Portable and Mobile Industrial
- 1212.5 Connection of Portable and Mobile Industrial
- 1212.9 Sediment Trap. Where a sediment trap is not incorporate…
- 1212.6 Appliance Shutoff Valves and Connections.
- 1212.7 Quick-Disconnect Devices. Quick-disconnect
- 1212.8 Gas Convenience Outlets. Appliances shall be
- 1212.10 Installation of Piping. Piping shall be installed in
- 1212.11 Liquefied Petroleum Gas Facilities and Pip-
- 1213.0 Pressure Testing, Inspection, and Purging.1213.1 Piping…
- 1213.2 Test Preparation. Test preparation shall comply
- 1213.3 Test Pressure. This inspection shall include an air,
- 1213.4 Detection of Leaks and Defects. The piping system shall…
- 1213.5 Piping System Leak Test. Leak checks using fuel
- 1213.6 Purging Requirements. The purging of piping
- 1215.2 Tables for Sizing Gas Piping Systems. Table
- 1215.3 Sizing Equations. The inside diameter of smoothwall pip…
- 1214.2 Volume. The hourly volume of gas required at each
- 1214.3 Gas Appliances. Where the gas appliances to be
- 1214.4 Size of Piping Outlets. The size of the supply piping o…
- 1215.0 Required Gas Piping Size.1215.1 Pipe Sizing Methods. Wh…
- 1215.5 Engineering Methods. For conditions other than
- 1215.6 Variable Gas Pressure. Where the supply gas
- 1215.4 Sizing of Piping Sections. To determine the size
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR