1208.6 Acceptable Piping Materials and JoiningMethods.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Materials used for piping systems shall either comply with the requirements of this chapter or be acceptable to the Authority Having Jurisdiction. [NFPA 54:5.6.1.1]
« « «
| APPLIANCE | INPUT (Btu/h approx.) |
|---|---|
Warm air furnace Single family Multifamily, per unit Hydronic boiler Single family Multifamily, per unit |
100 000 60 000 100 000 60 000 |
Hydronic boiler Single-family Multifamily, per unit |
120 000 75 000 |
Water heater, automatic storage 30 to 40 gallon tank Water heater, automatic storage 50 gallon tank Water heater, automatic instantaneous Capacity at 2 gallons per minute Capacity at 4 gallons per minute Capacity at 6 gallons per minute Water heater, domestic, circulating or side-arm |
35 000 50 000 142 800 285 000 428 400 35 000 |
Range, freestanding, domestic Built-in oven or broiler unit, domestic Built-in top unit, domestic |
65 000 25 000 40 000 |
Refrigerator Clothes dryer, Type 1 (domestic) Gas fireplace direct vent Gas log Barbecue Gaslight |
3000 35 000 40 000 80 000 40 000 2500 |
1208.4.2 Sizing Methods. Gas piping shall be sized in accordance with one of the following: (1) Pipe sizing tables or sizing equations in this chap ter.
1208.6.1 Used Materials. Pipe, fittings, valves, or other materials shall not be used again unless they are free of foreign materials and have been ascertained to be approved for the service intended. [NFPA 54:5.6.1.2] 1208.6.2 Other Materials. Material not covered by the standards specifications listed herein shall meet the following criteria: (1) Be investigated and tested to determine that it is safe
and suitable for the proposed service.
(1) Pipe sizing tables or sizing equations in this chap ter. (2) Other approved engineering methods acceptable to
the Authority Having Jurisdiction.
(1) Be investigated and tested to determine that it is safe
and suitable for the proposed service. (2) Be recommended for that service by the manufac turer.
(2) Be recommended for that service by the manufac turer. (3) Be acceptable to the Authority Having Jurisdiction.
[NFPA 54:5.6.1.3]
[NFPA 54:5.6.1.3]
the Authority Having Jurisdiction.
2019 CALIFORNIA PLUMBING CODE 223
» » » » » » » » » »
FUEL GAS PIPING any other purpose or distributed to any other persons or parti es.
1208.6.4.1 Steel Tubing. Steel tubing shall comply with ASTM A254. [NFPA 54:5.6.3.1] 1208.6.4.2 Copper and Copper Alloy Tubing. Copper and copper alloy tubing shall not be used where the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 scf of gas (0.7 mg/100 L). Copper tubing shall comply with standard Type K or L of ASTM B88 or ASTM B280.
[NFPA 54:5.6.3.2] 1208.6.4.3 Aluminum Alloy Tubing. Aluminum alloy tubing shall comply with ASTM B210 or ASTM B241. Aluminum alloy tubing shall be coated to protect against external corrosion where it is in contact with masonry, plaster, insulation, or is subject to repeated wettings by such liquids as water, detergent, or sewage. Aluminum alloy tubing shall not be used in exterior locations or underground.
[NFPA 54:5.6.3.3] 1208.6.4.4 Corrugated Stainless Steel Tub- ing. Corrugated stainless steel tubing shall be listed in accordance with CSA LC-1. [NFPA 54:5.6.3.4] 1208.6.5 Plastic Pipe, Tubing, and Fittings. Polyethylene plastic pipe, tubing, and fittings used to supply fuel gas shall conform to ASTM D2513. Pipe to be used shall be marked “gas” and “ASTM D2513.” Polyvinyl chloride (PVC) and chlorinated polyvinyl chloride
1208.6.10.1 Damaged Threads. Pipe with threads that are stripped, chipped, corroded, or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. [NFPA 54:5.6.7.2] 1208.6.10.2 Number of Threads. Field threading of metallic pipe shall be in accordance with Table 1208.6.10.2. [NFPA 54:5.6.7.3] 1208.6.10.3 Thread Joint Compounds. Thread joint compounds shall be resistant to the action of LP-Gas or to any other chemical constituents of the gases to be conducted through the piping. [NFPA 54:5.6.7.4] 1208.6.11 Metallic Piping Joints and Fittings. The type of piping joint used shall be suitable for the pressure and temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force due to the internal pressure and any additional forces due to temperature expansion or contraction, vibration, fatigue, or the weight of the pipe and its contents. [NFPA 54:5.6.8]
1208.6.3 Metallic Pipe. Cast-iron pipe shall not be used. [NFPA 54:5.6.2.1]
1208.6.3.1 Steel and Wrought-Iron Pipe. Steel and wrought-iron pipe shall be at least of standard weight (Schedule 40) and shall comply with one of the following standards: (1) ASME B36.10 (2) ASTM A53 (3) ASTM A106 [NFPA 54:5.6.2.2] 1208.6.3.2 Copper and Copper Alloy Pipe. Copper and copper alloy pipe shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet (scf) of gas (0.7 mg/100 L).
-iron pipe shall be at least of standard weight (Schedule 40) and shall comply with one of the following standards: (1) ASME B36.10 (2) ASTM A53 (3) ASTM A106 [NFPA 54:5.6.2.2] 1208.6.3.2 Copper and Copper Alloy Pipe. Copper and copper alloy pipe shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet (scf) of gas (0.7 mg/100 L).
(CPVC) plastic pipe, tubing, and fittings shall not be used to supply fuel gas. [NFPA 54:5.6.4.1.1 – 5.6.4.1.3] 1208.6.6 Regulator Vent Piping. Plastic pipe and fittings used to connect regulator vents to remote vent terminations shall be PVC conforming to UL 651(Schedule 40 and 80). PVC vent piping shall not be installed indoors. [NFPA 54:5.6.4.2] 1208.6.7 Anodeless Risers. Anodeless risers shall comply with the following: (1) Factory-assembled anodeless risers shall be recom mended by the manufacturer for the gas used and shall be
Threaded copper, copper alloy, or aluminum alloy pipe shall not be used with gases corrosive to such material. [NFPA 54:5.6.2.3 – 5.6.2.4] 1208.6.3.3 Aluminum Alloy Pipe. Aluminum alloy pipe shall comply with ASTM B241 (except that the use of alloy 5456 is prohibited) and shall be marked at each end of each length indicating compliance. Aluminum alloy pipe shall be coated to protect against external corrosion where it is in contact with masonry, plaster, insulation or is subject to repeated wettings by such liquids as water, detergents, or sewage. [NFPA 54:5.6.2.5]
(1) Factory-assembled anodeless risers shall be recom mended by the manufacturer for the gas used and shall be leak-tested by the manufacturer in accordance with written procedures. (2) Service head adapters and field-assembled anodeless ris ers incorporating service head adapters shall be recom
(2) Service head adapters and field-assembled anodeless ris ers incorporating service head adapters shall be recommended by the manufacturer for the gas used and shall be design-certified to be in accordance with the requirements of Category I of ASTM D2513. The manufacturer shall provide the user qualified installation instructions. (3) The use of plastic pipe, tubing, and fittings in undiluted
LP-Gas piping systems shall be in accordance with
(3) The use of plastic pipe, tubing, and fittings in undiluted
LP-Gas piping systems shall be in accordance with NFPA 58. [NFPA 54:5.6.4.3(3)] 1208.6.8 Workmanship and Defects. Gas pipe, tubing, and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed and chip and scale blown. Defects in pipe, tubing, and fittings shall not be repaired. Defective pipe, tubing, and fittings shall be replaced. [NFPA 54:5.6.5] 1208.6.9 Protective Coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion-resistant material shall be used. External or internal coatings or linings used on piping or components shall not be considered as adding strength.
all not be repaired. Defective pipe, tubing, and fittings shall be replaced. [NFPA 54:5.6.5] 1208.6.9 Protective Coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion-resistant material shall be used. External or internal coatings or linings used on piping or components shall not be considered as adding strength.
[NFPA 54:5.6.6] 1208.6.10 Metallic Pipe Threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1.20.1. [NFPA 54:5.6.7.1]
Aluminum alloy pipe shall not be used in exterior locations or underground. [NFPA 54:5.6.2.6] 1208.6.4 Metallic Tubing. Seamless copper, aluminum alloy, or steel tubing shall not be used with gases corrosive to such material. [NFPA 54:5.6.3]
« « « «
« «
«
«
224 2019 CALIFORNIA PLUMBING CODE
FUEL GAS PIPING
»
FUEL GAS PIPING
TABLE 1208.6.10.2 SPECIFICATIONS FOR THREADING METALLIC PIPE
[NFPA 54: TABLE 5.6.7.3]
(a) Flanges shall be permitted. (b) Bushings shall not be used. (c) Fittings shall not be used in systems con taining flammable gas-air mixtures.
(c) Fittings shall not be used in systems con taining flammable gas-air mixtures. (d) Fittings in sizes 4 inches (100 mm) and
larger shall not be used indoors unless
(d) Fittings in sizes 4 inches (100 mm) and
larger shall not be used indoors unless approved by the Authority Having Jurisdiction. (e) Fittings in sizes 6 inches (150 mm) and
larger shall not be used unless approved by
(e) Fittings in sizes 6 inches (150 mm) and
larger shall not be used unless approved by the Authority Having Jurisdiction. (6) Aluminum alloy fitting threads shall not form
the joint seal.
(6) Aluminum alloy fitting threads shall not form
the joint seal. (7) Zinc-aluminum alloy fittings shall not be used
in systems containing flammable gas-air mix
(7) Zinc-aluminum alloy fittings shall not be used
in systems containing flammable gas-air mixtures. (8) Special fittings such as couplings; proprietary type joints; saddle tees; gland-type compression
» » » »
| IRON PIPE SIZE (inches) |
APPROXIMATE LENGTH OF THREADED PORTION (inches) |
APPROXIMATE NUMBER OF THREADS TO BE CUT |
|---|---|---|
| ~~1⁄~~2 |
~~3⁄~~4 |
|
| ~~3⁄~~4 |
~~3⁄~~4 |
|
| ~~7⁄~~8 |
||
| ~~11⁄~~4 |
||
| ~~11⁄~~2 |
||
| ~~21⁄~~2 |
~~11⁄~~2 |
|
| ~~11⁄~~2 |
||
~~15⁄~~8 |
1208.6.11.1 Pipe Joints. Pipe joints shall be threaded, flanged, brazed, welded, or press-connect fittings that comply with CSA LC-4. Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1000°F (538°C). Brazing alloys shall not contain more than 0.05 percent phosphorus. [NFPA 54:5.6.8.1] 1208.6.11.2 Tubing Joints. Tubing joints shall be made with approved gas tubing fittings, be brazed with a material having a melting point in excess of 1000°F (538°C), or made by press-connect fittings that comply with CSA LC-4. Brazing alloys shall not contain more than 0.05 percent phosphorus.
[NFPA 54:5.6.8.2] 1208.6.11.3 Flared Joints. Flared joints shall be used only in systems constructed from nonferrous pipe and tubing where experience or tests have demonstrated that the joint is approved for the conditions and where provisions are made in the design to prevent separation of the joints. [NFPA 54:5.6.8.3] Valves, Strainers, Filters).1208.6.11.4 Metallic Pipe Fittings (Including Metallic pipe fittings shall comply with the following: (1) Threaded fittings in sizes larger than 4 inches
(100 mm) shall not be used unless approved by
Special fittings such as couplings; proprietary type joints; saddle tees; gland-type compression fittings; and flared, flareless, or compressiontype tubing fittings shall be as follows: (a) Used within the fitting manufacturer’s
pressure-temperature recommendations.
(a) Used within the fitting manufacturer’s
pressure-temperature recommendations. (b) Used within the service conditions antici pated with respect to vibration, fatigue,
(b) Used within the service conditions antici pated with respect to vibration, fatigue, thermal expansion, or contraction. (c) Installed or braced to prevent separation of
the joint by gas pressure or external physi
(c) Installed or braced to prevent separation of
the joint by gas pressure or external physical damage. (d) Approved by the Authority Having Juris diction. [NFPA 54:5.6.8.4 (1-8)]
« « « «
(1) Threaded fittings in sizes larger than 4 inches
(100 mm) shall not be used unless approved by the Authority Having Jurisdiction. (2) Fittings used with steel or wrought-iron pipe
shall be steel, copper alloy, malleable iron, or
(2) Fittings used with steel or wrought-iron pipe
shall be steel, copper alloy, malleable iron, or cast-iron. (3) Fittings used with copper or copper alloy pipe
shall be copper or copper alloy.
(3) Fittings used with copper or copper alloy pipe
shall be copper or copper alloy. (4) Fittings used with aluminum alloy pipe shall be
of aluminum alloy.
(4) Fittings used with aluminum alloy pipe shall be
of aluminum alloy. (5) Cast-iron fittings shall comply with the follow ing:
(d) Approved by the Authority Having Juris diction. [NFPA 54:5.6.8.4 (1-8)] 1208.6.12 Plastic Piping, Joints, and Fittings. Plastic pipe, tubing, and fittings shall be installed in accordance with the manufacturer’s installation instructions. Section 1208.6.12.1 through Section 1208.6.12.4 shall be observed where making such joints. [NFPA 54:5.6.9] 1208.6.12.1 Joint Design. The joint shall be designed and installed so that the longitudinal pullout resistance of the joint will be at least equal to the tensile strength of the plastic piping material. [NFPA 54:5.6.9(1)] 1208.6.12.2 Heat-Fusion Joint. Heat-fusion joints shall be made in accordance with qualified procedures that have been established and proven by test to produce gastight joints as strong as the pipe or tubing being joined. Joints shall be made with the joining method recommended by the pipe manufacturer. Heat-fusion fittings shall be marked “ASTM D2513.” [NFPA 54:5.6.9(2)] 1208.6.12.3 Compression-Type MechanicalJoints. Where compression-type mechanical joints are used, the gasket material in the fitting shall be compatible with the plastic piping and with the gas distributed by the system. An internal tubular rigid stiffener shall be used in conjunction with the fit
ing:
2019 CALIFORNIA PLUMBING CODE 225
FUEL GAS PIPING any other purpose or distributed to any other persons or parti es.
» »
«
«
» » » »
ting. The stiffener shall be flush with the end of the pipe or tubing and shall extend not less than the outside end of the compression fitting where installed. The stiffener shall be free of rough or sharp edges and shall not be a forced fit in the plastic. Split tubular stiffeners shall not be used. [NFPA 54:5.6.9(3)] 1208.6.12.4 Liquefied Petroleum Gas PipingSystems. Plastic piping joints and fittings for use in LP-Gas piping systems shall be in accordance with NFPA 58. [NFPA 54:5.6.9(4)] 1208.6.13 Flange Specification. Flanges shall comply with Section 1208.6.13.1 through Section 1208.6.13.7. 1208.6.13.1 Cast Iron Flanges. Cast iron flanges shall be in accordance with ASME B16.1. [NFPA 54:5.6.10.1.1] 1208.6.13.2 Steel Flanges. Steel flanges shall be in accordance with the following: (1) ASME B16.5 or (2) ASME B16.47. [NFPA 54:5.6.10.1.2] 1208.6.13.3 Non-Ferrous Flanges. Non-ferrous flanges shall be in accordance with ASME B16.24.
[NFPA 54:5.6.10.1.3] 1208.6.13.4 Ductile Iron Flanges. Ductile iron flanges shall be in accordance with ASME B16.42.
[NFPA 54:5.6.10.1.4] 1208.6.13.5 Dissimilar Flange Connections. Raised-face flanges shall not be joined to flat-faced cast iron, ductile iron or nonferrous material flanges.
[NFPA 54:5.6.10.2] 1208.6.13.6 Flange Facings. Standard facings shall be permitted for use under this code. Where 150 psi (1034 kPa) steel flanges are bolted to Class 125 cast-iron flanges, the raised face on the steel flange shall be removed. [NFPA 54:5.6.10.3] 1208.6.13.7 Lapped Flanges. Lapped flanges shall be used only aboveground or in exposed locations accessible for inspection. [NFPA 54:5.6.10.4] 1208.6.14 Flange Gaskets. The material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system and the chemical constituents of the gas being conducted without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing the material. [NFPA 54:5.6.11]
1208.6.14.1 Flange Gasket Materials. Acceptable materials shall include the following: (1) Metal (plain or corrugated) (2) Composition (3) Aluminum o-rings (4) Spiral-wound metal gaskets (5) Rubber-faced phenolic (6) Elastomeric [NFPA 54:5.6.11.1]
1208.6.14.2 Metallic Flange Gaskets. Metallic flange gaskets shall be in accordance with ASME B16.20. [NFPA 54:5.6.11.2.1] 1208.6.14.3 Non-Metallic Flange Gaskets. Non-metallic flange gaskets shall be in accordance with ASME B16.21. [NFPA 54:5.6.11.2.2] 1208.6.14.4 Full-Face Flange Gasket. Full-face flange gaskets shall be used with all non-steel flanges. [NFPA 54:5.6.11.3] 1208.6.14.5 Separated Flanges. When a flanged joint is separated, the gasket shall be replaced. [NFPA 54:5.6.11.2.4]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
▸Chapter 12 — FUEL GAS PIPING
Overview- 1201.0 General.1201.1 Applicability. The regulations of this c…
- 1202.0 Coverage of Piping System.1202.1 General. Coverage of p…
- 1202.2 Piping System Requirements. Requirements for
- 1202.3 Applications. This code shall not apply to the followin…
- 1203.2 Excavation. Excavations required for the installation o…
- 1203.3 Type of Inspections. The Authority Having Jurisdiction …
- 1203.4 Inspection Waived. In cases where the work
- 1204.2 Gas Supplier. A copy of the certificate of such final
- 1204.3 Unlawful. It shall be unlawful for a serving gas suppli…
- 1205.2 Outlets. It shall be unlawful to turn on or connect gas
- 1206.2 Notice. Where such disconnection has been made, a
- 1206.3 Capped Outlets. It shall be unlawful to remove or
- 1208.0 Gas Piping System Design, Materials, and
- 1208.2 Provision for Location of Point of Delivery. The locati…
- 1208.3 Interconnections Between Gas Piping Sys-tems. Where two…
- 1208.4 Sizing of Gas Piping Systems. Gas piping systems shall …
- 1208.5 Maximum Design Operating Pressure. The
- 1208.6 Acceptable Piping Materials and JoiningMethods. Materia…
- 1208.7 Gas Meters. Gas meters shall be selected for the
- 1208.8 Gas Pressure Regulators. A line pressure regulator or g…
- 1208.9 Overpressure Protection Devices. Where the
- 1208.10 Pressure Limitation Requirements. Where
- 1208.11 Backpressure Protection. Protective devices
- 1208.12 Low-Pressure Protection. A protective device
- 1208.13 Shutoff Valves. Shutoff valves shall be approved
- 1208.14 Expansion and Flexibility. Piping systems shall
- 1210.0 Gas Piping Installation.1210.1 Piping Underground. Unde…
- 1210.2 Installation of Piping. Piping installed aboveground sh…
- 1210.3 Concealed Piping in Buildings. Gas piping in
- 1210.4 Piping in Vertical Chases. Where gas piping
- 1210.6 Drips and Sediment Traps. For other than dry gas
- 1210.7 Outlets. Outlets shall be located and installed in
- 1210.5 Gas Pipe Turns. Changes in direction of gas pipe
- 1210.10 Prohibited Devices. No device shall be placed
- 1210.11 Systems Containing Gas-Air Mixtures Out-side the Flamm…
- 1210.12 Systems Containing Flammable Gas-AirMixtures. Systems …
- 1210.8 Branch Pipe Connection. Where a branch outlet
- 1210.9 Manual Gas Shutoff Valves. An accessible gas
- 1211.2 Bonding of CSST Gas Piping. CSST gas piping
- 1211.3 Prohibited Use. Gas piping shall not be used as a
- 1211.4 Lightning Protection System. Where a lightning
- 1211.5 Electrical Circuits. Electrical circuits shall not util…
- 1211.6 Electrical Connections. All electrical connections
- 1211.7 Earthquake-Actuated Gas Shutoff Valves. Earth-
- 1212.2 Suspended Low-Intensity Infrared TubeHeaters. Suspended…
- 1212.3 Use of Nonmetallic Gas Hose Connectors. Listed gas hose…
- 1212.1 Connecting Appliances and Equipment.
- 1212.4 Injection (Bunsen) Burners. Injection (Bunsen)
- 1212.5 Connection of Portable and Mobile Industrial
- 1212.5 Connection of Portable and Mobile Industrial
- 1212.9 Sediment Trap. Where a sediment trap is not incorporate…
- 1212.6 Appliance Shutoff Valves and Connections.
- 1212.7 Quick-Disconnect Devices. Quick-disconnect
- 1212.8 Gas Convenience Outlets. Appliances shall be
- 1212.10 Installation of Piping. Piping shall be installed in
- 1212.11 Liquefied Petroleum Gas Facilities and Pip-
- 1213.0 Pressure Testing, Inspection, and Purging.1213.1 Piping…
- 1213.2 Test Preparation. Test preparation shall comply
- 1213.3 Test Pressure. This inspection shall include an air,
- 1213.4 Detection of Leaks and Defects. The piping system shall…
- 1213.5 Piping System Leak Test. Leak checks using fuel
- 1213.6 Purging Requirements. The purging of piping
- 1215.2 Tables for Sizing Gas Piping Systems. Table
- 1215.3 Sizing Equations. The inside diameter of smoothwall pip…
- 1214.2 Volume. The hourly volume of gas required at each
- 1214.3 Gas Appliances. Where the gas appliances to be
- 1214.4 Size of Piping Outlets. The size of the supply piping o…
- 1215.0 Required Gas Piping Size.1215.1 Pipe Sizing Methods. Wh…
- 1215.5 Engineering Methods. For conditions other than
- 1215.6 Variable Gas Pressure. Where the supply gas
- 1215.4 Sizing of Piping Sections. To determine the size
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR