1208.11 Backpressure Protection. Protective devices

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

shall be installed as close to the equipment as practical where the design of the equipment connected is such that air, oxygen, or standby gases are capable of being forced into the gas supply system.

1208.10.1 Overpressure Protection Required. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches water column (3.5 kPa) are required to be equipped with overpressure protection by Section 1208.9, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s installation instructions.

[NFPA 54:5.9.2.2] 1208.10.2 Overpressure Protection Devices. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by this section independently of any other pressure control equipment in the piping system. [NFPA 54:5.9.2.3] 1208.10.3 Detection of Failure. Each gas piping system for which an overpressure protection device is required by this section shall be designed and installed so that a failure of the primary pressure control device(s) is detectable. [NFPA 54:5.9.2.4] 1208.10.4 Flow Capacity. If a pressure relief valve is used to meet the requirements of this section, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 1208.10 under the following conditions: (1) The line pressure regulator for which the relief valve

is providing overpressure protection has failed wide

«

(1) The line pressure regulator for which the relief valve

is providing overpressure protection has failed wide open. (2) The gas pressure at the inlet of the line pressure reg ulator for which the relief valve is providing over

2019 CALIFORNIA PLUMBING CODE 227

FUEL GAS PIPING any other purpose or distributed to any other persons or parti es.

» »

Gas and air combustion mixers incorporating double diaphragm “zero” or “atmosphere” governors or regulators shall require no further protection unless connected directly to compressed air or oxygen at pressures of 5 psi (34 kPa) or more. [NFPA 54:5.10.1.1 – 5.10.1.2]

1208.11.1 Protective Devices. Protective devices shall include, but not be limited to the following: (1) Check valves. (2) Three-way valves (of the type that completely closes

one side before starting to open the other side).

the pipe or tubing from external forces is likely to result. Where a minimum of 12 inches (305 mm) of cover cannot be provided, the pipe shall be installed in conduit or bridged (shielded). [NFPA 54:7.1.2.1 (A) (B)] 1210.1.2 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench. [NFPA 54:7.1.2.2]

(2) Three-way valves (of the type that completely closes

one side before starting to open the other side). (3) Reverse flow indicators controlling positive shutoff

valves.

(3) Reverse flow indicators controlling positive shutoff

valves. (4) Normally closed air-actuated positive shutoff pres sure regulators. [NFPA 54:5.10.2]

1210.1.2.1 Backfilling. Where flooding of the trench is done to consolidate the backfill, care shall be exercised to see that the pipe is not floated from its firm bearing on the trench bottom. [NFPA 54:7.1.2.3] 1210.1.3 Protection Against Corrosion. Steel pipe and steel tubing installed underground shall be installed in accordance with Section 1210.1.3.1 through Section 1210.1.3.9. [NFPA 54:7.1.3] 1210.1.3.1 Zinc Coating. Zinc coating (galvanizing) shall not be deemed adequate protection for underground gas piping. [NFPA 54:7.1.3.1] 1210.1.3.2 Underground Piping. Underground piping shall comply with one or more of the following unless approved technical justification is provided to demonstrate that protection is unnecessary: (1) The piping shall be made of a corrosion-resis tant material that is suitable for the environment

» » »

(4) Normally closed air-actuated positive shutoff pres sure regulators. [NFPA 54:5.10.2]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
    Overview
    1. 1201.0 General.1201.1 Applicability. The regulations of this c…
    2. 1202.0 Coverage of Piping System.1202.1 General. Coverage of p…
    3. 1202.2 Piping System Requirements. Requirements for
    4. 1202.3 Applications. This code shall not apply to the followin…
    5. 1203.2 Excavation. Excavations required for the installation o…
    6. 1203.3 Type of Inspections. The Authority Having Jurisdiction …
    7. 1203.4 Inspection Waived. In cases where the work
    8. 1204.2 Gas Supplier. A copy of the certificate of such final
    9. 1204.3 Unlawful. It shall be unlawful for a serving gas suppli…
    10. 1205.2 Outlets. It shall be unlawful to turn on or connect gas
    11. 1206.2 Notice. Where such disconnection has been made, a
    12. 1206.3 Capped Outlets. It shall be unlawful to remove or
    13. 1208.0 Gas Piping System Design, Materials, and
    14. 1208.2 Provision for Location of Point of Delivery. The locati…
    15. 1208.3 Interconnections Between Gas Piping Sys-tems. Where two…
    16. 1208.4 Sizing of Gas Piping Systems. Gas piping systems shall …
    17. 1208.5 Maximum Design Operating Pressure. The
    18. 1208.6 Acceptable Piping Materials and JoiningMethods. Materia…
    19. 1208.7 Gas Meters. Gas meters shall be selected for the
    20. 1208.8 Gas Pressure Regulators. A line pressure regulator or g…
    21. 1208.9 Overpressure Protection Devices. Where the
    22. 1208.10 Pressure Limitation Requirements. Where
    23. 1208.11 Backpressure Protection. Protective devices
    24. 1208.12 Low-Pressure Protection. A protective device
    25. 1208.13 Shutoff Valves. Shutoff valves shall be approved
    26. 1208.14 Expansion and Flexibility. Piping systems shall
    27. 1210.0 Gas Piping Installation.1210.1 Piping Underground. Unde…
    28. 1210.2 Installation of Piping. Piping installed aboveground sh…
    29. 1210.3 Concealed Piping in Buildings. Gas piping in
    30. 1210.4 Piping in Vertical Chases. Where gas piping
    31. 1210.6 Drips and Sediment Traps. For other than dry gas
    32. 1210.7 Outlets. Outlets shall be located and installed in
    33. 1210.5 Gas Pipe Turns. Changes in direction of gas pipe
    34. 1210.10 Prohibited Devices. No device shall be placed
    35. 1210.11 Systems Containing Gas-Air Mixtures Out-side the Flamm…
    36. 1210.12 Systems Containing Flammable Gas-AirMixtures. Systems …
    37. 1210.8 Branch Pipe Connection. Where a branch outlet
    38. 1210.9 Manual Gas Shutoff Valves. An accessible gas
    39. 1211.2 Bonding of CSST Gas Piping. CSST gas piping
    40. 1211.3 Prohibited Use. Gas piping shall not be used as a
    41. 1211.4 Lightning Protection System. Where a lightning
    42. 1211.5 Electrical Circuits. Electrical circuits shall not util…
    43. 1211.6 Electrical Connections. All electrical connections
    44. 1211.7 Earthquake-Actuated Gas Shutoff Valves. Earth-
    45. 1212.2 Suspended Low-Intensity Infrared TubeHeaters. Suspended…
    46. 1212.3 Use of Nonmetallic Gas Hose Connectors. Listed gas hose…
    47. 1212.1 Connecting Appliances and Equipment.
    48. 1212.4 Injection (Bunsen) Burners. Injection (Bunsen)
    49. 1212.5 Connection of Portable and Mobile Industrial
    50. 1212.5 Connection of Portable and Mobile Industrial
    51. 1212.9 Sediment Trap. Where a sediment trap is not incorporate…
    52. 1212.6 Appliance Shutoff Valves and Connections.
    53. 1212.7 Quick-Disconnect Devices. Quick-disconnect
    54. 1212.8 Gas Convenience Outlets. Appliances shall be
    55. 1212.10 Installation of Piping. Piping shall be installed in
    56. 1212.11 Liquefied Petroleum Gas Facilities and Pip-
    57. 1213.0 Pressure Testing, Inspection, and Purging.1213.1 Piping…
    58. 1213.2 Test Preparation. Test preparation shall comply
    59. 1213.3 Test Pressure. This inspection shall include an air,
    60. 1213.4 Detection of Leaks and Defects. The piping system shall…
    61. 1213.5 Piping System Leak Test. Leak checks using fuel
    62. 1213.6 Purging Requirements. The purging of piping
    63. 1215.2 Tables for Sizing Gas Piping Systems. Table
    64. 1215.3 Sizing Equations. The inside diameter of smoothwall pip…
    65. 1214.2 Volume. The hourly volume of gas required at each
    66. 1214.3 Gas Appliances. Where the gas appliances to be
    67. 1214.4 Size of Piping Outlets. The size of the supply piping o…
    68. 1215.0 Required Gas Piping Size.1215.1 Pipe Sizing Methods. Wh…
    69. 1215.5 Engineering Methods. For conditions other than
    70. 1215.6 Variable Gas Pressure. Where the supply gas
    71. 1215.4 Sizing of Piping Sections. To determine the size
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.