1210.4 Piping in Vertical Chases. Where gas piping
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
exceeding 5 psi (34 kPa) is located within vertical chases in accordance with Section 1208.5(2), the requirements of Section 1210.4.1 through Section 1210.4.3 shall apply. [NFPA 54:7.4] 1210.4.1 Pressure Reduction. Where pressure reduction is required in branch connections for compliance with Section 1208.5, such reduction shall take place either inside the chase or immediately adjacent to the outside wall of the chase. Regulator venting and downstream overpressure protection shall comply with Section 1208.8.4 and Section 1208.9 through Section 1208.10.4. The regulator shall be accessible for service and repair, and vented in accordance with one of the following: (1) Where the fuel gas is lighter than air, regulators
equipped with a vent limiting means shall be per
(4) The pipe shall not be bent through an arc of more
than 90 degrees (1.57 rad).
(4) The pipe shall not be bent through an arc of more
than 90 degrees (1.57 rad). (5) The inside radius of a bend shall be not less than six
times the outside diameter of the pipe. [NFPA
(5) The inside radius of a bend shall be not less than six
times the outside diameter of the pipe. [NFPA 54:7.5.1] 1210.5.2 Plastic Pipe. Plastic pipe bends shall comply with the following: (1) The pipe shall not be damaged, and the internal
diameter of the pipe shall not be effectively reduced.
(1) The pipe shall not be damaged, and the internal
diameter of the pipe shall not be effectively reduced. (2) Joints shall not be located in pipe bends. (3) The radius of the inner curve of such bends shall not
be less than 25 times the inside diameter of the pipe.
(3) The radius of the inner curve of such bends shall not
be less than 25 times the inside diameter of the pipe. (4) Where the piping manufacturer specifies the use of
special bending tools or procedures, such tools or
« « « « «
(1) Where the fuel gas is lighter than air, regulators
equipped with a vent limiting means shall be permitted to be vented into the chase. Regulators not equipped with a vent limiting means shall be permitted to be vented either directly to the outdoors or to a point within the top 1 foot (305 mm) of the chase. (2) Where the fuel gas is heavier than air, the regulator
vent shall be vented only directly to the outdoors.
(4) Where the piping manufacturer specifies the use of
special bending tools or procedures, such tools or procedures shall be used. [NFPA 54:7.5.2] 1210.5.3 Elbows. Factory-made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch at least 1 inch (25.4 mm) for pipe sizes 2 inches (50 mm) and larger. [NFPA 54:7.5.3]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
▸Chapter 12 — FUEL GAS PIPING
Overview- 1201.0 General.1201.1 Applicability. The regulations of this c…
- 1202.0 Coverage of Piping System.1202.1 General. Coverage of p…
- 1202.2 Piping System Requirements. Requirements for
- 1202.3 Applications. This code shall not apply to the followin…
- 1203.2 Excavation. Excavations required for the installation o…
- 1203.3 Type of Inspections. The Authority Having Jurisdiction …
- 1203.4 Inspection Waived. In cases where the work
- 1204.2 Gas Supplier. A copy of the certificate of such final
- 1204.3 Unlawful. It shall be unlawful for a serving gas suppli…
- 1205.2 Outlets. It shall be unlawful to turn on or connect gas
- 1206.2 Notice. Where such disconnection has been made, a
- 1206.3 Capped Outlets. It shall be unlawful to remove or
- 1208.0 Gas Piping System Design, Materials, and
- 1208.2 Provision for Location of Point of Delivery. The locati…
- 1208.3 Interconnections Between Gas Piping Sys-tems. Where two…
- 1208.4 Sizing of Gas Piping Systems. Gas piping systems shall …
- 1208.5 Maximum Design Operating Pressure. The
- 1208.6 Acceptable Piping Materials and JoiningMethods. Materia…
- 1208.7 Gas Meters. Gas meters shall be selected for the
- 1208.8 Gas Pressure Regulators. A line pressure regulator or g…
- 1208.9 Overpressure Protection Devices. Where the
- 1208.10 Pressure Limitation Requirements. Where
- 1208.11 Backpressure Protection. Protective devices
- 1208.12 Low-Pressure Protection. A protective device
- 1208.13 Shutoff Valves. Shutoff valves shall be approved
- 1208.14 Expansion and Flexibility. Piping systems shall
- 1210.0 Gas Piping Installation.1210.1 Piping Underground. Unde…
- 1210.2 Installation of Piping. Piping installed aboveground sh…
- 1210.3 Concealed Piping in Buildings. Gas piping in
- 1210.4 Piping in Vertical Chases. Where gas piping
- 1210.6 Drips and Sediment Traps. For other than dry gas
- 1210.7 Outlets. Outlets shall be located and installed in
- 1210.5 Gas Pipe Turns. Changes in direction of gas pipe
- 1210.10 Prohibited Devices. No device shall be placed
- 1210.11 Systems Containing Gas-Air Mixtures Out-side the Flamm…
- 1210.12 Systems Containing Flammable Gas-AirMixtures. Systems …
- 1210.8 Branch Pipe Connection. Where a branch outlet
- 1210.9 Manual Gas Shutoff Valves. An accessible gas
- 1211.2 Bonding of CSST Gas Piping. CSST gas piping
- 1211.3 Prohibited Use. Gas piping shall not be used as a
- 1211.4 Lightning Protection System. Where a lightning
- 1211.5 Electrical Circuits. Electrical circuits shall not util…
- 1211.6 Electrical Connections. All electrical connections
- 1211.7 Earthquake-Actuated Gas Shutoff Valves. Earth-
- 1212.2 Suspended Low-Intensity Infrared TubeHeaters. Suspended…
- 1212.3 Use of Nonmetallic Gas Hose Connectors. Listed gas hose…
- 1212.1 Connecting Appliances and Equipment.
- 1212.4 Injection (Bunsen) Burners. Injection (Bunsen)
- 1212.5 Connection of Portable and Mobile Industrial
- 1212.5 Connection of Portable and Mobile Industrial
- 1212.9 Sediment Trap. Where a sediment trap is not incorporate…
- 1212.6 Appliance Shutoff Valves and Connections.
- 1212.7 Quick-Disconnect Devices. Quick-disconnect
- 1212.8 Gas Convenience Outlets. Appliances shall be
- 1212.10 Installation of Piping. Piping shall be installed in
- 1212.11 Liquefied Petroleum Gas Facilities and Pip-
- 1213.0 Pressure Testing, Inspection, and Purging.1213.1 Piping…
- 1213.2 Test Preparation. Test preparation shall comply
- 1213.3 Test Pressure. This inspection shall include an air,
- 1213.4 Detection of Leaks and Defects. The piping system shall…
- 1213.5 Piping System Leak Test. Leak checks using fuel
- 1213.6 Purging Requirements. The purging of piping
- 1215.2 Tables for Sizing Gas Piping Systems. Table
- 1215.3 Sizing Equations. The inside diameter of smoothwall pip…
- 1214.2 Volume. The hourly volume of gas required at each
- 1214.3 Gas Appliances. Where the gas appliances to be
- 1214.4 Size of Piping Outlets. The size of the supply piping o…
- 1215.0 Required Gas Piping Size.1215.1 Pipe Sizing Methods. Wh…
- 1215.5 Engineering Methods. For conditions other than
- 1215.6 Variable Gas Pressure. Where the supply gas
- 1215.4 Sizing of Piping Sections. To determine the size
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR