Chapter 4 — VENTILATION AIR

414.1 Exhaust Systems — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 414.1 · Effective January 1, 2026 · Official source: Building Standards Commission

A separate, dedicated exhaust system shall be provided for airborne infection isolation rooms. The dedicated system may serve more than one air- borne infection isolation room, adjoining toilet room and anteroom. The exhaust ducts shall be identified by appro- priate labeling with the words "Caution Airborne Infection Isolation Rooms Exhaust" or similar terminology. Such labeling shall be in a manner which is not readily removable and shall appear on the exhaust duct at intervals of not more than 20 feet (6096 mm) and at least once near each room and each story traversed by the exhaust system. Exhaust fans shall comply with Section 407.1.2. The discharge from exhaust fans shall be located above the roof and shall be located a minimum of 25 feet (7620 mm) from areas that may be occupied, doors, operable windows, outdoor air intakes, or other openings into the building. The exhaust fan dis- charge shall be labeled in a manner which readily identifies the precautions which should be observed. To ensure that the airborne contaminates do not reenter the building, one of the following shall be provided:

414.1.1 Exhaust discharge from fan shall extend at least 10 feet (3048 mm) above the roof and discharge verti- cally upward. Self-draining stacks or equivalent shall be used for rain protection. Rain caps which divert the exhaust toward the roof shall be prohibited.

414.1.2 Exhaust shall discharge above roof level and through an accessible HEPA filter. The HEPA filter shall be located upstream of the exhaust fan and have a mini- mum efficiency of 99.97 percent based on the DOP method in accordance with Mil-Std. 282 or a minimum

efficiency reporting value (MERV) of 17, based on ASHRAE 52.2. Filter gage shall be installed across the filter. For maintenance of air balance relationship, see Section 407.3.1. The 25-foot (7620 mm) dimension required by Section 414.1 may be reduced when a 99.97 percent HEPA filter or a minimum efficiency reporting value (MERV) of 17, based on ASHRAE 52.2 is used and the reduced dimension is specifically approved by the enforcing agency.