410.3 Laboratory Fume Hoods — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 410.3 · Effective January 1, 2026 · Official source: Building Standards Commission
Laboratory fume hoods shall meet the following standards:
410.3.1 General Standard. Average face velocity shall be at least 75 feet per minute (0.38 meters per sec- ond). Exhaust system shall be separate from the build- ing exhaust system. Exhaust fan shall be located at the discharge end of the system. Exhaust duct system shall be of noncombustible corrosion-resistant material as required to meet the planned usage of the hood.
<
<
<