A mechanical exhaust system that discharges directly to the outdoors shall be provided in each kitchen. The fan shall run intermittently (on demand) or continuously. A readily accessible manual control designed to be operated as needed or an automatic control shall be provided for intermittent operations.

Exception: Recirculating systems installed in accordance with Section 516.0 and the manufacturer’s installation

instructions.

405.4.1 Exhaust Rate. For intermittent-controlled operations, the exhaust rate shall be not less than 100 ft [3] /min (47.2 L/s) for range hoods or 300 ft [3] /min (142 L/s) for mechanical exhaust fans including downdraft appliances. For continuous operated ventilation, the exhaust rate shall be not less than 50 ft [3] /min (23.6 L/s).