403.2 Zone Calculations — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 403.2 · Effective January 1, 2026 · Official source: Building Standards Commission
Ventilation zone parameters shall be determined in accordance with Section 403.2.1 through Section 403.2.3 for ventilation zones served by the ventilation system, except that the ventilation rates from ASHRAE/ASHE 170 shall be used for the occupancy categories, as applicable. [ASHRAE 62.1:6.2.1]
403.2.1 Breathing Zone Outdoor Airflow. The outdoor airflow required in the breathing zone ( Vbz ) of the occupiable space or spaces in a ventilation zone shall be not less than the value determined in accordance with Equation 403.2.1.
Vbz = Rp•Pz + Ra• Az (Equation 403.2.1)
Where: Az = zone floor area, the net occupiable floor area of the ventilation zone, ft [2] (m [2] ). Pz = zone population, the number of people in the ventilation zone during usage. Rp= outdoor airflow rate required per person (CFM/person) as determined from Table 402.1. Ra= outdoor airflow rate required per unit area (CFM/ft [2] ) as determined from Table 402.1.
[ASHRAE 62.1:6.2.1.1] For SI Units: 1 square foot = 0.0929 m [2], 1 cubic foot per minute = 0.0283 m [3] /min, 1 cubic foot per minute = 0.4719 L/s, 1 cubic foot per minute per square foot = 5.08 [(L/s)/m [2] ] 403.2.2 Zone Air Distribution Effectiveness. The zone air distribution effectiveness ( Ez ) shall be determined in accordance with Table 403.2.2. [ASHRAE 62.1:6.2.1.2] 403.2.2.1 Stratified Air Distribution Systems. A stratified air distribution system shall be designed in accordance with Section 403.2.2.1.1 through Section 403.2.2.2.2, or the zone air distribution effectiveness ( Ez ) shall be determined in accordance with ASHRAE 62.1. [ASHRAE 62.1:6.2.1.2.1] 403.2.2.1.1 Supply Air. Cool air shall be at least 4°F (2°C) less than the average room air temperature. [ASHRAE 62.1:6.2.1.2.1.1] 403.2.2.1.2 Return Air. The return air openings or pathways shall be located not less than 9 feet (2743 mm) above the floor. [ASHRAE 62.1:6.2.1.2.1.2]
403.2.2.1.3 Stratification. The zone shall not contain any devices that mechanically mix the air, and shall be protected from impinging airstreams from adjacent ventilation zones.
[ASHRAE 62.1:6.2.1.2.1.3] 403.2.2.2 Personalized Ventilation Systems. A personalized ventilation system shall be designed in accordance with the following subsections, or the zone air distribution effectiveness ( Ez ) shall be determined in accordance with ASHRAE 62.1.
[ASHRAE 62.1:6.2.1.2.2] 403.2.2.2.1 Personalized Air. The personalized air shall be distributed in the breathing zone and designed such that the velocity is
equal to or less than 50 feet per minute (0.25 m/s) at the head/facial region of the occupant.
[ASHRAE 62.1:6.2.1.2.2.1] 403.2.2.2.2 Return Air. The return air openings or pathways shall be located more than 9 feet (2.8 m) above the floor. [ASHRAE 62.1:6.2.1.2.2.2]
403.2.3 Zone Outdoor Airflow. The zone outdoor airflow ( Voz ) provided to the ventilation zone by the supply air distribution system shall be determined in accordance with Equation 403.2.3. [ASHRAE 62.1:6.2.1.3]
Voz = Vbz / Ez (Equation 403.2.3)