Chapter 4 — VENTILATION AIR

403.9 Air Classification and Recirculation — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 403.9 · Effective January 1, 2026 · Official source: Building Standards Commission

Air shall be

classified as shown in Table 402.1, Table 403.7, or Table 403.9, and its recirculation shall be limited in accordance with Section

403.9.1 through Section 403.9.4. {ASHRAE 62.1:5.18} Recirculated air shall not be taken from prohibited locations in accordance with Section 311.3.

Air (return, transfer, or exhaust air) leaving each space or location shall be designated at an expected air-quality classification not less than that shown in Table 402.1, Table 403.7, or Table 403.9 or as approved by the Authority Having Jurisdiction. Air leaving spaces or locations that are not listed in Table 402.1, Table 403.7, or Table 403.9 shall be designated with the same classification as air from the most similar space or location listed in terms of occupant activities and building construction.

Exception: Air from spaces where environmental tobacco smoke (ETS) is present. (Classification of air from spaces where ETS is present is not addressed. Spaces that are expected to include ETS do not have a classification listed in Table 402.1.)

[ASHRAE 62.1:5.18.1]

TABLE 403.9

AIRSTREAMS OR SOURCES DESCRIPTION AIR CLASS

[ASHRAE 62.1: TABLE 6-3]

DESCRIPTION AIR
CLASS

Kitchen grease hoods
4
Kitchen hoods other than grease
3

Diazo printing equipment discharge
4

Hydraulic elevator machine room
2

Laboratory hoods
4
Paint spray booths
4
Refrigerating machinery rooms 3

403.9.1 Class 1 Air. Recirculation or transfer of Class 1 air to any space shall be permitted. [ASHRAE 62.1:5.18.3.1]

403.9.2 Class 2 Air. Recirculation of Class 2 air within the space of origin shall be permitted. Recirculation or transfer of Class 2 air to other Class 2 or Class 3 spaces shall be permitted, provided that the other spaces are used for the same or similar purpose or task and involve the same or similar pollutant sources as the Class 2 space. Transfer of Class 2 air to toilet rooms shall be permitted. Recirculation or transfer of Class 2 air to Class 4 spaces shall be permitted. Class 2 air shall not be recirculated or transferred to Class 1 spaces.

Exception: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device shall be permitted but shall not be counted as outdoor air. Exhaust air transfer ratio of Class 2 air shall not exceed 10 percent of the outdoor air intake flow. {ASHRAE 62.1:5.18.3.2 – 5.18.3.2.5}

403.9.3 Class 3 Air. Recirculation of Class 3 air within the space of origin shall be permitted. Class 3 air shall not be recirculated or transferred to any other space.

Exception: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device shall be permitted but shall not be counted as outdoor air. Exhaust air transfer ratio of Class 3 air shall not exceed 5 percent of the outdoor air intake flow. {ASHRAE 62.1:5.18.3.3 – 5.18.3.3.2}

403.9.4 Class 4 Air. Class 4 air shall not be recirculated or transferred to any space or recirculated within the space of origin. [ASHRAE 62.1:5.18.3.4]