404.1 System Ventilation Efficiency — 2025 California Mechanical Code
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 404.1 · Effective January 1, 2026 · Official source: Building Standards Commission
The system ventilation efficiency shall equal the lowest zone ventilation efficiency among the ventilation zones served by the air handler in accordance with Equation 404.1. [ASHRAE 62.1:A1.3] This section presents an alternative procedure for calculating the system ventilation efficiency ( Ev ) for multiple zone recirculating systems that shall be used when Section 403.5.1.3 is not used.
Ev = minimum ( Evz ) (Equation 404.1)