404.1 General.

404.1 General. The provisions of Sections 404.1 through 404.12 shall apply to buildings containing atriums. Atriums are not permitted in buildings or structures classified as Group H. Exception: Vertical openings that comply with Sections 712.1.1 through 712.1.3, and Sections 712.1.9 through 712.1.14.

404.2 Use.

404.2 Use. The floor of the atrium shall not be used for other than low fire hazard uses and only approved materials and decorations in accordance with the California Fire Code shall be used in the atrium space. Exception: The atrium floor area is permitted to be used for any approved use where the individual space is provided with an automatic sprinkler system in accordance with Section 903.3.1.1. [F] 404.3 Automatic sprinkler protection. An approved automatic sprinkler system shall be installed throughout the entire building. Exceptions: 1. That area of a building adjacent to or above the…

404.5 Smoke control.

404.5 Smoke control. A smoke control system shall be installed in accordance with Section 909. Exceptions: 1. In other than Group I-2 and R-2.1, Condition 2, smoke control is not required for atriums that connect only two stories. 2. A smoke control system is not required for atriums connecting more than two stories when all of the following are met: 2.1. Only the two lowest stories shall be permitted to be open to the atrium. 2.2. All stories above the lowest two stories shall be separated from the atrium in accordance with the provisions for a shaft in Section 713.4.

404.6 Enclosure of atriums.

404.6 Enclosure of atriums. Atrium spaces shall be separated from adjacent spaces by a 1-hour fire barrier constructed in accordance with Section 707 or a horizontal assembly constructed in accordance with Section 711, or both. Exceptions: 1. A fire barrier is not required where a glass wall forming a smoke partition is provided. The glass wall shall comply with all of the following: 1.1. Automatic sprinklers are provided along both sides of the separation wall and doors, or on the room side only if there is not a walkway on the atrium side. The sprinklers shall be located between 4 inches…

404.8 Interior finish.

404.8 Interior finish. The interior finish of walls and ceilings of the atrium shall be not less than Class B. Sprinkler protection shall not result in a reduction in class. [BE] 404.9 Exit access travel distance. Exit access travel distance for areas open to an atrium shall comply with the requirements of Section 1017. [BE] 404.10 Exit stairways in an atrium. Where an atrium contains an interior exit stairway all the following shall be met: 1. The entry to the exit stairway is the edge of the closest riser of the exit stairway. 2. The entry of the exit stairway shall have access from a…

404.12 Group I and R-2.1 occupancy means of egress.

404.12 Group I and R-2.1 occupancy means of egress. Required means of egress from sleeping and treatment rooms in Group I and R-2.1 occupancies shall not pass through the atrium.