Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE

Section 452 — SCHOOL FACILITIES FOR KINDERGARTEN THROUGH 12TH GRADE AND GROUP E CHILD CARE

2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

452.1 General provisions.

School facilities for Kindergarten through 12th grade and Group E child care shall comply with the provisions of this section and other applicable provisions of this code including requirements for specific occupancies.

452.1.1 Location on property. All buildings housing Group E occupancies shall front directly on a public street or an exit discharge not less than 20 feet (6096 mm) in width. The exit discharge to the public street shall be a minimum 20-foot-wide (6096 mm) right-of- way, unobstructed and maintained only as access to the public street. At least one required exit shall be located on the public street or on the exit discharge.

452.1.2 Separate means of egress systems required. Every room with an occupant load of 300 or more shall have one of its exits or exit-access doorways lead directly into a separate means of egress system that consists of not less than two paths of exit travel which are separated by a smoke barrier in accordance with Section 709 in such a manner to provide an atmospheric separation that precludes contamination of both paths of exit travel by the same fire. Not more than two required exits or exit-access doorways shall enter into the same means of egress system.

452.1.3 Fences and gates. School grounds may be fenced and gates therein may be equipped with locks, provided that safe disper- sal areas based on 3 square feet (0.28 m [2] ) per occupant are located between the school and the fence. Such required safe dispersal areas shall not be located less than 50 feet (15 240 mm) from school buildings.

4-66 2025 CALIFORNIA BUILDING CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE

Every public and private school shall conform with Section 32020 of the Education Code which states:

The governing board of every public school district, and the governing authority of every private school, which maintains any building used for the instruction or housing of school pupils on land entirely enclosed (except for building walls) by fences of walls, shall, through cooperation with the local law enforcement and fire-protection agencies having jurisdiction of the area, make provi- sion for the erection of gates in such fences or walls. The gates shall be of sufficient size to permit the entrance of the ambulances, police equipment and firefighting apparatus used by the law enforcement and fire-protection agencies. There shall be no less than one such access gate and there shall be as many such gates as needed to assure access to all major buildings and ground areas. If such gates are to be equipped with locks, the locking devices shall be designed to permit ready entrance by the use of the chain or bolt-cutting devices with which the local law enforcement and fire-protection agencies may be equipped.

There shall be no less than_ one such access gate and there shall be as many such gates as needed to assure access to all major buildings and ground areas. If such gates are to be equipped with locks, the locking devices shall be designed to permit ready entrance by the use of the chain or bolt-cutting devices with which the local law enforcement and fire-protection agencies may be equipped.

452.1.4 Special provisions. Rooms used by kindergarten, first- or second-grade pupils, and Group E child care, shall not be located above or below the first story.

Exceptions: 1. Kindergarten, first- or second-grade pupils, or Group E child care may be located in basements or stories having floor levels located within 4 feet (1219 mm), measured vertically, from the adjacent ground level at the level of exit discharge, provided the basement or story has exterior exit doors at that level. 2. In buildings equipped with an automatic sprinkler system throughout, rooms used for kindergarten, first- and second-grade children or for Group E child-care purposes may be located on the second story, provided there are at least two exterior exit doors, or other egress systems complying with Section 1020 with two exits, for the exclusive use of such occupants. Egress systems for the exclusive use of such occupants shall be maintained until exit discharge at grade is attained. 3. Group E day-care facilities may be located above the first story in buildings of Type I-A, I-B, II-A, III-A, IV-A, IV-B and IV-C construction, subject to the limitation of Section 503 when: 3.1. Facilities with children under the age of seven or containing more than 12 children per story shall not be located above the fourth floor; and

ned until exit discharge at grade is attained._ 3. Group E day-care facilities may be located above the first story in buildings of Type I-A, I-B, II-A, III-A, IV-A, IV-B and IV-C construction, subject to the limitation of Section 503 when: 3.1. Facilities with children under the age of seven or containing more than 12 children per story shall not be located above the fourth floor; and

3.2. The entire story in which the day-care facility is located is equipped with an approved manual fire alarm and automatic smoke-detection system. Actuation of an initiating device shall sound an audible alarm throughout the entire story. When a building fire alarm system is required by other provisions of this code, the alarm system shall be interconnected and sound the day-care fire alarm system; and 3.3. The day-care facility, if more than 1,000 square feet (92.9 m [2] ) in area, is divided into at least two compartments of approximately the same size by a smoke barrier in accordance with Section 709. In addition to the requirements of Section 508, occupancy separations between day-care and other occupancies shall be constructed as smoke barri- ers. Door openings in the smoke barrier shall be tight fitting, with gaskets installed as required by Section 716.5.3.1 and shall be automatic closing by actuation of the fire sprinklers, fire alarm or smoke detection system; and 3.4. Each compartment formed by the smoke barrier has not less than two exits or exit-access doors, one of which is permitted to pass through the adjoining compartment, and 3.5. At least one exit or exit-access door from the day-care facility shall be into a separate means of egress with not less than two paths of exit travel, which are separated in such a manner to provide an atmospheric separation. The egress system shall comply with the requirements of Section 709 for smoke barriers. 3.6. The building is equipped with an automatic sprinkler system throughout.

452.1.5 Special hazards. School classrooms constructed after January 1, 1990, not equipped with automatic sprinkler systems, which have metal grilles or bars on all their windows and do not have at least two exit doors within 3 feet (914 mm) of each end of the classroom opening to the exterior of the building or to a common hallway used for evacuation purposes, shall have an inside release for the grilles or bars on at least one window farthest from the exit doors. The window or windows with the inside release shall be clearly marked as emergency exits.

452.1.6 Class I, II or III-A flammable liquids shall not be placed, stored or used in Group E occupancies, except in approved quantities as necessary in laboratories and classrooms and for operation and maintenance as set forth in the California Fire Code.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Building Code (Title 24, Part 2)
2025 California Building Code (Title 24, Part 2)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
  4. Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
    Overview
    1. Section 401 — SCOPE
    2. Section 402 — COVERED MALL AND OPEN MALL BUILDINGS
    3. Section 403 — HIGH-RISE BUILDINGS AND GROUP I-2 OCCUPANCIES HA…
    4. Section 404 — ATRIUMS
    5. Section 405 — UNDERGROUND BUILDINGS
    6. Section 406 — MOTOR-VEHICLE-RELATED OCCUPANCIES
    7. Section 407 — GROUP I-2
    8. Section 408 — GROUP I-3
    9. Section 409 — MOTION PICTURE PROJECTION ROOMS
    10. Section 410 — STAGES, PLATFORMS AND TECHNICAL PRODUCTION AREAS
    11. Section 411 — SPECIAL AMUSEMENT AREAS
    12. Section 412 — AIRCRAFT-RELATED OCCUPANCIES
    13. Section 413 — COMBUSTIBLE STORAGE
    14. Section 414 — HAZARDOUS MATERIALS
    15. Section 415 — GROUPS H-1, H-2, H-3, H-4 AND H-5
    16. Section 416 — SPRAY APPLICATION OF FLAMMABLE FINISHES
    17. Section 417 — DRYING ROOMS
    18. Section 418 — ORGANIC COATINGS
    19. Section 419 — ARTIFICIAL DECORATIVE VEGETATION
    20. Section 420 — GROUPS R-1, R-2, R-2.1, R-2.2, R-3, R-3.1 AND R-4
    21. Section 421 — HYDROGEN FUEL GAS ROOMS
    22. Section 422 — AMBULATORY CARE FACILITIES
    23. Section 423 — STORM SHELTERS
    24. Section 424 — PLAY STRUCTURES
    25. Section 425 — HYPERBARIC FACILITIES
    26. Section 427 — MEDICAL GAS SYSTEMS
    27. Section 435 — SPECIAL PROVISIONS FOR LICENSED 24-HOUR CARE FAC…
    28. Section 436 — GROUP I-4 [SFM]
    29. Section 437 — RESERVED
    30. Section 438 — RESERVED
    31. Section 439 — ROAD TUNNELS, BRIDGES AND OTHER LIMITED-ACCESS H…
    32. Section 440 — HORSE RACING STABLES [SFM]
    33. Section 441 — PET KENNELS AND PET BOARDING FACILITIES [SFM]
    34. Section 442 — COMBUSTION ENGINES AND GAS TURBINES [SFM]
    35. Section 443 — FIXED GUIDEWAY TRANSIT AND PASSENGER RAIL SYSTEM…
    36. Section 444 — EXPLOSIVES [SFM]
    37. Section 445 — RESERVED
    38. Section 446 — WINERY CAVES [SFM]
    39. Section 447 — RESERVED
    40. Section 448 — RESERVED
    41. Section 449 — PUBLIC LIBRARIES [SL AND SFM]
    42. Section 450 — GROUP C [SFM]
    43. Section 451 — RESERVED
    44. Section 452 — SCHOOL FACILITIES FOR KINDERGARTEN THROUGH 12TH …
    45. Section 453 — GROUP L [SFM]
    46. Section 454 — RESERVED
    47. Section 455 — LARGE FAMILY DAY-CARE HOMES [SFM]
  5. Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
  6. Chapter 6 — TYPES OF CONSTRUCTION
  7. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  8. Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
  9. Chapter 8 — INTERIOR FINISHES
  10. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  11. Chapter 10 — MEANS OF EGRESS
  12. Chapter 11 — RESERVED
  13. Chapter 11A — HOUSING ACCESSIBILITY
  14. Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
  15. Chapter 12 — INTERIOR ENVIRONMENT
  16. Chapter 13 — ENERGY EFFICIENCY
  17. Chapter 14 — EXTERIOR WALLS
  18. Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
  19. Chapter 16 — STRUCTURAL DESIGN
  20. Chapter 16A — STRUCTURAL DESIGN
  21. Chapter 17 — SPECIAL INSPECTIONS AND TESTS
  22. Chapter 17A — SPECIAL INSPECTIONS AND TESTS
  23. Chapter 18 — SOILS AND FOUNDATIONS
  24. Chapter 18A — SOILS AND FOUNDATIONS
  25. Chapter 19 — CONCRETE
  26. Chapter 19A — CONCRETE
  27. Chapter 20 — ALUMINUM
  28. Chapter 21 — MASONRY
  29. Chapter 21A — MASONRY
  30. Chapter 22 — STEEL
  31. Chapter 22A — STEEL
  32. Chapter 23 — WOOD
  33. Chapter 24 — GLASS AND GLAZING
  34. Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
  35. Chapter 26 — PLASTIC
  36. Chapter 27 — ELECTRICAL
  37. Chapter 28 — MECHANICAL SYSTEMS
  38. Chapter 29 — PLUMBING SYSTEMS
  39. Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
  40. Chapter 31 — SPECIAL CONSTRUCTION
  41. Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
  42. Chapter 31B — PUBLIC POOLS
  43. Chapter 31C — RADIATION
  44. Chapter 31D — FOOD ESTABLISHMENTS
  45. Chapter 31F — MARINE OIL TERMINALS
  46. Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
  47. Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
  48. Chapter 34 — RESERVED
  49. Chapter 35 — REFERENCED STANDARDS
  50. Appendix A — EMPLOYEE QUALIFICATIONS
  51. Appendix B — BOARD OF APPEALS
  52. Appendix C — GROUP U—AGRICULTURAL BUILDINGS
  53. Appendix D — FIRE DISTRICTS
  54. Appendix E — RESERVED
  55. Appendix F — RODENTPROOFING
  56. Appendix G — FLOOD-RESISTANT CONSTRUCTION
  57. Appendix H — SIGNS
  58. Appendix I — PATIO COVERS
  59. Appendix J — GRADING
  60. Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
  61. Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
  62. Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
  63. Appendix N — REPLICABLE BUILDINGS
  64. Appendix O — PERFORMANCE-BASED APPLICATION
  65. Appendix P — SLEEPING LOFTS
  66. Appendix Q — EMERGENCY HOUSING

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.