407.2 Outdoor Air Intakes and Exhaust Outlets.

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

407.2.1 Outdoor Air Intakes. Outdoor air intakes shall be located at least 25 feet (7.62 m) from exhaust outlets of ventilating systems, combustion equipment stacks, med- ical-surgical vacuum systems, cooling towers, and areas that may collect vehicular exhaust or other noxious fumes. Plumbing vents shall be located in relation to out- door air intakes per California Plumbing Code. The bot- tom of outdoor air intakes shall be located as high as practicable, but not less than 10 feet (3048 mm) above ground level. If installed above the roof, they shall be located 18 inches (457 mm) above roof level or 3 feet (914 mm) above a flat roof where heavy snowfall is anticipated. Outside air intakes located in a below grade areaway shall have the top of the areaway extend a minimum of 10 feet (3048 mm) above grade.

Exceptions:

(1) These dimensions may be reduced if it is demon- strated by the submission of details and calculations that location of intakes with respect to exhausts and

their orientation, or the use of special filters, pro- vides equal performance.

(2) The requirements regarding the bottom of outdoor air intakes and installation through the roof do not apply to skilled nursing facilities, intermediate-care facilities or nonsensitive areas in correctional treat-

ment centers.

407.2.2 Exhaust Outlets. Exhaust outlets shall be located a minimum of 10 feet (3048 mm) above adjoining grade and 10 feet (3048 mm) from doors, occupied areas, and operable windows.

Exception: Airborne infection isolation rooms shall comply with Section 414.1.

407.2.2.1 Hazardous Exhaust Outlets. Haz- ardous exhaust outlets from airborne infection iso- lation rooms, bronchoscopy and sputum collection exhaust, hazardous drug compounding, morgues, autopsy rooms and laboratory chemical fume hoods shall discharge a minimum of 10 feet (3048 mm) above the adjacent roof surface and a minimum of 30 feet (9144.mm) from outdoor air intakes, build- ing openings and areas normally accessible to the public.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
    Overview
    1. 401.1 Applicability. This chapter contains requirements for
    2. 401.2 Indoor Swimming Pools. The design of ventilation
    3. 401.3 Filters. [BSC-CG & DSA-SS] In mechanically ven-
    4. 402.1 Occupiable Spaces. Occupiable spaces listed in
    5. 402.2 Natural Ventilation Procedure. [Not permitted
    6. 402.3 Mechanical Ventilation. [Not permitted for
    7. 402.4 Outdoor Air Intakes. Ventilation system outdoor
    8. 403.1 General. The design outdoor air intake flow rate for
    9. 403.2 Zone Calculations. Ventilation zone parameters
    10. 403.3 Single-Zone Systems. For ventilation systems
    11. 403.4 One Hundred Percent Outdoor Air Systems.
    12. 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
    13. 403.6 Design for Varying Operating Conditions. Ventilation sys…
    14. 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
    15. 403.8 Dynamic Reset. The system shall be permitted to be
    16. 403.9 Air Classification and Recirculation. Air shall be
    17. 403.10 Air Balance. All mechanical ventilation systems
    18. 404.1 System Ventilation Efficiency. The system ventilation ef…
    19. 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
    20. 404.3 Zone Ventilation Efficiency. The zone ventilation
    21. 405.1 General. Rooms or occupied spaces within residential occ…
    22. 405.2 Ventilation Air Rate. The required mechanical ventilatio…
    23. 405.3 Bathroom Exhaust. A mechanical exhaust directly
    24. 405.4 Kitchen Exhaust. A mechanical exhaust system that
    25. 405.5 Ventilation Openings. Occupiable spaces shall be
    26. 406.0 Evaporative Cooling System for Health Care
    27. 407.1 General.
    28. 407.2 Outdoor Air Intakes and Exhaust Outlets.
    29. 407.3 Air Balance.
    30. 407.4 Air Circulation.
    31. 407.5 Variable Air Volume.
    32. 407.6 Economizers.
    33. 407.7 Unoccupied Turndown.
    34. 408.3 Filters for Skilled Nursing Facilities, Intermedi-
    35. 408.4 Filters for Outpatient Facilities.
    36. 408.5 Filters for Recirculating Room Units.
    37. 409.1 Ducts which penetrate construction, intended for X-
    38. 409.2 Duct linings and their use shall meet the requirements
    39. 409.3 The anchorage and supporting structural elements for
    40. 410.1 Laboratory Ventilating Systems. Laboratory ven-
    41. 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
    42. 410.3 Laboratory Fume Hoods. Laboratory fume hoods
    43. 407.8 Building Pressurization.
    44. 408.1 General. Filter efficiencies shall be certified by the
    45. 408.2 Filters for Hospitals.
    46. 411.1 The air from dining areas may be used to ventilate the
    47. 412.1 Boiler, heater and electrical equipment rooms shall be
    48. 412.2 Floor surfaces in occupied spaces above such rooms
    49. 413.1 Rooms in areas where excessive heat or moisture is
    50. 413.2 Kitchen, morgues and laundries located inside a hos-
    51. 414.1 Exhaust Systems. A separate, dedicated exhaust
    52. 414.2 Air Distribution. The supply outlets and exhaust
    53. 415.1 Air Distribution. The supply outlets and exhaust and
    54. 416.1 An alarm system which is based on static pressure con-
    55. 416.2 Other acceptable alarm systems will be allowed when
    56. 416.3 [OSHPD 4] For correctional treatment centers, the
    57. 416.4 Prior to acceptance of the rooms, the alarm system
    58. 417.0 Testing and Balancing Airborne Infection Isola-
    59. 418.1 Air Changes. The ETO sterilization equipment room
    60. 418.2 Exhaust Requirements.
    61. 418.3 Ventilation Requirements.
    62. 418.4 Gas Valves. Installation of gas line hand valves at the
    63. 418.5 Alarm Systems. An Audible and visual alarm system
    64. 419.1 Formula Preparation Area. Air shall be supplied
    65. 419.2 Treatment Area/Room. Air shall be supplied over
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
  18. Chapter 18 — REFERENCED STANDARDS
  19. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  20. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  21. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  22. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  23. Appendix E — SUSTAINABLE PRACTICES
  24. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
  26. Appendix H — PROFESSIONAL QUALIFICATIONS
  27. Appendix I — INDOOR HORTICULTURAL FACILITIES
  28. Appendix J — CLEAN AIR DELIVERY

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.