717.1 General — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 717.1 · Effective January 1, 2026 · Official source: Building Standards Commission
The minimum size of a building sewer shall be determined on the basis of the total number of fixture units drained by such sewer, in accordance with Table 717.1. No building sewer shall be smaller than the building drain.
For alternate methods of sizing building sewers, see Appendix C.
TABLE 717.1
MAXIMUM/MINIMUM FIXTURE UNIT LOADING
| ON BUILDING SEWER PIPING* | |||
|---|---|---|---|
SIZE OF PIPE (inches) |
SLOPE (inches per foot) |
SLOPE (inches per foot) |
SLOPE (inches per foot) |
SIZE OF PIPE (inches) |
1⁄16 | 1⁄8 | 1⁄4 |
6 and smaller |
(As specified in Table 703.2/ No minimum loading) |
(As specified in Table 703.2/ No minimum loading) |
(As specified in Table 703.2/ No minimum loading) |
8 |
1950/1500 | 2800/625 | 3900/275 |
10 |
3400/1600 | 4900/675 | 6800/300 |
12 |
5600/1700 | 8000/725 | 11 200/325 |
For SI units: 1 inch = 25 mm, 1 inch per foot = 83.3 mm/m
- See also Appendix H, Private Sewage Disposal Systems. For alternate methods of sizing drainage piping, see Appendix C.