Chapter 7 — SANITARY DRAINAGE

704.3 Commercial Sinks — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 704.3 · Effective January 1, 2026 · Official source: Building Standards Commission

Pot sinks, scullery sinks, dishwashing sinks, silverware sinks, and other similar fixtures shall be connected directly to the drainage system. A floor drain shall be provided adjacent to the fixture and shall be connected on the sewer side of the sink. No other drainage

168 2025 CALIFORNIA PLUMBING CODE

SANITARY DRAINAGE

TABLE 703.2

MAXIMUM UNIT LOADING AND MAXIMUM LENGTH OF DRAINAGE AND VENT PIPING

SIZE OF PIPE (inches) 11⁄4 11⁄2 2 3 4 5 6 8 10 12
Maximum Units
Drainage Piping1
Vertical
Horizontal


1
1


22, 7
17


163
83


484
354


256
2165


600
4285


1380
7205


3600
26405


5600
46805


8400
82005
Maximum Length
Drainage Piping
Vertical, (feet)
Horizontal (unlimited)


45


65


85


212


300


390


510


750


–


–
Vent Piping
Horizontal and Vertical6
Maximum Units
Maximum Lengths, (feet)


1
45


83
60


24
120


84
212


256
300


600
390


1380
510


3600
750


–


–

For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm

Notes: 1 Excluding trap arm. 2 Except for sinks, urinals, and dishwashers – exceeding 1 fixture unit. 3 Except for six-unit traps or water closets. 4 Not to exceed six water closets or five six-unit traps. 5 Based on 1 ⁄ 4 inch per foot (20.8 mm/m) slope. For 1 ⁄ 8 of an inch per foot (10.4 mm/m) slope, multiply horizontal fixture units by a factor of 0.8. 6 The diameter of an individual vent shall be not less than 1 1 ⁄ 4 inches (32 mm) nor less than one-half the diameter of the drain to which it is connected. Fixture unit load values for drainage and vent piping shall be computed from Table 702.1 and Table 702.2. Not to exceed one-third of the total permitted length of a vent shall be permitted to be installed in a horizontal position. Where vents are increased one pipe size for their entire length, the maximum length limitations specified in this table do not apply. This table is in accordance with the requirements of Section 901.3. 7 Up to 8 public lavatories are permitted to be installed on a 1 1 ⁄ 2 inch (40 mm) vertical branch or horizontal sanitary branch sloped at 1 ⁄ 4 inch per foot (20.8 mm/m).

line shall be connected between the floor drain waste con nection and the fixture drain. The fixture and floor drain shall be trapped and vented in accordance with this code.