702.2 Intermittent Flow — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 702.2 · Effective January 1, 2026 · Official source: Building Standards Commission
Drainage fixture units for intermittent flow into the drainage system shall be computed on the rated discharge capacity in gallons per minute (gpm) (L/s) in accordance with Table 702.2.
TABLE 702.1(1) MAXIMUM DRAINAGE FIXTURE UNITS FOR A
TRAP AND TRAP ARM*
For SI Units: 1 inch = 25 mm
*** Exception:** On self-service laundries.
TABLE 702.2
DISCHARGE CAPACITY IN GALLONS PER MINUTE FOR
INTERMITTENT FLOW ONLY*
| GPM | FIXTURE UNITS |
|---|---|
Up to 71⁄2 |
Equals 1 Fixture Unit |
Greater than 71⁄2 to 15 |
Equals 2 Fixture Units |
Greater than 15 to 30 |
Equals 4 Fixture Units |
Greater than 30 to 50 |
Equals 6 Fixture Units |
For SI units: 1 gallon per minute = 0.06 L/s
- Discharge capacity exceeding 50 gallons per minute (3.15 L/s) shall be determined by the Authority Having Jurisdiction.