710.13 Macerating Toilet Systems and Pumped Waste Systems — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 710.13 · Effective January 1, 2026 · Official source: Building Standards Commission
Waste Systems. Fixtures shall be permitted to discharge to a macerating toilet system, or pumped waste system shall be permitted as an alternate to a sewage pump system where approved by the Authority Having Jurisdiction. Such systems shall comply with ASME A112.3.4/CSA B45.9 and shall be installed in accordance with the manufacturer’s installation
instructions.
710.13.1 Sumps. The sump shall be watertight and gastight. 710.13.2 Discharge Piping. The discharge piping shall be sized in accordance with manufacturer’s instructions and shall be not less than 3/4 of an inch (20 mm) in diameter. The developed length of the discharge piping shall not exceed the manufacturer’s instructions. A check
174 2025 CALIFORNIA PLUMBING CODE
SANITARY DRAINAGE
valve and fullway-type shutoff valve shall be located within the discharge line or internally within the device.
710.13.3 Venting. The plumbing fixtures that discharge into the macerating device shall be vented in accordance with this code. The sump shall be vented in accordance with the manufacturer’s instructions, and such vent shall be permitted to connect to the fixture venting.
Get a plain-English answer with a citation back to this text.