Skip to content

Earlier editions: 20222019

Chapter 4 — VENTILATION AIR

404.3 Zone Ventilation Efficiency. The zone ventilation

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

efficiency ( Evz ) shall be determined in accordance with Section 404.3.1 or Section 404.3.2. [ASHRAE 62.1:A1.2] 404.3.1 Single Supply Systems. For single supply systems, where all of the air supplied to each ventilation zone is a mixture of outdoor air and system-level recirculated air, zone ventilation efficiency ( Evz ) shall be determined in accordance with Equation 404.3.1(1). Examples of single supply systems include constant-volume reheat, single-duct VAV, single-fan dual-duct, and multizone-systems.

Evz = 1+ XsZpz [Equation 404.3.1(1)]

Where the average outdoor air fraction for the system ( Xs ) shall be determined in accordance with Equation 404.2 and the primary outdoor air fraction for the zone ( Zpz ) shall be determined in accordance with Equation 404.3.1(2).

Zpz = Voz/Vpz [Equation 404.3.1(2)]

For VAV systems, Vpz is the lowest zone primary airflow value expected at the design condition analyzed.

[ASHRAE 62.1:A1.2.1] 404.3.2 Secondary-Recirculation Systems. For secondary-recirculation systems where the supply air or a portion thereof to each ventilation zone is recirculated air (air that has not been directly mixed with outdoor air) from other zones, zone ventilation efficiency ( Evz ) shall be determined in accordance with Equation 404.3.2(1). Examples

of secondary-recirculation systems include dual-fan dualduct and fan-powered mixing-box systems, and systems that include transfer fans for conference rooms.

[Equation 404.3.2(1)] Evz = ( Fa+Xs•Fb–Zpz•Ep•Fc )/ Fa

Where system air fractions Fa, Fb, and Fc are determined in accordance with Equation 404.3.2(2), Equation 404.3.2(3), and Equation 404.3.2(4), as applicable.

Fa = Ep + (1– Ep )• Er [Equation 404.3.2(2)]

Fb = Ep [Equation 404.3.2(3)]

Fc = 1–(1– Ez )•(1– Er )•(1– Ep ) [Equation 404.3.2(4)]

Where the zone primary air fraction ( Ep ) shall be determined in accordance with Equation 404.3.2(5), zone secondary recirculation fraction ( Er ) shall be determined by the designer based on system configuration, and zone air distribution effectiveness ( Ez ) shall be determined in accordance with Section 403.2.2. [ASHRAE 62.1:A1.2.2]

Ep = Vpz / Vdz [Equation 404.3.2(5)]

Where:

Az = Zone floor area: The net occupiable floor area of the ventilation zone, ft [2] (m [2] ).

D = Occupant diversity: The ratio of the system population to the sum of the zone populations. Ep = Primary air fraction: The fraction of primary air in the discharge air to the ventilation zone. Er = Secondary recirculation fraction: In systems with secondary recirculation of return air, the fraction of secondary recirculated air to the zone that is representative of average system return air rather than air directly recirculated from the zone. Ev = System ventilation efficiency: the efficiency with which the system distributes air from the outdoor air intake to the breathing zone in the ventilationcritical zone, which requires the largest fraction of outdoor air in the primary airstream. Evz = Zone ventilation efficiency: The efficiency with which the system distributes air from the outdoor air intake to the breathing zone in any particular ventilation zone.

Ez = Zone air distribution effectiveness: A measure of the effectiveness of supply air distribution to the breathing zone. Ez is determined in accordance with Section 403.2.2.

Fa = Supply air fraction: The fraction of supply air to the ventilation zone from sources or air outside the

zone.

76 2025 CALIFORNIA MECHANICAL CODE

VENTILATION AIR

Fb = Mixed air fraction: The fraction of supply air to the ventilation zone from fully mixed primary air.

Fc = Outdoor air fraction: The fraction of outdoor air to the ventilation zone from sources of air outside

the zone.

Ps = System population: the simultaneous number of occupants in the area served by the ventilation sys tem.

Pz = Zone population: see Section 403.2.1. Ra = Area outdoor air rate, CFM/ft [2] . See Section 403.2.1.

Rp = People outdoor air rate, CFM/person. See Section 403.2.1.

Vbz = Breathing zone outdoor airflow, CFM. See Section 403.2.1.

Vdz = Zone discharge airflow, CFM. The expected discharge (supply) airflow to the zone that includes primary airflow and secondary recirculated airflow, CFM.

Vot = Outdoor air intake flow, CFM. See Section 403.3, Section 403.4, and Section 403.5.2.

Vou = Uncorrected outdoor air intake, CFM. See Section 403.5.1.

Voz = Zone outdoor airflow, CFM. See Section 403.2.3. Vps = System primary airflow, CFM. The total primary airflow supplied to all zones served by the system from the air-handling unit at which the outdoor air intake is located.

Vpz = Zone primary airflow, CFM. The zone primary airflow to the ventilation zone, including outdoor air and recirculated air.

Xs = Average outdoor air fraction: At the primary air handler, the fraction of outdoor air intake flow in the system primary airflow. Zpz = Primary outdoor air fraction: The outdoor air fraction required in the primary air supplied to the ventilation zone prior to the introduction of any secondary recirculation air. [ASHRAE 62.1:A3]

For SI Units: 1 square foot = 0.0929 m [2], 1 cubic foot per minute =

0.0283 m [3] /min, 1 cubic foot per minute = 0.4719 L/s, 1 cubic foot per

minute per square foot = 5.08 [(L/s)/m [2] ]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
    Overview
    1. 401.1 Applicability. This chapter contains requirements for
    2. 401.2 Indoor Swimming Pools. The design of ventilation
    3. 401.3 Filters. [BSC-CG & DSA-SS] In mechanically ven-
    4. 402.1 Occupiable Spaces. Occupiable spaces listed in
    5. 402.2 Natural Ventilation Procedure. [Not permitted
    6. 402.3 Mechanical Ventilation. [Not permitted for
    7. 402.4 Outdoor Air Intakes. Ventilation system outdoor
    8. 403.1 General. The design outdoor air intake flow rate for
    9. 403.2 Zone Calculations. Ventilation zone parameters
    10. 403.3 Single-Zone Systems. For ventilation systems
    11. 403.4 One Hundred Percent Outdoor Air Systems.
    12. 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
    13. 403.6 Design for Varying Operating Conditions. Ventilation sys…
    14. 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
    15. 403.8 Dynamic Reset. The system shall be permitted to be
    16. 403.9 Air Classification and Recirculation. Air shall be
    17. 403.10 Air Balance. All mechanical ventilation systems
    18. 404.1 System Ventilation Efficiency. The system ventilation ef…
    19. 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
    20. 404.3 Zone Ventilation Efficiency. The zone ventilation
    21. 405.1 General. Rooms or occupied spaces within residential occ…
    22. 405.2 Ventilation Air Rate. The required mechanical ventilatio…
    23. 405.3 Bathroom Exhaust. A mechanical exhaust directly
    24. 405.4 Kitchen Exhaust. A mechanical exhaust system that
    25. 405.5 Ventilation Openings. Occupiable spaces shall be
    26. 406.0 Evaporative Cooling System for Health Care
    27. 407.1 General.
    28. 407.2 Outdoor Air Intakes and Exhaust Outlets.
    29. 407.3 Air Balance.
    30. 407.4 Air Circulation.
    31. 407.5 Variable Air Volume.
    32. 407.6 Economizers.
    33. 407.7 Unoccupied Turndown.
    34. 408.3 Filters for Skilled Nursing Facilities, Intermedi-
    35. 408.4 Filters for Outpatient Facilities.
    36. 408.5 Filters for Recirculating Room Units.
    37. 409.1 Ducts which penetrate construction, intended for X-
    38. 409.2 Duct linings and their use shall meet the requirements
    39. 409.3 The anchorage and supporting structural elements for
    40. 410.1 Laboratory Ventilating Systems. Laboratory ven-
    41. 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
    42. 410.3 Laboratory Fume Hoods. Laboratory fume hoods
    43. 407.8 Building Pressurization.
    44. 408.1 General. Filter efficiencies shall be certified by the
    45. 408.2 Filters for Hospitals.
    46. 411.1 The air from dining areas may be used to ventilate the
    47. 412.1 Boiler, heater and electrical equipment rooms shall be
    48. 412.2 Floor surfaces in occupied spaces above such rooms
    49. 413.1 Rooms in areas where excessive heat or moisture is
    50. 413.2 Kitchen, morgues and laundries located inside a hos-
    51. 414.1 Exhaust Systems. A separate, dedicated exhaust
    52. 414.2 Air Distribution. The supply outlets and exhaust
    53. 415.1 Air Distribution. The supply outlets and exhaust and
    54. 416.1 An alarm system which is based on static pressure con-
    55. 416.2 Other acceptable alarm systems will be allowed when
    56. 416.3 [OSHPD 4] For correctional treatment centers, the
    57. 416.4 Prior to acceptance of the rooms, the alarm system
    58. 417.0 Testing and Balancing Airborne Infection Isola-
    59. 418.1 Air Changes. The ETO sterilization equipment room
    60. 418.2 Exhaust Requirements.
    61. 418.3 Ventilation Requirements.
    62. 418.4 Gas Valves. Installation of gas line hand valves at the
    63. 418.5 Alarm Systems. An Audible and visual alarm system
    64. 419.1 Formula Preparation Area. Air shall be supplied
    65. 419.2 Treatment Area/Room. Air shall be supplied over
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
  18. Chapter 18 — REFERENCED STANDARDS
  19. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  20. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  21. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  22. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  23. Appendix E — SUSTAINABLE PRACTICES
  24. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
  26. Appendix H — PROFESSIONAL QUALIFICATIONS
  27. Appendix I — INDOOR HORTICULTURAL FACILITIES
  28. Appendix J — CLEAN AIR DELIVERY

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.