402.2 Natural Ventilation Procedure. [Not permitted
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
for OSHPD 1, 2, 3, 4 & 5] Natural ventilation systems shall comply with the requirements of either Section 402.2.1 through Section 402.2.1.6(A) or Section 402.2.2. Designers shall provide interior air barriers, insulation, or other means that separate naturally ventilated spaces from mechanically cooled spaces to prevent high-dew-point outdoor air from coming into contact with mechanically cooled surfaces.
[ASHRAE 62.1:6.4]
402.2.1 Prescriptive Compliance Path. Any zone designed for natural ventilation shall include a mechanical ventilation system designed in accordance with Section 403.0.
Exceptions:
(1) Zones in buildings that have all of the following:
(a) Natural ventilation openings that comply with the requirements of Section 402.2.1.
(b) Controls that prevent the natural ventilation openings from being closed during periods of expected occupancy, or natural ventilation openings that are permanently open.
(2) Zones that are not served by heating or cooling equipment. {ASHRAE 62.1:6.4.1}
402.2.1.1 Ceiling Height. For ceilings that are parallel to the floor, the ceiling height ( H ) to be used in Section 402.2.1.3 through Section 402.2.1.5 shall be the minimum ceiling height in the zone.
For zones where ceiling height increases as distance from the openings is increased, the ceiling height shall be determined as the average height of the ceiling within 20 feet (6096 mm) from the operable openings. [ASHRAE 62.1:6.4.1.1]
402.2.1.2 Floor Area to be Ventilated. The nat urally ventilated area in zones or portions of zones shall extend from the openings to a distance determined in accordance with Section 402.2.1.3, Section 402.2.1.4, or Section 402.2.1.5. Openings shall be in accordance with the requirements of Section 402.2.1.6.
For zones where ceilings are not parallel to the floor, the ceiling height shall be determined in accordance with Section 402.2.1.1. [ASHRAE 62.1:6.4.1.2]
402.2.1.3 Single Side Opening. For zones with openings on only one side of the zone, the naturally ventilated area shall extend to a distance not greater than 2 times the height of the ceiling from the openings. [ASHRAE 62.1:6.4.1.3]
402.2.1.4 Double Side Opening. For zones with openings on two opposite sides of the zone, the naturally ventilated area shall extend between the openings separated by a distance not greater than 5 times the height of the ceiling. [ASHRAE 62.1:6.4.1.4]
70 2025 CALIFORNIA MECHANICAL CODE
VENTILATION AIR
TABLE 402.2.1.6(A)(1) MINIMUM OPENABLE AREAS: SINGLE OPENINGS*
| [ASHRAE 62.1: TABLE 6-5] | |||
|---|---|---|---|
| Vbz/Az ≤ (CFM/ft2) |
TOTAL OPENABLE AREAS IN ZONE AS A PERCENTAGE OFAz |
TOTAL OPENABLE AREAS IN ZONE AS A PERCENTAGE OFAz |
TOTAL OPENABLE AREAS IN ZONE AS A PERCENTAGE OFAz |
| Vbz/Az ≤ (CFM/ft2) |
HS/WS ≤ 0.1 | 0.1 <****HS/WS ≤ 1 | HS/WS > 1 |
| 0.2 | 4.0 | 2.9 | 2.5 |
| 0.4 | 6.9 | 5.0 | 4.4 |
| 0.6 | 9.5 | 6.9 | 6.0 |
| 0.8 | 12.0 | 8.7 | 7.6 |
| 1.1 | 15.5 | 11.2 | 9.8 |
For SI units: 1 cubic foot per minute = 0.0283 m [3] /min, 1 cubic foot per minute = 0.4719 L/s, 1 cubic foot per minute per square foot = 5.08
[(L/s)/m [2] ], 1 square foot = 0.0929 m [2]
Where:
Vbz = breathing zone outdoor airflow, per Table 402.1. Az = zone floor area, the net occupiable floor area of the ventilation zone. W S = aggregated width of all single outdoor openings located at the same elevation.
H S = vertical dimension of the single opening or the least vertical dimension of the openings where there are multiple openings.
Volumetric airflow rates used to estimate required openable area are based on the following:
Dry-air density of 0.075 lbda/ft [3] (1.2 kgda/m [3] ) at a barometric pressure of 1 atm (101.3 kPa) and an air temperature of 70°F (21°C)
Temperature difference between indoors and outdoors of 1.8°F (1°C)
Gravity constant of 32.2 ft/s [2] (9.81m/s [2] )
Window discharge coefficient of 0.6
(2) Determine the effect of pressure losses along natural ventilation airflow paths on the resulting flow rates, including inlet openings, air transfer grills, ventilation stacks, and outlet openings during representative conditions of expected natural ventilation system use.
(3) Quantify natural ventilation airflow rates of identified airflow paths accounting for wind induced and thermally induced driving pressures during representative conditions of expected natural ventilation system use.
(4) Design to provide outdoor air in quantities sufficient to result in acceptable IAQ as established under Section 403.2.1 or ASHRAE 62.1 during representative conditions of expected natural ventilation system use. {ASHRAE 62.1:6.4.2}
402.2.3 Control and Accessibility. The means to open required operable openings shall be readily accessible to building occupants whenever the space is occupied. Controls shall be designed to coordinate operation of the natural and mechanical ventilation systems.
[ASHRAE 62.1:6.4.3]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
▸Chapter 4 — VENTILATION AIR
Overview- 401.1 Applicability. This chapter contains requirements for
- 401.2 Indoor Swimming Pools. The design of ventilation
- 401.3 Filters. [BSC-CG & DSA-SS] In mechanically ven-
- 402.1 Occupiable Spaces. Occupiable spaces listed in
- 402.2 Natural Ventilation Procedure. [Not permitted
- 402.3 Mechanical Ventilation. [Not permitted for
- 402.4 Outdoor Air Intakes. Ventilation system outdoor
- 403.1 General. The design outdoor air intake flow rate for
- 403.2 Zone Calculations. Ventilation zone parameters
- 403.3 Single-Zone Systems. For ventilation systems
- 403.4 One Hundred Percent Outdoor Air Systems.
- 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
- 403.6 Design for Varying Operating Conditions. Ventilation sys…
- 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
- 403.8 Dynamic Reset. The system shall be permitted to be
- 403.9 Air Classification and Recirculation. Air shall be
- 403.10 Air Balance. All mechanical ventilation systems
- 404.1 System Ventilation Efficiency. The system ventilation ef…
- 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
- 404.3 Zone Ventilation Efficiency. The zone ventilation
- 405.1 General. Rooms or occupied spaces within residential occ…
- 405.2 Ventilation Air Rate. The required mechanical ventilatio…
- 405.3 Bathroom Exhaust. A mechanical exhaust directly
- 405.4 Kitchen Exhaust. A mechanical exhaust system that
- 405.5 Ventilation Openings. Occupiable spaces shall be
- 406.0 Evaporative Cooling System for Health Care
- 407.1 General.
- 407.2 Outdoor Air Intakes and Exhaust Outlets.
- 407.3 Air Balance.
- 407.4 Air Circulation.
- 407.5 Variable Air Volume.
- 407.6 Economizers.
- 407.7 Unoccupied Turndown.
- 408.3 Filters for Skilled Nursing Facilities, Intermedi-
- 408.4 Filters for Outpatient Facilities.
- 408.5 Filters for Recirculating Room Units.
- 409.1 Ducts which penetrate construction, intended for X-
- 409.2 Duct linings and their use shall meet the requirements
- 409.3 The anchorage and supporting structural elements for
- 410.1 Laboratory Ventilating Systems. Laboratory ven-
- 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
- 410.3 Laboratory Fume Hoods. Laboratory fume hoods
- 407.8 Building Pressurization.
- 408.1 General. Filter efficiencies shall be certified by the
- 408.2 Filters for Hospitals.
- 411.1 The air from dining areas may be used to ventilate the
- 412.1 Boiler, heater and electrical equipment rooms shall be
- 412.2 Floor surfaces in occupied spaces above such rooms
- 413.1 Rooms in areas where excessive heat or moisture is
- 413.2 Kitchen, morgues and laundries located inside a hos-
- 414.1 Exhaust Systems. A separate, dedicated exhaust
- 414.2 Air Distribution. The supply outlets and exhaust
- 415.1 Air Distribution. The supply outlets and exhaust and
- 416.1 An alarm system which is based on static pressure con-
- 416.2 Other acceptable alarm systems will be allowed when
- 416.3 [OSHPD 4] For correctional treatment centers, the
- 416.4 Prior to acceptance of the rooms, the alarm system
- 417.0 Testing and Balancing Airborne Infection Isola-
- 418.1 Air Changes. The ETO sterilization equipment room
- 418.2 Exhaust Requirements.
- 418.3 Ventilation Requirements.
- 418.4 Gas Valves. Installation of gas line hand valves at the
- 418.5 Alarm Systems. An Audible and visual alarm system
- 419.1 Formula Preparation Area. Air shall be supplied
- 419.2 Treatment Area/Room. Air shall be supplied over
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY