402.1 Occupiable Spaces. Occupiable spaces listed in
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Table 402.1 shall be designed to have ventilation (outdoor) air for occupants in accordance with this chapter. [DSA-SS] Ven- tilation air requirements for occupancies regulated by the California Energy Commission are found in the California Energy Code.
[CEC] Ventilation air requirements for occupancies regu- lated by the California Energy Commission and found in the California Energy Code supersede those of the California Mechanical Code.
[OSHPD 1, 2, 3, 4 & 5] Health care spaces shall meet the ventilation requirements found in Table 4-A. Ventilation rates for areas not specified in Table 4-A shall have minimum ven- tilation and air change rates per ANSI/ASHRAE Standard 62.1. Where areas with prescribed ventilation rates in both Standards 62.1 and Table 4-A exist, the higher of the two air change rates shall be used.
402.1.1 Construction Documents. The outdoor air ventilation rate and air distribution assumptions made in the design of the ventilation system shall be clearly identified on the construction documents.
402.1.2 Ventilation in Health Care Facilities.
Mechanical ventilation for health care facilities shall be designed and installed in accordance with this code, ASHRAE/ASHE 170, and NFPA 99. [OSHPD 1, 1R, 2, 3, 4 & 5] Ventilation for health care facilities shall be designed and installed in accordance with this code and Table 4-A. All supply-air, return air, and exhaust-air sys- tems shall comply with this code and ASHRAE 170. When the requirements of this code conflict with ASHRAE 170, the most restrictive requirements shall prevail. The text of ASHRAE 170 shall be modified as follows:
(1) ASHRAE 170. Section 6.1.2.1 -- Also see Section 319.0.
(2) ASHRAE 170. Section 6.3.1.3 – Modify as follows: Relief air other than class 1 shall discharge at least 10 feet (3048 mm) from any outside air intake.
(3) ASHRAE 170. Section 6.3.2 -- Also see Section 407.1.2 and 407.2.2.
(4) ASHRAE 170. Section 6.4 -- Modify as follows:
c.: Replace Table 7-1, 8-1, 8-2, or 9-1 with Table 4-A.
d.: Replace Table 7-1, 8-1, 8-2, or 9-1 with Table 4-A.
(5) ASHRAE 170. Section 6.9 -- See also Section 605.2 and 605.3.
(6) ASHRAE 170. Section 7.1a -- Modify as follows:
Replace reference to Table 7-1 with reference to Table 4-A.
(7) ASHRAE 170. Section 7.2.1 c -- Not adopted.
(8) ASHRAE 170. Section 7.2.2 Also see Section 415.0.
(9) ASHRAE 170. Section 7.2.3 -- Not adopted.
(10)ASHRAE 170. Section 7.3.1 -- Modify as follows:
Replace reference to Table 7-1 with reference to Table 4-A.
(11) ASHRAE 170. Section 7.4.1 -- Modify as follows:
Delete the Exception that allows for high return grilles.
(12)ASHRAE 170. Section 8.1a -- Modify as follows: Replace reference to Table 8-1 with reference to Table 4-A.
(13)ASHRAE 170. Section 8.2 -- Modify as follows: Replace reference to Table 8-2 with reference to Table 4-A.
(14)ASHRAE 170. Section 9.1a -- Modify as follows: Replace reference to Table 9-1 with reference to Table 4-A.
VENTILATION AIR
«
«
402.2.1.5 Corner Openings. For zones with operable openings on two adjacent sides of a zone, the distance from the operable openings shall be not more than 5 H along a line drawn between the two openings that are farthest apart. Floor area outside that line shall comply with Section 402.2.1.1 as a zone having openings on only one side of the zone.
[ASHRAE 62.1:6.4.1.5]
402.2.1.6 Location and Size of Openings. Zones or portions of zones to be naturally ventilated shall have a permanently open airflow path to openings directly connected to the outdoors. The minimum flow rate to the zone shall be determined in accordance with
Section 403.2.1. This flow rate shall be used to deter mine the required openable area of openings, accounting only for buoyancy-driven flow. Wind-driven flow shall be used only where it can be demonstrated that the minimum flow rate is provided during all occupied hours. Openings shall be sized in accordance with Section 402.2.1.6(A). Permanently open airflow path shall include, but not be limited to, pathways that would allow airflow unimpeded by partitions, walls, and furnishings. {ASHRAE 62.1:6.4.1.6}
402.2.1.6(A) Sizing Openings. Where the zone is ventilated using a single opening or multiple single openings located at the same elevation, the openable area as a percent of the net occupiable floor area shall be greater than or equal to the value indicated in Table 402.2.1.6(A)(1). Where the zone is ventilated using two openings located at different elevations or multiple pairs of such openings, the openable area as a percent of the net occupiable floor area shall be greater than or equal to the value indicated in Table 402.2.1.6(A)(2).
Where openings are obstructed by louvers or screens, the openable area shall be based on the net free area of the opening. Where interior zones, or portions of zones, without direct openings to the outdoors are ventilated through adjoining zones, the opening between zones shall be permanently unobstructed and have a free area of not less than twice the percent of occupiable floor area used to determine the opening size of adjacent exterior zones, or 25 square feet (2.3 m [2] ), whichever is greater. Table 402.2.1.6(A)(1) and Table 402.2.1.6(A)(2) are based on buoyancy-driven flow and shall not address thermal comfort. [ASHRAE 62.1:6.4.1.6.1]
402.2.2 Engineered System Compliance Path. For an engineered natural ventilation system, the following shall be included:
(1) Determine hourly environmental conditions, including outdoor air dry-bulb temperature; dew-point temperature; outdoor concentration of contaminants, including PM2.5, PM10, and ozone where data are available; wind speed and direction; and internal heat gains during expected hours of natural ventilation operation.
»
»
»
»
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
▸Chapter 4 — VENTILATION AIR
Overview- 401.1 Applicability. This chapter contains requirements for
- 401.2 Indoor Swimming Pools. The design of ventilation
- 401.3 Filters. [BSC-CG & DSA-SS] In mechanically ven-
- 402.1 Occupiable Spaces. Occupiable spaces listed in
- 402.2 Natural Ventilation Procedure. [Not permitted
- 402.3 Mechanical Ventilation. [Not permitted for
- 402.4 Outdoor Air Intakes. Ventilation system outdoor
- 403.1 General. The design outdoor air intake flow rate for
- 403.2 Zone Calculations. Ventilation zone parameters
- 403.3 Single-Zone Systems. For ventilation systems
- 403.4 One Hundred Percent Outdoor Air Systems.
- 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
- 403.6 Design for Varying Operating Conditions. Ventilation sys…
- 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
- 403.8 Dynamic Reset. The system shall be permitted to be
- 403.9 Air Classification and Recirculation. Air shall be
- 403.10 Air Balance. All mechanical ventilation systems
- 404.1 System Ventilation Efficiency. The system ventilation ef…
- 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
- 404.3 Zone Ventilation Efficiency. The zone ventilation
- 405.1 General. Rooms or occupied spaces within residential occ…
- 405.2 Ventilation Air Rate. The required mechanical ventilatio…
- 405.3 Bathroom Exhaust. A mechanical exhaust directly
- 405.4 Kitchen Exhaust. A mechanical exhaust system that
- 405.5 Ventilation Openings. Occupiable spaces shall be
- 406.0 Evaporative Cooling System for Health Care
- 407.1 General.
- 407.2 Outdoor Air Intakes and Exhaust Outlets.
- 407.3 Air Balance.
- 407.4 Air Circulation.
- 407.5 Variable Air Volume.
- 407.6 Economizers.
- 407.7 Unoccupied Turndown.
- 408.3 Filters for Skilled Nursing Facilities, Intermedi-
- 408.4 Filters for Outpatient Facilities.
- 408.5 Filters for Recirculating Room Units.
- 409.1 Ducts which penetrate construction, intended for X-
- 409.2 Duct linings and their use shall meet the requirements
- 409.3 The anchorage and supporting structural elements for
- 410.1 Laboratory Ventilating Systems. Laboratory ven-
- 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
- 410.3 Laboratory Fume Hoods. Laboratory fume hoods
- 407.8 Building Pressurization.
- 408.1 General. Filter efficiencies shall be certified by the
- 408.2 Filters for Hospitals.
- 411.1 The air from dining areas may be used to ventilate the
- 412.1 Boiler, heater and electrical equipment rooms shall be
- 412.2 Floor surfaces in occupied spaces above such rooms
- 413.1 Rooms in areas where excessive heat or moisture is
- 413.2 Kitchen, morgues and laundries located inside a hos-
- 414.1 Exhaust Systems. A separate, dedicated exhaust
- 414.2 Air Distribution. The supply outlets and exhaust
- 415.1 Air Distribution. The supply outlets and exhaust and
- 416.1 An alarm system which is based on static pressure con-
- 416.2 Other acceptable alarm systems will be allowed when
- 416.3 [OSHPD 4] For correctional treatment centers, the
- 416.4 Prior to acceptance of the rooms, the alarm system
- 417.0 Testing and Balancing Airborne Infection Isola-
- 418.1 Air Changes. The ETO sterilization equipment room
- 418.2 Exhaust Requirements.
- 418.3 Ventilation Requirements.
- 418.4 Gas Valves. Installation of gas line hand valves at the
- 418.5 Alarm Systems. An Audible and visual alarm system
- 419.1 Formula Preparation Area. Air shall be supplied
- 419.2 Treatment Area/Room. Air shall be supplied over
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY