Piping installed aboveground shall comply with all of the following:
(1) Piping shall be securely supported and located where it will be protected from physical damage.
(2) Where passing through an exterior wall, the piping shall also be protected from corrosion by coating or wrapping with an inert material approved for such applications.
(3) The piping shall be sealed around its circumference at the point of the exterior penetration to prevent the entry of water, insects, and rodents.
284 2025 CALIFORNIA MECHANICAL CODE
FUEL GAS PIPING
(4) Where piping is encased in a protective pipe sleeve, the annular spaces between the gas piping and the sleeve and between the sleeve and the wall opening shall be sealed.
(5) Piping installed outdoors shall be elevated not less than 3½ inches (89 mm) above the ground.
(6) Sealing materials shall be compatible with the piping and sleeve. [NFPA 54:7.2.1]
1310.3.1 Protective Coating. Where piping is in contact with a material or an atmosphere corrosive to the piping system, the piping and fittings shall be coated with a corrosion-resistant material. Any such coating used on piping or components shall not be considered as adding strength to the system. [NFPA 54:7.2.2]
1310.3.2 Building Structure. The installation of gas piping shall not cause structural stresses within building components to exceed allowable design limits. Approval shall be obtained before any beams or joists are cut or notched. [NFPA 54:7.2.3.1 – 7.2.3.2]
1310.3.3 Gas Piping to be Sloped. Piping for other than dry gas conditions shall be sloped not less than 1/4 inch in 15 feet (1.4 mm/m) to prevent traps. [NFPA 54:7.2.4]
1310.3.3.1 Ceiling Locations. Gas piping shall be permitted to be installed in accessible spaces between a fixed ceiling and a dropped ceiling, whether or not such spaces are used as a plenum. Valves shall not be located in such spaces.
Exception: Appliance or equipment shutoff valves required by this code shall be permitted to be installed in accessible spaces containing vented appliances.
1310.3.4 Prohibited Locations. Gas piping inside any building shall not be installed in or through a clothes chute, chimney or gas vent, dumbwaiter, elevator shaft, or air duct, other than combustion air ducts. [NFPA 54:7.2.5]
Exception: Ducts used to provide ventilation air in accordance with Section 701.0 or to above-ceiling spaces in accordance with Section 1310.3.3.1.
1310.3.5 Hangers, Supports, and Anchors. Piping shall be supported with metal pipe hooks, metal pipe straps, metal bands, metal brackets, metal hangers, or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue strains on connected appliances and equipment and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP-58. [NFPA 54:7.2.6.1]
1310.3.5.1 Spacing. Spacing of supports in gas piping installations shall not be greater than shown in Table 1310.3.5.1. Spacing of supports of CSST shall be in accordance with the CSST manufac turer’s instructions. [NFPA 54:7.2.6.2]
TABLE 1310.3.5.1
SUPPORT OF PIPING
[NFPA 54: TABLE 7.2.6.2]
| STEEL PIPE, NOMINAL SIZE OF PIPE(inches) |
SPACING OF SUPPORTS (feet) |
NOMINAL SIZE OF TUBING SMOOTH WALL (inches O.D.) |
SPACING OF SUPPORTS (feet) |
|---|---|---|---|
| 1⁄2 | 6 | 1⁄2 | 4 |
3⁄4 or 1 |
8 | 5⁄8 or3⁄4 | 6 |
11⁄4 or larger (horizontal) |
10 | 7⁄8 or 1 (horizontal) |
8 |
11⁄4 or larger (vertical) |
Every floor level |
1 or larger (vertical) |
Every floor level |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
1310.3.5.2 Expansion and Contraction. Supports, hangers, and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting system shall be designed and installed so they are not disengaged by movement of the supported piping. [NFPA 54:7.2.6.3]
1310.3.5.3 Piping on Roofs. Gas piping installed on the roof surfaces shall be supported in accordance with Table 1310.3.5.1. Gas piping shall be elevated not less than 3½ inches (89 mm) above the roof surface. [NFPA 54:7.2.6.4.1, 7.2.6.4.2]
1310.3.6 Removal of Piping. Where piping containing gas is to be removed, the line shall be first disconnected from sources of gas and then thoroughly purged with air, water, or inert gas before cutting or welding is done.