Skip to content

Earlier editions: 20222019

Chapter 13 — FUEL GAS PIPING

1308.6 Gas Pressure Regulators — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1308.6 · Effective January 1, 2026 · Official source: Building Standards Commission

A line pressure regulator shall be installed where the gas supply pressure exceeds the maximum allowable inlet pressure of the appliance served. [NFPA 54:5.7.1]

«

«

«

«

«

«

«

«

«

«

«

«

280 2025 CALIFORNIA MECHANICAL CODE

FUEL GAS PIPING

»

»

»

»

»

»

»

»

»

»

1308.6.1 Listing. Line pressure regulators shall be listed in accordance with CSA/ANSI Z21.80/CSA 6.22

where the outlet pressure is set to 2 psi (14 kPa) or less.

[NFPA 54:5.7.2]

1308.6.2 Location. The gas pressure regulator shall be accessible for servicing. [NFPA 54:5.7.3]

1308.6.3 Regulator Protection. Pressure regulators shall be protected against physical damage. [NFPA 54:5.7.4]

1308.6.4 Regulator Vents. Regulator vents shall be in accordance with Section 1308.14. [NFPA 54:5.7.5]

1308.6.5 Identification. Line pressure regulators at multiple regulator installations shall be marked by a metal tag or other permanent means designating the building or the part of the building being supplied.

[NFPA 54:5.7.6]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Mechanical Code (Title 24, Part 4)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.