Skip to content

Earlier editions: 20222019

Chapter 13 — FUEL GAS PIPING

1311.7 Electrical Connections — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1311.7 · Effective January 1, 2026 · Official source: Building Standards Commission

All electrical connections between wiring and electrically operated control devices in a piping system shall conform to the requirements of NFPA 70.

[NFPA 54:7.14.1]

1311.7.1 Safety Control. Any essential safety control depending on electric current as the operating medium shall be of a type that shuts off (fail safe) the flow of gas in the event of current failure. [NFPA 54:7.14.2]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Mechanical Code (Title 24, Part 4)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.