Skip to content

Earlier editions: 20222019

Chapter 13 — FUEL GAS PIPING

1308.10 Backpressure Protection — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 1308.10 · Effective January 1, 2026 · Official source: Building Standards Commission

Protective devices shall be installed as close to the equipment as practical where the design of equipment connected is such that air, oxygen, or standby gases could be forced into the gas supply system. Gas and air combustion mixers incorporating double diaphragm “zero” or “atmosphere” governors or regulators shall require no further protection unless connected directly to compressed air or oxygen at pressures of 5 psi (34 kPa) or more. [NFPA 54:5.9.1.1, 5.9.1.2]

1308.10.1 Protective Devices. Protective devices shall include but not be limited to the following:

(1) Check valves.

(2) Three-way valves (of the type that completely closes one side before starting to open the other side).

(3) Reverse flow indicators controlling positive shutoff valves.

(4) Normally closed air-actuated positive shutoff pressure regulators. [NFPA 54:5.9.2]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Mechanical Code (Title 24, Part 4)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.