This hub summarizes Division A5.5 environmental‑quality measures, Division A5.6 voluntary Tier 1/Tier 2 performance paths, and the A5.602 verification checklists used to document compliance.

Last reviewed: July 6, 2026

Overview

Appendix Division A5.5 (Environmental Quality) collects nonresidential measures that reduce indoor pollutants and greenhouse‑gas impacts—low‑emitting adhesives, paints and coatings, carpet and resilient flooring, thermal insulation, acoustical controls, refrigerant limits and outdoor/indoor air and moisture controls (see, for example, §A5.504.4.3, §A5.504.4.6 and §A5.508) . These provisions are organized as mandatory measures and elective options intended to improve occupant health, materials performance and lifecycle impacts.

Division A5.6 establishes Voluntary Tiers (CALGreen Tier 1 and Tier 2) that local agencies may adopt to require higher performance. Tiers bundle prerequisites and elective measures across Appendix A5 divisions and set higher thresholds for things like EV charging, cool‑roof reflectance and building energy performance; see §A5.601 for the tier structure and required measures for Tier 1 and Tier 2 .

Verification is handled through CALGreen checklists and documentation requirements: Appendix A5 includes the CALGreen Verification Guidelines and Mandatory/Tier checklists (A5.602, A5.602.1 and A5.602.2) and requires that compliance documentation be placed in the project record per the code’s recording and Chapter 7 verification procedures .

In this section

Code references

Grounded in the retrieved California Green Building Standards Code (CALGreen) — click a citation to read the verbatim passage:

  • CALGreen § 602.1 High relevance — show source text

    VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3

    A5.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A5-3 A5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . APPENDIX A5-13 A5.3 Water Efficiency and Conservation . . . APPENDIX A5-19 A5.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-25 A5.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A5-35 A5.6 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-41 A5.601 CALGren Tier 1 and Tier 2. . . . . . . . . . APPENDIX A5-41

    A5.602 CALGreen Verification Guidelines Mandatory Measures Checklist . . . . . . . . . . . . . . . APPENDIX A5-44

    A5.602.1 CALGreen Verification Guidelines

    Tier 1 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-48

    A5.602.2 CALGreen Verification Guidelines

    Tier 2 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-55

    APPENDIX A6 VOLUNTARY STANDARDS FOR HEALTH

    FACILITIES [OSHPD 1, 2 & 4] . . . . . . . . . . . APPENDIX A6.1-3 A6.1 Site Planning and Design . . . . . . . . . . . APPENDIX A6.1-3 A6.2 Energy Efficiency . . . . . . . . . . . . . . . . . . APPENDIX A6.1-3 A6.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . APPENDIX A6.1-32 A6.5 Environmental Quality . . . . . . . . . . . . APPENDIX A6.1-33

    INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INDEX-1

    HISTORY NOTE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HIST-1

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE vii

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    viii 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE

    CHAPTER 1 – ADMINISTRATION

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    |Adopting

  • CALGreen § 504.4.5.3 Medium relevance — show source text

    504.4.5.3||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Resilient flooring systems|5.504.4.6||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Resilient flooring: verification of compliance|5.504.4.6.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Thermal insulation|5.504.4.7||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Verification of compliance|5.504.4.8.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Acoustical ceilings and wall panels|5.504.4.8||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Verification of compliance|5.504.4.8.1|||||

    APPENDIX A5-46 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    CHAPTER 5
    DIVISIONS
    Col2 SECTION TITLE CODE
    SECTION
    Y N/A O PLAN SHEET,
    SPEC OR
    ATTACH
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Filters (with exceptions) 5.504.5
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Filters: labeling 5.504.5.1
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Environmental tobacco smoke (ETS) control 5.504.7
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Indoor moisture control 5.505.1
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Outside air delivery 5.506.1
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Carbon dioxide (CO2) monitoring 5.506.2
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Carbon dioxide (CO2) monitoring in classrooms 5.506.3
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Acoustical control (with exception) 5.507.4
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Mandatory Exterior noise transmission, prescriptive method
    (with exceptions)
    5.507.4.
  • CALGreen § 504.4.7.2 Medium relevance — show source text

    504.4.7.2_||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Thermal insulation|5.504.4.7||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Verification of compliance|5.504.4.7.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Tier 1
    Prerequisite|Thermal insulation, Tier 1 (with verification of
    compliance)|A5.504.4.8.1,
    A5.504.4.8.1|||||

    APPENDIX A5-52 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    CHAPTER 5
    DIVISIONS
    Col2 Col3 SECTION TITLE CODE
    SECTION
    Y N O PLAN SHEET,
    SPEC OR
    ATTACH
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    Mandatory Acoustical ceilings and wall panels 5.504.4.8
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    Mandatory Verification of compliance 5.504.4.8.1
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    Mandatory Filters (with exceptions) 5.504.5
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    Mandatory Filters: labeling 5.504.5.1
    (continued)
    DIVISION 5.5
    Environmental
    Quality
    Select One Elective
    (continued)
    **DIVISION 5.
  • CALGreen § 5.5 Medium relevance — show source text

    2||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Composite wood products|5.504.4.5||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Composite wood products: documentation|5.504.4.5.3||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Resilient flooring systems|5.504.4.6||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Resilient flooring: verification of compliance|5.504.4.6.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Tier 1
    Prerequisite|Resilient flooring systems, Tier 1 (with verification of
    compliance)|A5.504.4.7,
    A5.504.4.7.2||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Thermal insulation|5.504.4.7||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Verification of compliance|5.504.4.7.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|DIVISION 5.5
    Environmental
    Quality
    (continued)|Tier 1
    Prerequisite|Thermal insulation, Tier 1 (with verification of
    compliance)|A5.504.4.8.1,
    A5.504.4.8.1|||||

    APPENDIX A5-52 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    CHAPTER 5
    DIVISIONS
    Col2 Col3 SECTION TITLE CODE
    SECTION
    Y N O PLAN SHEET,
    SPEC OR
    ATTACH
    (continued)
    **DIVISION 5.
  • CALGreen § 504.3 Medium relevance — show source text

    504.3||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Adhesives, sealants and caulks|5.504.4.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Paints and coatings|5.504.4.3||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Aerosol paints and coatings|5.504.4.3.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Aerosol paints and coatings: verification|5.504.4.3.2||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Carpet systems|5.504.4.4||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Carpet cushion|5.504.4.4.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Carpet adhesives per Table 5.504.4.1|5.504.4.4.2||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Composite wood products|5.504.4.5||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Composite wood products: documentation|5.504.4.5.3||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Resilient flooring systems|5.504.4.6||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Resilient flooring: verification of compliance|5.504.4.6.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Thermal insulation|5.504.4.7||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Verification of compliance|5.504.4.8.1||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Acoustical ceilings and wall panels|5.504.4.8||||| |DIVISION 5.5
    Environmental
    Quality
    (continued)|Mandatory|Verification of compliance|5.504.4.8.1|||||

    APPENDIX A5-46 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    |CHAPTER 5
    DIVISIONS|Col2|SECTION TITLE|CODE
    SECTION|Y|N/A|O|PLAN SHEET,

  • CALGreen § 8-40 Medium relevance — show source text

    . . . . . . . . . . . . . 8-40

    APPENDIX A4 RESIDENTIAL

    VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A4-3

    A4.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A4-3 A4.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . APPENDIX A4-9 A4.3 Water Efficiency and Conservation . . . APPENDIX A4-13 A4.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A4-15 A4.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A4-19 A4.6 Tier 1 and Tier 2 . . . . . . . . . . . . . . . . . . . . APPENDIX A4-21

    Division A4.6—Residential Occupancies Application Checklist . . . . . . . . . . . . . APPENDIX A4-23 A4.7 Residential Model Ordinance . . . . . . . . . APPENDIX A4-31

    APPENDIX A5 NONRESIDENTIAL

    VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3

    A5.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A5-3 A5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . APPENDIX A5-13 A5.3 Water Efficiency and Conservation . . . APPENDIX A5-19 A5.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-25 A5.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A5-35 A5.6 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-41 A5.601 CALGren Tier 1 and Tier 2. . . . . . . . . . APPENDIX A5-41

    A5.602 CALGreen Verification Guidelines Mandatory Measures Checklist . . . . . . . . . . . . . . . APPENDIX A5-44

    A5.602.1 CALGreen Verification Guidelines

    Tier 1 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-48

    A5.602.2 CALGreen Verification Guidelines

    Tier 2 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-55

    APPENDIX A6 VOLUNTARY STANDARDS FOR HEALTH

  • CALGreen § 304.1 Medium relevance — show source text

    SECTION 304—VOLUNTARY TIERS

    304.1 Purpose. Voluntary tiers are intended to further encourage building practices that improve public health, safety and general welfare by promoting the use of building concepts which minimize the building’s impact on the environment and promote a more sustainable design.

    304.1.1 Tiers. The provisions of Divisions A4.6 and A5.6 outline means, in the form of voluntary tiers, for achieving enhanced construction levels by incorporating additional measures for residential and nonresidential new construction. Voluntary tiers may be adopted by local governments and, when adopted, enforced by local enforcing agencies. Buildings complying with tiers specified for each occupancy contain additional prerequisite and elective green building measures necessary to meet the threshold of each tier. See Section 101.7 of this code for procedures and requirements related to local amendments, additions or deletions, including changes to energy standards.

    [BSC & HCD] Where there are practical difficulties involved in complying with the threshold levels of a tier, the enforcing agency may grant modifications for individual cases. The enforcing agency shall first find that a special individual reason makes the strict letter of the tier impractical and that modification is in conformance with the intent and purpose of the measure. The details of any action granting modification shall be recorded and entered in the files of the enforcing agency.

    SECTION 305 [OSHPD 1]— CALGreen TIER 1 AND CALGreen TIER 2

    305.1 CALGreen Tier 1 and CALGreen Tier 2 buildings contain voluntary green building measures necessary to meet the threshold of each level.

    305.1.1 CALGreen Tier 1. To achieve CALGreen Tier 1, buildings must comply with the latest edition of “Savings By Design, Healthcare Modeling Procedures” found online at http://www.energysoft.com/main/page_ downloads_ sbd_healthcare.html.

    305.1.2 CALGreen Tier 2. To achieve CALGreen Tier 2, buildings must exceed the latest edition of “Savings By Design, Healthcare Modeling Procedures” by a minimum of 15 percent.

    SECTION 306 [DSA-SS]—VOLUNTARY MEASURES

    306.1 Purpose. For public schools and community colleges, voluntary measures further encourage building practices that improve public health, safety and general welfare by promoting the use of building concepts which minimize the building’s impact on the environment and promote a more sustainable design.

    306.1.1 Appendix A5, Divisions A5.1 through A5.5, outline means of achieving enhanced sustainable design and construction by incorporating voluntary measures that exceed the mandatory measures.

    306.1.2 Chapter 5 Nonresidential Mandatory Measures that are not adopted as mandatory measures by DSA-SS are voluntary measures recommended and encouraged for the design, construction, verification and maintenance of non-energy systems.

    Note: The building commissioning requirements for energy efficiency specified in the California Energy Code are required.

    3-4 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE

    CHAPTER 4 – RESIDENTIAL MANDATORY MEASURES

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

  • CALGreen § 601.3.4 Medium relevance — show source text

    A5.601.3.4 Voluntary measures for Tier 2. In addition to the provisions of Sections A5.601.3.1 and A5.601.3.3 above, compliance with the following voluntary measures from Appendix A5 is required for Tier 2:

    1. From Division A5.1, a. Comply with the designated parking requirements for fuel efficient vehicles for a minimum of 50 percent of parking capacity per Section A5.106.5.1. b. Electric vehicle (EV) charging [N] and Table A5.106.5.3.2 with footnotes. c. Comply with thermal emittance, solar reflectance or SRI values for cool roofs in Section A5.106.11.2 and Table A5.106.11.2.3. [1]

    d. Comply with three elective measures selected from this division.

    APPENDIX A5-42 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    1. From Division A5.2 comply with TWO of the following:

    2. Outdoor lighting as described in A5.203.1.1.1.

    3. Service water heating in restaurants as described in A5.203.1.1.2.

    4. Warehouse Dock Seal Doors A5.203.1.1.3.

    5. Daylight Design Power Adjustments 5.203.1.1.4.

    6. Exhaust Air Heat Recovery A5.203.1.1.5.

    7. From Division A5.3,

    a. Comply with the 20-percent reduction for indoor potable water use in Section A5.303.2.3.2. b. Comply with three elective measures selected from this division.

    1. From Division A5.4,

    a. Comply with recycled content of 15 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4.1. b. Comply with the 80-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with three elective measures selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 100 percent of resilient flooring in Section A5.504.4.7.1. Exception: Allowance may be permitted in Tier 2 for up to 5-percent specialty purpose flooring. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list and no added formaldehyde in Section A5.504.4.8.1.

    c. Comply with three elective measures selected from this division. 6. Comply with three additional elective measures selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.4 Compliance verification. Compliance with Section A5.601.2 or A5.601.3 shall be as required in Chapter 7 of this code. Compliance documentation shall be made part of the project record as required in Section 5.410.2 or 5.410.3.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-43

  • CALGreen § 602.1 Medium relevance — show source text

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-39

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5-40 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    A5 NONRESIDENTIAL VOLUNTARY MEASURES

    DIVISION A5.6 – VOLUNTARY TIERS

    SECTION A5.601—CALGreen TIER 1 AND TIER 2 Col2 Col3 Col4
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    CATEGORY ENVIRONMENTAL
    PERFORMANCE GOAL
    TIER 1 TIER 2
    All Minimum Mandatory
    (See Mandatory Checklist)
    Meet all of the provisions
    of Chapter 5 (See Tier 1 Checklist)
    Meet all of the provisions
    of Chapter 5 (See Tier 2 Checklist)
    DIVISION 5.1
    Planning and Design
    Reuse of existing building See Section A5.105.1 and Section
    A5.105.2 requirements
    See Section A5.105.1 and Section
    A5.105.2 requirements
    DIVISION 5.1
    Planning and Design
    Designated Parking for
    Fuel Efficient Vehicles
    (Tier 1 and Tier 2 only)
    Approx. 35% of total spaces Approx. 50% of total spaces
    DIVISION 5.1
    Planning and Design
    Electric Vehicle Charging Approx. 30% of total spaces Approx. 45% of total spaces
    **DIVISION 5.
  • CALGreen § 601.2.4 Medium relevance — show source text

    A5.601.2.4 Voluntary measures for Tier 1. In addition to the provisions of Sections A5.601.2.1 and A5.601.2.3 above, compliance with the following voluntary measures from Appendix A5 is required for Tier 1:

    1. From Division A5.1, a. Comply with the designated parking requirements for high-efficiency vehicles for a minimum of 35 percent of parking capacity per Section A5.106.5.1. b. Electric vehicle (EV) charging [N] and Table A5.106.5.3.1 w/ footnotes. c. Comply with thermal emittance, solar reflectance or SRI values for cool roofs in Section A5.106.11.2 and Table A5.106.11.2.2. [1]

    d. Comply with one elective measure selected from this division. 2. From Division A5.2 comply with ONE of the following:

    1. Outdoor lighting as described in A5.203.1.1.1.

    2. Service water heating in restaurants as described in A5.203.1.1.2.

    3. Warehouse Dock Seal Doors A5.203.1.1.3.

    4. Daylight Design Power Adjustments 5.203.1.1.4.

    5. Exhaust Air Heat Recovery A5.203.1.1.5.

    6. From Division A5.3,

    a. Comply with the 12-percent reduction for indoor potable water use in Section A5.303.2.3.1. b. Comply with one elective measure selected from this division.

    1. From Division A5.4,

    a. Comply with recycled content of 10 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4. b. Comply with the 65-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with one elective measure selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 90 percent of resilient flooring in Section A5.504.4.7. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list in Section A5.504.4.8. c. Comply with one elective measure selected from this division. 6. Comply with one additional elective measure selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.3 CALGreen Tier 2.

    A5.601.3.1 Prerequisites. To achieve CALGreen tier status, a project must meet all of the mandatory measures in Chapter 5 and, in addition, meet the provisions of this section.

    A5.601.3.2 Energy performance. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

    A5.601.3.3 Tier 2. Comply with the energy efficiency requirements in Section A5.203.1.1 and Section A5.203.1.2.2.

  • CALGreen § 405.4 Medium relevance — show source text
    1. From Division A5.4,

    a. Comply with recycled content of 10 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4. b. Comply with the 65-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with one elective measure selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 90 percent of resilient flooring in Section A5.504.4.7. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list in Section A5.504.4.8. c. Comply with one elective measure selected from this division. 6. Comply with one additional elective measure selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.3 CALGreen Tier 2.

    A5.601.3.1 Prerequisites. To achieve CALGreen tier status, a project must meet all of the mandatory measures in Chapter 5 and, in addition, meet the provisions of this section.

    A5.601.3.2 Energy performance. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

    A5.601.3.3 Tier 2. Comply with the energy efficiency requirements in Section A5.203.1.1 and Section A5.203.1.2.2.

    A5.601.3.4 Voluntary measures for Tier 2. In addition to the provisions of Sections A5.601.3.1 and A5.601.3.3 above, compliance with the following voluntary measures from Appendix A5 is required for Tier 2:

    1. From Division A5.1, a. Comply with the designated parking requirements for fuel efficient vehicles for a minimum of 50 percent of parking capacity per Section A5.106.5.1. b. Electric vehicle (EV) charging [N] and Table A5.106.5.3.2 with footnotes. c. Comply with thermal emittance, solar reflectance or SRI values for cool roofs in Section A5.106.11.2 and Table A5.106.11.2.3. [1]

    d. Comply with three elective measures selected from this division.

    APPENDIX A5-42 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    1. From Division A5.2 comply with TWO of the following:

    2. Outdoor lighting as described in A5.203.1.1.1.

    3. Service water heating in restaurants as described in A5.203.1.1.2.

    4. Warehouse Dock Seal Doors A5.203.1.1.3.

    5. Daylight Design Power Adjustments 5.203.1.1.4.

    6. Exhaust Air Heat Recovery A5.203.1.1.5.

    7. From Division A5.3,

  • CALGreen § 508.1.3 Medium relevance — show source text

    SECTION A5.508—OUTDOOR AIR QUALITY

    A5.508.1.3 Hydrochlorofluorocarbons (HCFCs). Install HVAC and refrigeration equipment that do not contain HCFCs.

    A5.508.1.4 Hydrofluorocarbons (HFCs). Install HVAC complying with either of the following:

    1. Install HVAC, refrigeration and fire suppression equipment that do not contain HFCs or that do not contain HFCs with a global warming potential greater than 150.
    2. Install HVAC and refrigeration equipment that limit the use of HFC refrigerant through the use of a secondary heat transfer fluid with a global warming potential no greater than 1.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-37

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5-38 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE

    APPENDIX A5 – NONRESIDENTIAL VOLUNTARY MEASURES

    DIVISION A5.6 – VOLUNTARY TIERS

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    Adopting agency BSC BSC-
    CG
    SFM HCD Col6 Col7 DSA Col9 OSHPD Col11 Col12 Col13 Col14 Col15 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting agency BSC BSC-
    CG
    SFM 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
    Adopt entire CA chapter X
    Adopt entire chapter as
    amended (amended
    sections listed below)
    Adopt only those sections
    that are listed below
    Chapter/Section

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-39

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5-40 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    A5 NONRESIDENTIAL VOLUNTARY MEASURES

    DIVISION A5.6 – VOLUNTARY TIERS

Frequently asked questions

Are Voluntary Tiers mandatory for every project?

No. Tiers in Division A5.6 (CALGreen Tier 1 and Tier 2) are voluntary measures that a local jurisdiction may adopt; projects only must comply when the local enforcing agency has adopted the tier requirements (§304.1 and §A5.601) .

How do I demonstrate compliance for a Tier or A5.5 measure?

Use the CALGreen verification checklists in Appendix A5: the Mandatory Checklist (A5.602) and the Tier 1/Tier 2 Checklists (A5.602.1 and A5.602.2). Required documentation is submitted per the checklists and becomes part of the project record under the code’s Chapter 7 recording/verification rules .

What kinds of environmental‑quality controls are in Division A5.5?

Division A5.5 covers low‑emitting materials (adhesives, sealants, paints, coatings), carpet and resilient flooring requirements and verification, thermal insulation, acoustic performance and refrigerant/HFC limits among other indoor‑environment and material‑quality measures (see §§A5.504.4.1–A5.504.4.8 and §A5.508) .