1308.9 Overpressure Protection Devices.

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Overpressure protection devices shall be one of the following:

(1) Pressure relief valve.

(2) Monitor regulator.

(3) Series regulator installed upstream from the line regulator and set to continuously limit the pressure on the inlet of the line regulator to the maximum values specified by Section 1308.8 or less.

(4) Automatic shutoff device installed in series with the line pressure regulator and set to shut off when the pressure on the downstream piping system reaches the maximum values specified by Section 1308.8 or less. This device shall be designed so that it will remain closed until manually reset. [NFPA 54:5.8.3.1]

1308.9.1 Separate Devices. The devices in Section 1308.9 shall be installed either as an integral part of the service or line pressure regulator or as separate units. Where separate overpressure protection devices are installed, they shall comply with Section 1308.9.2 through Section 1308.9.7. [NFPA 54:5.8.3.2]

1308.9.2 Construction and Installation. All overpressure protection devices shall meet the following requirements:

(1) Be constructed of materials so that the operation of the device is not impaired by corrosion of external parts by the atmosphere or of internal parts by the gas.

(2) Be designed and installed so they can be operated to determine whether the valve is free. The devices shall also be designed and installed so they can be tested to determine the pressure at which they operate and be examined for leakage when in the closed position. [NFPA 54:5.8.4]

1308.9.3 External Control Piping. External control piping shall be designed and installed so that damage to the control piping of one device does not render both the regulator and the overpressure protective device inoperative. [NFPA 54:5.8.5]

1308.9.4 Setting. Each pressure limiting or pressure relieving device shall be set so that the gas pressure supplied to the connected appliance(s) does not exceed the limits specified in Section 1308.8 and Section 1308.8.1.

[NFPA 54:5.8.6]

1308.9.5 Unauthorized Operation. Where unauthorized operation of any shutoff valve could render a pres

«

«

«

«

«

«

FUEL GAS PIPING

TABLE 1308.12

MANUAL GAS VALVE STANDARDS

[NFPA 54: TABLE 5.11]

SHUTOFF VALVE
APPLICATION
STANDARDS




Appliance shutoff
valve up to1_/_2 psi
CSA/ANSI Z21.15/CSA 9.1




Appliance shutoff
valve up to1_/_2 psi
ASME B16.44




Appliance shutoff
valve up to1_/_2 psi
ASME B16.33 marked 125 G




Appliance shutoff
valve up to1_/_2 psi
CSA/ANSI LC 4/CSA 6.32



Valve up to1_/_2 psi
ASME B16.44



Valve up to1_/_2 psi
ASME B16.33 marked 125 G



Valve up to1_/_2 psi
CSA/ANSI LC 4/CSA 6.32






Valve up to 2 psi
ASME B16.44 labeled 2G






Valve up to 2 psi
ASME B16.33 marked 125 G






Valve up to 2 psi
CSA/ANSI LC 4/CSA 6.32 with
ANSI/ASME B16.44 labeled 2G or
labeled 5G






Valve up to 2 psi
CSA/ANSI LC 4/CSA 6.32 with
ANSI/ASME B16.33 marked 125 G






Valve up to 5 psi
ASME B16.44 labeled 5G






Valve up to 5 psi
ASME B16.33






Valve up to 5 psi
CSA/ANSI LC 4/CSA 6.32 with
ANSI/ASME B16.44 marked 5G






Valve up to 5 psi
CSA/ANSI LC 4/CSA 6.32 with
ANSI/ASME B16.33 marked 125 G

Valve up to 125 psi
ASME B16.33 marked 125 G

Valve up to 125 psi
CSA/ANSI LC 4/CSA 6.32 with
ASME B16.33 marked 125 G

For SI Units: 1 pound-force per square inch = 6.8947 kPa

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
    Overview
    1. 1301.1 Applicability. The regulations of this chapter shall
    2. 1302.1 General. Coverage of piping systems shall extend
    3. 1302.2 Piping System Requirements. Requirements for
    4. 1302.3 Applications. This chapter shall not apply to the
    5. 1303.1 Inspection Notification. Upon completion of the
    6. 1303.2 Excavation. Excavations required for the installation o…
    7. 1303.3 Type of Inspections. The Authority Having Jurisdiction …
    8. 1303.4 Inspection Waived. In cases where the work authorized b…
    9. 1304.1 Issuance. Whereupon final piping inspection, the
    10. 1304.2 Gas Supplier. A copy of the certificate of such final
    11. 1304.3 Unlawful. It shall be unlawful for a serving gas suppli…
    12. 1305.1 Authorized Personnel. It shall be unlawful for a
    13. 1305.2 Outlets. It shall be unlawful to turn on or connect gas
    14. 1306.1 Disconnection. The Authority Having Jurisdiction
    15. 1306.2 Notice. Where such disconnection has been made, a
    16. 1306.3 Capped Outlets. It shall be unlawful to remove or
    17. 1307.1 General. Where temporary use of gas is desired, and
    18. 1308.1 Installation of Piping System. Where required
    19. 1308.2 Interconnections Supplying Separate Users.
    20. 1308.3 Sizing of Gas Piping Systems. Gas piping systems shall …
    21. 1308.4 Acceptable Piping Materials and Joining
    22. 1308.5 Gas Meters. Gas meters shall be selected for the
    23. 1308.6 Gas Pressure Regulators. A line pressure regulator shal…
    24. 1308.7 Overpressure Protection. Where the serving gas
    25. 1308.8 Pressure Limitation Requirements. Where piping systems …
    26. 1308.9 Overpressure Protection Devices. Overpressure protectio…
    27. 1308.13 Expansion and Flexibility. Piping systems shall
    28. 1308.14 Pressure Regulator and Pressure Control
    29. 1308.10 Backpressure Protection. Protective devices
    30. 1308.11 Low-Pressure Protection. A protective device
    31. 1308.12 Shutoff Valves. Shutoff valves shall be selected in
    32. 1309.1 General. Where automatic excess flow valves are
    33. 1310.1 Piping Underground. Underground gas piping shall
    34. 1310.2 CSST Piping Systems. CSST piping systems shall
    35. 1310.3 Installation of Aboveground Piping. Piping
    36. 1310.4 Concealed Piping in Buildings. Gas piping in
    37. 1310.5 Piping in Vertical Chases. Where gas piping
    38. 1310.6 Maximum Operating Pressure in Buildings.
    39. 1310.7 Appliance Overpressure Protection. The maximum operatin…
    40. 1310.8 Gas Pipe Turns. Changes in direction of gas pipe
    41. 1310.9 Drips and Sediment Traps. For other than dry gas
    42. 1310.10 Outlets. Outlets shall be located and installed in
    43. 1310.11 Manual Gas Shutoff Valves. An accessible gas
    44. 1310.12 Prohibited Devices. Devices shall not be placed
    45. 1310.13 Systems Containing Gas-Air Mixtures Out-
    46. 1310.14 Systems Containing Flammable Gas-Air
    47. 1311.1 Pipe and Tubing Other than CSST. Each aboveground porti…
    48. 1311.2 Bonding of CSST Gas Piping. CSST gas piping
    49. 1311.3 Arc-Resistant Jacketed CSST. CSST listed with
    50. 1311.4 Prohibited Use. Gas piping shall not be used as a
    51. 1311.5 Lightning Protection System. Where a lightning
    52. 1311.6 Electrical Circuits. Electrical circuits shall not util…
    53. 1311.7 Electrical Connections. All electrical connections
    54. 1312.1 Connecting Appliances and Equipment.
    55. 1312.3 Use of Nonmetallic Gas Hose Connectors.
    56. 1312.4 Injection (Bunsen) Burners. Injection (Bunsen)
    57. 1312.5 Connection of Portable and Mobile Industrial
    58. 1312.2 Suspended Low-Intensity Infrared Tube
    59. 1312.6 Appliance Shutoff Valves and Connections.
    60. 1312.7 Quick-Disconnect Devices. Quick-disconnect
    61. 1312.8 Gas Convenience Outlets. Appliances shall be
    62. 1312.9 Sediment Trap. Where a sediment trap is not incorporate…
    63. 1312.10 Installation of Piping. Piping shall be installed in
    64. 1312.11 Liquefied Petroleum Gas (LP-Gas) Facilities
    65. 1313.1 Piping Installations. Prior to acceptance and initial o…
    66. 1313.2 Test Preparation. Test preparation shall comply
    67. 1313.3 Test Pressure. This inspection shall include an air,
    68. 1313.4 Detection of Leaks and Defects. The piping system shall…
    69. 1313.5 Piping System Leak Test. Leak checks using fuel
    70. 1313.6 Purging Requirements. The purging of piping
    71. 1314.1 General. The following regulations, shall comply
    72. 1314.2 Volume. The hourly volume of gas required at each
    73. 1314.3 Gas Appliances. Where the gas appliances to be
    74. 1314.4 Size of Piping Outlets. The size of the supply piping o…
    75. 1315.1 Pipe Sizing Methods. Where the pipe size is to be
    76. 1315.2 Sizing of Gas Piping Systems. Sizing of piping
    77. 1315.3 Sizing Equations. The inside diameter of smooth
    78. 1315.4 Sizing of Piping Sections. To determine the size
    79. 1315.5 Engineering Methods. For conditions other than
    80. 1315.6 Variable Gas Pressures. Where the supply gas
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
  18. Chapter 18 — REFERENCED STANDARDS
  19. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  20. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  21. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  22. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  23. Appendix E — SUSTAINABLE PRACTICES
  24. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
  26. Appendix H — PROFESSIONAL QUALIFICATIONS
  27. Appendix I — INDOOR HORTICULTURAL FACILITIES
  28. Appendix J — CLEAN AIR DELIVERY

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.