What are CALGreen Tier 1 and Tier 2 energy performance requirements for health facilities?

For health facilities: CALGreen **Tier 1** means follow the Savings By Design healthcare modeling procedures; **Tier 2** means meet that same method and achieve at least a **15%** better modeled energy performance (use the Savings By Design procedures for the baseline and calculation).

Last reviewed: July 6, 2026

What the code requires — 2-4 sentences

  • Voluntary green-building Tier 1 for health facilities requires compliance with the latest edition of the "Savings By Design, Healthcare Modeling Procedures" (the procedures establish the modeling approach and target). See § A6.203.2.1.
  • Tier 2 requires the project to exceed the same Savings By Design healthcare modeling procedures by a minimum of 15 percent. See § A6.203.2.2.

The essential rule: follow the Savings By Design healthcare modeling procedures to establish the energy performance target (Tier 1); to reach Tier 2 you must beat that target by at least 15% as measured using the Savings By Design procedures.

Requirements in detail

Key definitions and controlling sections

  • Savings By Design, Healthcare Modeling Procedures — the referenced document and the method for modeling and measuring compliance (required for Tier 1 and the baseline for Tier 2). § A6.203.2.1.
  • 15% — the mandatory minimum improvement threshold for Tier 2 relative to the Savings By Design modeled target. § A6.203.2.2.

Decision‑relevant table

Tier What the project must do Key threshold / dimension Verification source Code Reference
Tier 1 Comply with the latest "Savings By Design, Healthcare Modeling Procedures" Meet the SBD healthcare modeled performance (follow SBD method) Project energy model & documentation per SBD procedures § A6.203.2.1
Tier 2 Exceed the latest SBD healthcare modeled performance by a minimum amount Minimum 15% improvement over the SBD-modeled target Project energy model showing ≥15% improvement per SBD method § A6.203.2.2
Both tiers (context) Tiers are voluntary measures for health facilities (appendix/voluntary tiers) Tiers apply where adopted; certain voluntary measures (e.g., cool roof) may be required for tier compliance Appendix A6 / Appendix A5 voluntary tier checklists See § 305.1.1, § 305.1.2 and related Appendix sections

What "comply" and "exceed by 15%" mean in practice

  • The CALGreen text points you to the Savings By Design procedures for the modeling rules and baseline definitions — CALGreen does not restate the modeling methodology; it requires you to use that external procedures document as the compliance method. § A6.203.2.1.
  • For Tier 2 the code text requires a quantifiable 15% improvement relative to whatever metric and baseline the Savings By Design healthcare procedures establish (energy use, energy cost, or other modeling metric as defined in SBD). The code does not redefine the metric; use the SBD procedures to calculate the percent improvement. § A6.203.2.2.

Exceptions & special cases

  • These tier measures are part of the voluntary tiers structure; local adoption/authority can affect whether tiers are enforced for a project. See the voluntary tiers overview and adoption notes in the CALGreen text.
  • The CALGreen excerpts provided do not include additional sector-specific exceptions for health facilities to modify the 15% requirement; where the code text defers to the Savings By Design procedures for modeling details, follow those procedures for baseline, metric, and any allowable tradeoffs. § A6.203.2.1 and § A6.203.2.2.
  • Some other voluntary-tier prerequisites (e.g., cool roof requirements) are noted elsewhere in the voluntary appendices and may be required to achieve Tier 1 or Tier 2 status; check the applicable Appendix Tier checklists.

Common mistakes

  • Mistaking "comply with SBD" (Tier 1) for "15% better than code" — Tier 1 requires meeting the Savings By Design healthcare modeling procedures, not simply meeting Title 24 or another baseline. § A6.203.2.1.
  • Interpreting "15%" without consulting the SBD procedures — CALGreen's § A6.203.2.2 specifies a 15% improvement relative to the SBD procedure result, so you must use SBD's modeling rules to determine the baseline and metric. Do not apply an ad‑hoc metric.
  • Forgetting verification/documentation: the project energy model must follow the SBD method and be documented in the construction documents per CALGreen verification guidance (see the Appendix checklists).

Worked example — concrete scenario

Assumptions (for illustration only — follow SBD modeling rules to calculate your actual baseline and metrics):

  • Savings By Design (SBD) healthcare modeling produces a modeled annual site energy use of 1,000,000 kWh for the SBD baseline/target for this project (this is the SBD-modeled target the project must meet to comply with Tier 1). Under § A6.203.2.1 you would document that your project model meets the SBD procedures' performance.

Tier 1:

  • Action: Demonstrate via the SBD-method model that projected performance equals the SBD target (1,000,000 kWh). Result: Tier 1 achieved per § A6.203.2.1.

Tier 2:

  • Requirement: Achieve at least 15% improvement over the SBD-modeled target per § A6.203.2.2.
  • Calculation (example): 15% of 1,000,000 kWh = 150,000 kWh. Tier 2 target = 1,000,000 − 150,000 = 850,000 kWh.
  • Action: Provide an energy model, prepared per the SBD healthcare modeling procedures, showing projected annual energy use ≤ 850,000 kWh and submit documentation per the CALGreen verification checklist. Result: Tier 2 achieved.

Note: The code text directs you to the SBD procedures for how to define the baseline and measure the percent improvement. Use the SBD procedures to confirm whether the percent is applied to energy use, energy cost, or another metric in your project's modeling context. § A6.203.2.1 and § A6.203.2.2.

Related provisions (select)

  • § A6.203.2.1 — CALGreen Tier 1: comply with Savings By Design healthcare modeling procedures.
  • § A6.203.2.2 — CALGreen Tier 2: exceed SBD healthcare modeling procedures by 15%.
  • § A6.203.2 — Energy performance intent and scope (parent section).
  • § A6.204.4 — Commissioning requirements (commissioning is required for energy-related systems and supports verification).
  • § 305.1.1 and § 305.1.2 — CALGreen Tier 1 and Tier 2 statements in the voluntary tiers chapter that reinforce the Appendix A6 language and link to SBD procedures.
  • Appendix A5 / A5.601 — nonresidential voluntary tier context and Tier checklists (verification guidance).

Code references

Grounded in the retrieved California Green Building Standards Code (CALGreen) — click a citation to read the verbatim passage:

  • CALGreen § 203.2 High relevance — show source text

    SECTION A6.203—PERFORMANCE APPROACH

    A6.203.2 Energy performance. It is the intent of this code to encourage green buildings to achieve exemplary performance in the area of energy efficiency.

    A6.203.2.1 CALGreen Tier 1. [OSHPD 1] To achieve CALGreen [Tier 1, buildings must comply with the latest edition of “Savings By](http://www.energysoft.com/ep/ 2007SBDHProcedures.pdf) Design, Healthcare Modeling Procedures” found online at http://www.energysoft.com/ep/ 2007SBDHProcedures.pdf.

    A6.203.2.2 CALGreen Tier 2. [OSHPD 1] To achieve CALGreen Tier 2, buildings must exceed the latest edition of “Savings By Design, Healthcare Modeling Procedures” by a minimum of 15 percent.

    SECTION A6.204—PRESCRIPTIVE APPROACH

    A6.204.1 ENERGY STAR equipment and appliances. All equipment and appliances provided by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment or appliance.

    A6.204.4 Commissioning. [OSHPD 1 & 4] Building commissioning shall be included in the design and construction processes of the building project to verify that the building’s energy related systems are installed, calibrated and perform according to the owner’s project requirements, basis of design and construction documents.

    The owner and designer shall designate an individual as the Commissioning Authority (CxA) to lead, review and oversee the completion of the commissioning process activities. The owner shall document the Owner’s Project Requirements (OPR). The design team shall develop the Basis of Design (BOD). The CxA shall review these documents for clarity and completeness. The owner and design team shall be responsible for updates to their respective documents, develop and incorporate commissioning requirements into the construction documents and develop and implement a commissioning plan. The CxA shall verify the installation and performance of the systems to be commissioned, verify that training and operation and maintenance documentation have been provided to the owner’s operations staff and complete a commissioning report.

    Commissioning process activities shall be completed for the following energy-related systems, at a minimum:

    1. Heating, ventilating, air conditioning and refrigeration (HVAC&R) systems (mechanical and passive) and associated controls.
    2. Lighting and daylighting controls.
    3. Domestic hot water systems.
    4. Renewable energy systems (wind, solar, etc.).
    5. Building envelope systems.

    A6.204.4.1 Owner’s Project Requirements (OPR). The expectations and requirements of the building shall be documented by the owner and the designer before the design phase of the project begins. This shall be reviewed by the CxA. At a minimum, this documentation shall include the following:

    1. Environmental and sustainability goals.
    2. Energy efficiency goals.
    3. Indoor environmental quality requirements.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A6.1-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A6.1VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

    1. Equipment and systems expectations.
    2. Building occupant and O&M personnel expectations.
  • CALGreen § 1-1 High relevance — show source text

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A6.1-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A6.1-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    A6 VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

    DIVISION A6.1 – SITE PLANNING AND DESIGN

    SECTION A6.106—SITE DEVELOPMENT

    A6.106.9 Building orientation. Locate and orient the building as follows:

    1. When site and location permit, orient the building with the long sides facing north and south.
    2. Protect the building from thermal loss, drafts and degradation of the building envelope caused by wind and wind-driven materials such as dust, sand, snow and leaves, with building orientation and landscape features. Note: For information on sun angles and shading, visit: http://www2.aud.ucla.edu/energy-design-tools/.

    Calculations may be made using the Solar-2 tool.

    DIVISION A6.2 – ENERGY EFFICIENCY

    SECTION A6.202—DEFINITIONS

    A6.202.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.

    ENERGY STAR. A joint program of the US Environmental Protection Agency and the US Department of Energy. ENERGY STAR is a voluntary program designed to identify and promote energy-efficient products and practices.

    SECTION A6.203—PERFORMANCE APPROACH

    A6.203.2 Energy performance. It is the intent of this code to encourage green buildings to achieve exemplary performance in the area of energy efficiency.

    A6.203.2.1 CALGreen Tier 1. [OSHPD 1] To achieve CALGreen [Tier 1, buildings must comply with the latest edition of “Savings By](http://www.energysoft.com/ep/ 2007SBDHProcedures.pdf) Design, Healthcare Modeling Procedures” found online at http://www.energysoft.com/ep/ 2007SBDHProcedures.pdf.

    A6.203.2.2 CALGreen Tier 2. [OSHPD 1] To achieve CALGreen Tier 2, buildings must exceed the latest edition of “Savings By Design, Healthcare Modeling Procedures” by a minimum of 15 percent.

    SECTION A6.204—PRESCRIPTIVE APPROACH

    A6.204.1 ENERGY STAR equipment and appliances. All equipment and appliances provided by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment or appliance.

    A6.204.4 Commissioning. [OSHPD 1 & 4] Building commissioning shall be included in the design and construction processes of the building project to verify that the building’s energy related systems are installed, calibrated and perform according to the owner’s project requirements, basis of design and construction documents.

    The owner and designer shall designate an individual as the Commissioning Authority (CxA) to lead, review and oversee the completion of the commissioning process activities. The owner shall document the Owner’s Project Requirements (OPR).

  • CALGreen § 5.105.2 High relevance — show source text

    Exception: Combined addition(s) to existing building(s) of two times the area or more of the existing building(s) is not eligible to meet compliance with Section 5.105.2 or Section A5.105.2.

    A5.409.2 Whole building life cycle assessment. Projects shall meet the minimum requirements of Section A5.409.2 for Tier 1 or Tier 2 compliance.

    A5.409.2.1 Tier 1. Projects shall conduct a cradle-to-grave whole building life cycle assessment meeting the requirements of Section 5.409.2 and performed in accordance with ISO 14040 and 14044, excluding operating energy, demonstrating a minimum 15-percent reduction in global warming potential (GWP) as compared to a reference baseline building of similar size, function, complexity, type of construction, material specification, and location that meets the requirements of all parts of the California Building Standards Code currently in effect. Software used to conduct the whole building life cycle assessment, including reference baseline building, shall have a data set compliant with ISO 14044, and ISO 21930 or EN 15804, and the software shall conform to ISO 21931 and/or EN 15978. The software tools and data sets shall be the same for evaluation of both the baseline building and the proposed building.

    Exception: For projects that include building reuse, the reference baseline building shall exclude the reused elements. The percent reduction in GWP shall be achieved through the design and construction of new project elements.

    A5.409.2.2 Tier 2. Projects shall conduct a cradle-to-grave whole building life cycle assessment meeting the requirements of Section 5.409.2 and performed in accordance with ISO 14040 and ISO 14044, excluding operating energy, demonstrating a minimum 20-percent reduction in GWP as compared to a reference baseline building of similar size, function, complexity, type of construction, material specification, and location that meets the requirements of all parts of the California Building Standards Code currently in effect. Software used to conduct the whole building life cycle assessment, including reference baseline building, shall have a data set compliant with ISO 14044, and ISO 21930 or EN 15804, and the software shall conform to ISO 21931 and/or EN 15978. The software tools and data sets shall be the same for evaluation of both the baseline building and the proposed building.

    Exception: For projects that include building reuse, the reference baseline building shall not be of new construction and shall retain existing materials. The percent reduction in GWP shall be achieved through the design and construction of new project elements.

    A5.409.2.3 Verification of compliance. A summary of the GWP analysis produced by the software and Worksheet WS-7 signed by the design professional of record shall be provided in the construction documents as documentation of compliance. A copy of the whole building life cycle assessment which includes the GWP analysis produced by the software, in addition to maintenance and training information, shall be included in the operation and maintenance manual and shall be provided to the owner at the close of construction. The enforcing agency may require inspection and inspection reports in accordance with Sections 702.2 and 703.1 during and at completion of construction to demonstrate substantial conformance. Inspection shall be performed by the design professional of record or third party acceptable to the enforcing agency.

    A5.409.3 Product GWP compliance—prescriptive path. Each product that is permanently installed and listed in Table A5.409.3 shall have a Type III environmental product declaration (EPD), either product-specific or factory-specific.

  • CALGreen § 405.4 High relevance — show source text
    1. From Division A5.4,

    a. Comply with recycled content of 10 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4. b. Comply with the 65-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with one elective measure selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 90 percent of resilient flooring in Section A5.504.4.7. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list in Section A5.504.4.8. c. Comply with one elective measure selected from this division. 6. Comply with one additional elective measure selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.3 CALGreen Tier 2.

    A5.601.3.1 Prerequisites. To achieve CALGreen tier status, a project must meet all of the mandatory measures in Chapter 5 and, in addition, meet the provisions of this section.

    A5.601.3.2 Energy performance. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

    A5.601.3.3 Tier 2. Comply with the energy efficiency requirements in Section A5.203.1.1 and Section A5.203.1.2.2.

    A5.601.3.4 Voluntary measures for Tier 2. In addition to the provisions of Sections A5.601.3.1 and A5.601.3.3 above, compliance with the following voluntary measures from Appendix A5 is required for Tier 2:

    1. From Division A5.1, a. Comply with the designated parking requirements for fuel efficient vehicles for a minimum of 50 percent of parking capacity per Section A5.106.5.1. b. Electric vehicle (EV) charging [N] and Table A5.106.5.3.2 with footnotes. c. Comply with thermal emittance, solar reflectance or SRI values for cool roofs in Section A5.106.11.2 and Table A5.106.11.2.3. [1]

    d. Comply with three elective measures selected from this division.

    APPENDIX A5-42 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    1. From Division A5.2 comply with TWO of the following:

    2. Outdoor lighting as described in A5.203.1.1.1.

    3. Service water heating in restaurants as described in A5.203.1.1.2.

    4. Warehouse Dock Seal Doors A5.203.1.1.3.

    5. Daylight Design Power Adjustments 5.203.1.1.4.

    6. Exhaust Air Heat Recovery A5.203.1.1.5.

    7. From Division A5.3,

  • CALGreen § 304.1 High relevance — show source text

    SECTION 304—VOLUNTARY TIERS

    304.1 Purpose. Voluntary tiers are intended to further encourage building practices that improve public health, safety and general welfare by promoting the use of building concepts which minimize the building’s impact on the environment and promote a more sustainable design.

    304.1.1 Tiers. The provisions of Divisions A4.6 and A5.6 outline means, in the form of voluntary tiers, for achieving enhanced construction levels by incorporating additional measures for residential and nonresidential new construction. Voluntary tiers may be adopted by local governments and, when adopted, enforced by local enforcing agencies. Buildings complying with tiers specified for each occupancy contain additional prerequisite and elective green building measures necessary to meet the threshold of each tier. See Section 101.7 of this code for procedures and requirements related to local amendments, additions or deletions, including changes to energy standards.

    [BSC & HCD] Where there are practical difficulties involved in complying with the threshold levels of a tier, the enforcing agency may grant modifications for individual cases. The enforcing agency shall first find that a special individual reason makes the strict letter of the tier impractical and that modification is in conformance with the intent and purpose of the measure. The details of any action granting modification shall be recorded and entered in the files of the enforcing agency.

    SECTION 305 [OSHPD 1]— CALGreen TIER 1 AND CALGreen TIER 2

    305.1 CALGreen Tier 1 and CALGreen Tier 2 buildings contain voluntary green building measures necessary to meet the threshold of each level.

    305.1.1 CALGreen Tier 1. To achieve CALGreen Tier 1, buildings must comply with the latest edition of “Savings By Design, Healthcare Modeling Procedures” found online at http://www.energysoft.com/main/page_ downloads_ sbd_healthcare.html.

    305.1.2 CALGreen Tier 2. To achieve CALGreen Tier 2, buildings must exceed the latest edition of “Savings By Design, Healthcare Modeling Procedures” by a minimum of 15 percent.

    SECTION 306 [DSA-SS]—VOLUNTARY MEASURES

    306.1 Purpose. For public schools and community colleges, voluntary measures further encourage building practices that improve public health, safety and general welfare by promoting the use of building concepts which minimize the building’s impact on the environment and promote a more sustainable design.

    306.1.1 Appendix A5, Divisions A5.1 through A5.5, outline means of achieving enhanced sustainable design and construction by incorporating voluntary measures that exceed the mandatory measures.

    306.1.2 Chapter 5 Nonresidential Mandatory Measures that are not adopted as mandatory measures by DSA-SS are voluntary measures recommended and encouraged for the design, construction, verification and maintenance of non-energy systems.

    Note: The building commissioning requirements for energy efficiency specified in the California Energy Code are required.

    3-4 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE

    CHAPTER 4 – RESIDENTIAL MANDATORY MEASURES

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

  • CALGreen § 601.2.4 High relevance — show source text

    A5.601.2.4 Voluntary measures for Tier 1. In addition to the provisions of Sections A5.601.2.1 and A5.601.2.3 above, compliance with the following voluntary measures from Appendix A5 is required for Tier 1:

    1. From Division A5.1, a. Comply with the designated parking requirements for high-efficiency vehicles for a minimum of 35 percent of parking capacity per Section A5.106.5.1. b. Electric vehicle (EV) charging [N] and Table A5.106.5.3.1 w/ footnotes. c. Comply with thermal emittance, solar reflectance or SRI values for cool roofs in Section A5.106.11.2 and Table A5.106.11.2.2. [1]

    d. Comply with one elective measure selected from this division. 2. From Division A5.2 comply with ONE of the following:

    1. Outdoor lighting as described in A5.203.1.1.1.

    2. Service water heating in restaurants as described in A5.203.1.1.2.

    3. Warehouse Dock Seal Doors A5.203.1.1.3.

    4. Daylight Design Power Adjustments 5.203.1.1.4.

    5. Exhaust Air Heat Recovery A5.203.1.1.5.

    6. From Division A5.3,

    a. Comply with the 12-percent reduction for indoor potable water use in Section A5.303.2.3.1. b. Comply with one elective measure selected from this division.

    1. From Division A5.4,

    a. Comply with recycled content of 10 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4. b. Comply with the 65-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with one elective measure selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 90 percent of resilient flooring in Section A5.504.4.7. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list in Section A5.504.4.8. c. Comply with one elective measure selected from this division. 6. Comply with one additional elective measure selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.3 CALGreen Tier 2.

    A5.601.3.1 Prerequisites. To achieve CALGreen tier status, a project must meet all of the mandatory measures in Chapter 5 and, in addition, meet the provisions of this section.

    A5.601.3.2 Energy performance. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

    A5.601.3.3 Tier 2. Comply with the energy efficiency requirements in Section A5.203.1.1 and Section A5.203.1.2.2.

  • CALGreen § 203.1.1 High relevance — show source text

    [OSHPD 1]**
    **A6.203.1.1 CALGreen Tier 1. [OSHPD 1]**Buildings must comply with the latest edition of
    “Savings By Design, Healthcare Modeling Procedures.”
    A.5.203.1.2 CALGreen Tier 2. [OSHPD 1] Buildings must exceed the latest edition of “Savings
    By Design, Healthcare Modeling Procedures” by 15 percent.||||| |SECTION A6.204 Prescriptive Measures||||| |**A6.204.1 ENERGY STAR equipment and appliances.**All equipment and appliances provided
    by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment
    or appliance.||||| |A6.204.4 Commissioning. Building commissioning for all building systems covered by T24,
    Part 6, process systems and renewable energy systems shall be included in the design and
    construction processes of the building project. Commissioning requirements shall include as
    a minimum items listed in Section A6.204.4.
    **A6.204.4.1 Owner’s Project Requirements (OPR).**Documented before the design phase of
    the project begins the OPR shall include items listed in Section A6.204.4.
    **A6.204.4.2 Basis of Design (BOD).**A written explanation of how the design of the building
    systems meets the OPR shall be completed at the design phase of the building project and
    updated periodically to cover the systems listed in Section A6.204.4.2.
    **A6.204.4.3 Commissioning plan.**A commissioning plan describing how the project will be
    commissioned shall be started during the design phase of the building project and shall
    include as a minimum items listed in Section A6.204.4.3.
    A6.204.4.4 Functional performance testingshall demonstrate the correct installation and
    operation of each component, system and system-to-system interface in accordance with
    the approved plans and specifications.
    **A6.204.4.5 Post construction documentation and training.**A systems manual and
    systems operations training are required.
    **A6.204.4.5.1 Systems manual.**The systems manual shall be delivered to the building
    owner and facilities operator and shall include the items listed in Section A6.204.4.5.1.
    A6.204.4.5.2 Systems operations training. The training of the appropriate maintenance
    staff for each equipment type and/or system shall include as a minimum items listed in
    Section A6.204.4.5.2.
    **A6.204.4.6 Commissioning report.**A complete report of commissioning process activities
    undertaken through the design, construction and postconstruction phases of the building
    project shall be completed and provided to the owner.||







    |







    || |**A6.204.6 Building orientation and shading.

  • CALGreen § 106.9 High relevance — show source text
    FEATURE OR MEASURE COMPLIANCE LEVELS Col3 Col4 NOTES
    FEATURE OR MEASURE Mandatory
    CALGreen
    VOLUNTARY
    CALGreen
    VOLUNTARY
    CALGreen
    VOLUNTARY
    CALGreen
    FEATURE OR MEASURE Mandatory
    CALGreen
    Tier 1 Tier 2 Tier 2
    DIVISION A6.1 – PLANNING AND DESIGN
    SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development
    **A6.106.9 Building orientation.**Locate and orient the building as follows:
    1. When site and location permit, orient the building with the long sides facing north and
    south.
    2. Protect the building from thermal loss, drafts and degradation of the building envelope
    caused by wind and wind-driven materials such as dust.
    DIVISION A6.2 – ENERGY EFFICIENCY
    SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures
    A6.203.1 Energy performance. [OSHPD 1]
    **A6.203.1.1 CALGreen Tier 1. [OSHPD 1]**Buildings must comply with the latest edition of
    “Savings By Design, Healthcare Modeling Procedures.”
    A.5.203.1.2 CALGreen Tier 2. [OSHPD 1] Buildings must exceed the latest edition of “Savings
    By Design, Healthcare Modeling Procedures” by 15 percent.
    SECTION A6.204 Prescriptive Measures
    **A6.204.1 ENERGY STAR equipment and appliances.**All equipment and appliances provided
    by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment
    or appliance.
    A6.204.4 Commissioning. Building commissioning for all building systems covered by T24,
    Part 6, process systems and renewable energy systems shall be included in the design and
    construction processes of the building project. Commissioning requirements shall include as
    a minimum items listed in Section A6.204.4.
    **A6.204.4.1 Owner’s Project Requirements (OPR).**Documented before the design phase of
    the project begins the OPR shall include items listed in Section A6.204.4.
    **A6.204.4.2 Basis of Design (BOD).**A written explanation of how the design of the building
    systems meets the OPR shall be completed at the design phase of the building project and
    updated periodically to cover the systems listed in Section A6.204.4.2.
    **A6.204.4.3 Commissioning plan.
  • CALGreen § 305.1.2 High relevance — show source text

    305.1.2 CALGreen Tier 2. To achieve CALGreen Tier 2, buildings must exceed the latest edition of “Savings By Design, Healthcare Modeling Procedures” by a minimum of 15 percent.

    SECTION 306 [DSA-SS]—VOLUNTARY MEASURES

    306.1 Purpose. For public schools and community colleges, voluntary measures further encourage building practices that improve public health, safety and general welfare by promoting the use of building concepts which minimize the building’s impact on the environment and promote a more sustainable design.

    306.1.1 Appendix A5, Divisions A5.1 through A5.5, outline means of achieving enhanced sustainable design and construction by incorporating voluntary measures that exceed the mandatory measures.

    306.1.2 Chapter 5 Nonresidential Mandatory Measures that are not adopted as mandatory measures by DSA-SS are voluntary measures recommended and encouraged for the design, construction, verification and maintenance of non-energy systems.

    Note: The building commissioning requirements for energy efficiency specified in the California Energy Code are required.

    3-4 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE

    CHAPTER 4 – RESIDENTIAL MANDATORY MEASURES

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    Adopting agency BSC BSC-
    CG
    SFM HCD Col6 Col7 DSA Col9 OSHPD Col11 Col12 Col13 Col14 Col15 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting agency BSC BSC-
    CG
    SFM 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
    Adopt entire CA chapter X
    Adopt entire chapter as
    amended (amended
    sections listed below)
    Adopt only those sections
    that are listed below
    X
    Chapter/Section
    Division 4.2 X

    The state agency does not adopt sections identified by the following symbol: †.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 4-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    4-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

  • CALGreen § 602.1 Medium relevance — show source text

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-39

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5-40 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    A5 NONRESIDENTIAL VOLUNTARY MEASURES

    DIVISION A5.6 – VOLUNTARY TIERS

    SECTION A5.601—CALGreen TIER 1 AND TIER 2 Col2 Col3 Col4
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    CATEGORY ENVIRONMENTAL
    PERFORMANCE GOAL
    TIER 1 TIER 2
    All Minimum Mandatory
    (See Mandatory Checklist)
    Meet all of the provisions
    of Chapter 5 (See Tier 1 Checklist)
    Meet all of the provisions
    of Chapter 5 (See Tier 2 Checklist)
    DIVISION 5.1
    Planning and Design
    Reuse of existing building See Section A5.105.1 and Section
    A5.105.2 requirements
    See Section A5.105.1 and Section
    A5.105.2 requirements
    DIVISION 5.1
    Planning and Design
    Designated Parking for
    Fuel Efficient Vehicles
    (Tier 1 and Tier 2 only)
    Approx. 35% of total spaces Approx. 50% of total spaces
    DIVISION 5.1
    Planning and Design
    Electric Vehicle Charging Approx. 30% of total spaces Approx. 45% of total spaces
    **DIVISION 5.
  • CALGreen § 301.1 Medium relevance — show source text

    Voluntary Measures 301.1, 306 Voluntary Tiers 304, 305, 306, A4.601, A5.601

    Water Resistance and Moisture Management 5.407, 5.505, A4.407, Appendix A6.1 (OSHPD) A5.407 Moisture control 4.505, 5.407.2, 5.505, Appendix A6.1 (OSHPD) A5.407.9, Appendix A6.1 (OSHPD) A5.505.2 Weather protection 5.407.1, A5.407.3

    Water Reuse Systems A4.305 Graywater A4.305.1, A5.304.8 Recycled water for landscape irrigation A4.305.3 Recycled water piping A4.305.2 Water Use, Indoor 4.303, 5.303, A4.303, A5.203

    Appliances A4.303.3, A5.303.3, Appendix A6.1 (OSHPD) A5.210 Dual plumbing A5.303.5 Fixture flow rates 4.303.1, Table A5.303.2.3.1, 5.303.2.3.1, A4.303 Kitchen faucets and dishwashers

    A4.303.1

    Meters 4.303.2, 5.303.1 Multiple showerheads serving one shower 4.303.1.3.2, 5.303.3.3.2 Nonwater urinals and waterless toilets

    A4.303.4, A5.303.4.1 Plumbing fixtures and fittings 4.303.1, 4.303.2, 5.303.3, 5.303.6 Tier 1, 12% savings; Tier 2, 20% savings; and 25% savings A5.303.2.1, A5.303.2.3.1, A5.303.2.3.2,

    A5.303.2.3.3

    Wastewater reduction 5.303.4

    Water Use Baseline Table A5.303.2.2

    Water Use, Outdoor 4.304, 5.304, A4.304, A5.304

    Graywater irrigation system A5.304.8 Low-water consumption irrigation system A4.304.1 Outdoor potable water meters A4.304.3, A5.304.2 Potable water elimination A4.304.2 Previously developed sites A5.304.7 Rainwater or stormwater collection systems A4.304.1 Restoration of areas disturbed by construction A5.304.6 Worksheet Baseline Water Use Chapter 8, (WS-1) 12%, 20% or 25% Reduction Water Use Calculation Table Chapter 8, (WS-2) Building Reuse Chapter 8, (WS-3) Whole Building Life Cycle Assessment 5.409.2, Chapter 8, (WS-4) Product GWP Compliance— Prescriptive Path 5.409.3, Chapter 8, (WS-5) Building Reuse Tier 1 and Tier 2 Chapter 8, (WS-6) Whole Building Life Cycle Assessment A5.409.2, Chapter 8, (WS-7) Product GWP Compliance— Prescriptive Path A5.409.3,

  • CALGreen § 602.1 Medium relevance — show source text

    )_|TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)| |CATEGORY|ENVIRONMENTAL
    PERFORMANCE GOAL|TIER 1|TIER 2| |All|Minimum Mandatory
    (See Mandatory Checklist)|Meet all of the provisions
    of Chapter 5 (See Tier 1 Checklist)|Meet all of the provisions
    of Chapter 5 (See Tier 2 Checklist)| |DIVISION 5.1
    Planning and Design|Reuse of existing building|See Section A5.105.1 and Section
    A5.105.2 requirements|See Section A5.105.1 and Section
    A5.105.2 requirements| |DIVISION 5.1
    Planning and Design|Designated Parking for
    Fuel Efficient Vehicles
    (Tier 1 and Tier 2 only)|Approx. 35% of total spaces|Approx. 50% of total spaces| |DIVISION 5.1
    Planning and Design|Electric Vehicle Charging|Approx. 30% of total spaces|Approx. 45% of total spaces| |DIVISION 5.1
    Planning and Design|Cool Roof to Reduce
    Heat Island Effect|Roof Slope < 2:12 SRI 75
    Roof Slope > 2:12 SRI 16|Roof Slope < 2:12 SRI 82
    Roof Slope > 2:12 SRI 27| |DIVISION 5.1
    Planning and Design||1 additional Elective from Division A5.1|3 additional Electives from Division A5.1| |DIVISION 5.2
    Energy Efficiency|Energy Performance2a, 2b|Outdoor lighting power 90%
    of Part 6 allowance|Outdoor lighting power 90%
    of Part 6 allowance| |||If applicable, solar water-heating system
    with minimum solar savings fraction of 0.15|If applicable, solar water-heating system
    with minimum solar savings fraction of 0.15| |||Warehouse door seals|Warehouse door seals| |||Comply with day lighting requirements|Comply with day lighting requirements| |||Exhaust heat recovery|Exhaust heat recovery| |||Energy Budget 95% or 90%
    of Part 6 calculated value of allowance|Energy Budget 90% or 85%
    of Part 6 calculated value of allowance| |DIVISION 5.3
    Water Efficiency
    and Conservation|Indoor Water Use|12% Savings|20% Savings| |DIVISION 5.3
    Water Efficiency
    and Conservation||1 additional Elective from Division A5.3|3 additional Electives from Division A5.3| |DIVISION 5.4
    Material Conservation
    and Resource Efficiency3|Construction Waste Reduction|At least 65% reduction|At least 80% reduction| |**DIVISION 5.

Frequently asked questions

What document defines how to model and verify Tier 1 and Tier 2 performance?

The CALGreen text requires use of the latest edition of the "Savings By Design, Healthcare Modeling Procedures" for both Tier 1 (comply) and Tier 2 (baseline and percent improvement). § A6.203.2.1 and § A6.203.2.2.

Does "15% improvement" mean 15% better than Title 24?

No — the code requires 15% better than the Savings By Design healthcare modeling result, not necessarily Title 24. Use the SBD procedures referenced in § A6.203.2.2 to determine the applicable baseline and metric.

Are Tiers mandatory for health facilities?

No — Tier 1 and Tier 2 are voluntary tiers in CALGreen; whether they apply depends on local adoption/enforcement and project goals. See the voluntary tiers discussion and adoption notes.

Is additional documentation required to prove compliance?

Yes — provide the energy model and documentation prepared per the Savings By Design procedures and the applicable CALGreen verification checklists (see Appendix Tier checklists). Commissioning and construction‑document submittals are also referenced elsewhere in the appendix.

If the Savings By Design procedures are updated, which edition applies?