CALGreen · California Green Building Standards Code (CALGreen)
Site Planning and Design (Division A6.1)
Division A6.1 (Appendix A6) directs site development and planning measures (see Section A6.106 and § A6.106.9) to reduce environmental impacts and improve building performance.
Last reviewed: July 6, 2026
Overview
Division A6.1 of the CALGreen Appendix A6 collects site-planning and site-development guidance tailored for health facilities, focusing on how siting, orientation and landscape decisions reduce environmental impacts and improve occupant comfort and safety. The Division identifies site-development provisions (Section A6.106) and specific measures such as building orientation (see § A6.106.9) that guide placement and shading to reduce thermal loss and manage solar exposure.
Although framed in the Appendix for state health-care occupancies, the Division aligns with the Chapter 5 planning-and-design topics used across CALGreen — stormwater control, bicycle and EV parking, shade/landscape, heat-island reduction and permeable surfaces — and cross‑references the Chapter 5 site development sections and voluntary planning electives. These cross-references help designers apply consistent site best practices (stormwater, shading, low‑impact development, EV readiness, bicycle parking, etc.).
Practically, Division A6.1 is used during early design and site feasibility: orient buildings to reduce energy use and wind exposure, locate landscape and shading to protect envelopes and manage stormwater, and plan parking and circulation to support active transportation and future electrification — all documented in the Site Development section and related CALGreen tables and appendices.
In this section
Code references
Grounded in the retrieved California Green Building Standards Code (CALGreen) — click a citation to read the verbatim passage:
CALGreen § 106.9 High relevance — show source text
FEATURE OR MEASURE COMPLIANCE LEVELS Col3 Col4 NOTES FEATURE OR MEASURE Mandatory
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenFEATURE OR MEASURE Mandatory
CALGreenTier 1 Tier 2 Tier 2 DIVISION A6.1 – PLANNING AND DESIGN SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development **A6.106.9 Building orientation.**Locate and orient the building as follows:
1. When site and location permit, orient the building with the long sides facing north and
south.
2. Protect the building from thermal loss, drafts and degradation of the building envelope
caused by wind and wind-driven materials such as dust. DIVISION A6.2 – ENERGY EFFICIENCY SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures A6.203.1 Energy performance. [OSHPD 1]
**A6.203.1.1 CALGreen Tier 1. [OSHPD 1]**Buildings must comply with the latest edition of
“Savings By Design, Healthcare Modeling Procedures.”
A.5.203.1.2 CALGreen Tier 2. [OSHPD 1] Buildings must exceed the latest edition of “Savings
By Design, Healthcare Modeling Procedures” by 15 percent. SECTION A6.204 Prescriptive Measures **A6.204.1 ENERGY STAR equipment and appliances.**All equipment and appliances provided
by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment
or appliance. A6.204.4 Commissioning. Building commissioning for all building systems covered by T24,
Part 6, process systems and renewable energy systems shall be included in the design and
construction processes of the building project. Commissioning requirements shall include as
a minimum items listed in Section A6.204.4.
**A6.204.4.1 Owner’s Project Requirements (OPR).**Documented before the design phase of
the project begins the OPR shall include items listed in Section A6.204.4.
**A6.204.4.2 Basis of Design (BOD).**A written explanation of how the design of the building
systems meets the OPR shall be completed at the design phase of the building project and
updated periodically to cover the systems listed in Section A6.204.4.2.
**A6.204.4.3 Commissioning plan.CALGreen § 1-1 High relevance — show source text
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A6.1-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A6.1-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
A6 VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]
DIVISION A6.1 – SITE PLANNING AND DESIGN
SECTION A6.106—SITE DEVELOPMENT
A6.106.9 Building orientation. Locate and orient the building as follows:
- When site and location permit, orient the building with the long sides facing north and south.
- Protect the building from thermal loss, drafts and degradation of the building envelope caused by wind and wind-driven materials such as dust, sand, snow and leaves, with building orientation and landscape features. Note: For information on sun angles and shading, visit: http://www2.aud.ucla.edu/energy-design-tools/.
Calculations may be made using the Solar-2 tool.
DIVISION A6.2 – ENERGY EFFICIENCY
SECTION A6.202—DEFINITIONS
A6.202.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.
ENERGY STAR. A joint program of the US Environmental Protection Agency and the US Department of Energy. ENERGY STAR is a voluntary program designed to identify and promote energy-efficient products and practices.
SECTION A6.203—PERFORMANCE APPROACH
A6.203.2 Energy performance. It is the intent of this code to encourage green buildings to achieve exemplary performance in the area of energy efficiency.
A6.203.2.1 CALGreen Tier 1. [OSHPD 1] To achieve CALGreen [Tier 1, buildings must comply with the latest edition of “Savings By](http://www.energysoft.com/ep/ 2007SBDHProcedures.pdf) Design, Healthcare Modeling Procedures” found online at http://www.energysoft.com/ep/ 2007SBDHProcedures.pdf.
A6.203.2.2 CALGreen Tier 2. [OSHPD 1] To achieve CALGreen Tier 2, buildings must exceed the latest edition of “Savings By Design, Healthcare Modeling Procedures” by a minimum of 15 percent.
SECTION A6.204—PRESCRIPTIVE APPROACH
A6.204.1 ENERGY STAR equipment and appliances. All equipment and appliances provided by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment or appliance.
A6.204.4 Commissioning. [OSHPD 1 & 4] Building commissioning shall be included in the design and construction processes of the building project to verify that the building’s energy related systems are installed, calibrated and perform according to the owner’s project requirements, basis of design and construction documents.
The owner and designer shall designate an individual as the Commissioning Authority (CxA) to lead, review and oversee the completion of the commissioning process activities. The owner shall document the Owner’s Project Requirements (OPR).
CALGreen § 602.1 High relevance — show source text
VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3
A5.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A5-3 A5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . APPENDIX A5-13 A5.3 Water Efficiency and Conservation . . . APPENDIX A5-19 A5.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-25 A5.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A5-35 A5.6 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-41 A5.601 CALGren Tier 1 and Tier 2. . . . . . . . . . APPENDIX A5-41
A5.602 CALGreen Verification Guidelines Mandatory Measures Checklist . . . . . . . . . . . . . . . APPENDIX A5-44
A5.602.1 CALGreen Verification Guidelines
Tier 1 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-48
A5.602.2 CALGreen Verification Guidelines
Tier 2 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-55
APPENDIX A6 VOLUNTARY STANDARDS FOR HEALTH
FACILITIES [OSHPD 1, 2 & 4] . . . . . . . . . . . APPENDIX A6.1-3 A6.1 Site Planning and Design . . . . . . . . . . . APPENDIX A6.1-3 A6.2 Energy Efficiency . . . . . . . . . . . . . . . . . . APPENDIX A6.1-3 A6.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . APPENDIX A6.1-32 A6.5 Environmental Quality . . . . . . . . . . . . APPENDIX A6.1-33
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INDEX-1
HISTORY NOTE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HIST-1
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE vii
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
viii 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE
CHAPTER 1 – ADMINISTRATION
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
|Adopting
CALGreen § 5.106.5.5.1 High relevance — show source text
1**
Planning and Design
Select Three Electives|Mandatory|Table 5.106.5.5.1|5.106.5.5 and
5.106.5.5.1||||| |(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|Mandatory|Light pollution reduction [N] (with exceptions, notes and
table)|5.106.8 through
5.106.8.2||||| |(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|Mandatory|Grading and paving (exception for additions and alter-
ations not altering the drainage path)|5.106.10||||| |(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|Tier 2
Prerequisite|Cool roof (A5.106.11.2.2): SRI 82 when≤_ 2:12, SRI 27 when >_
2:12|A5.106.11.2||||| |(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|Select Three Electives|Elective|Community connectivity|A5.103.1||||| |(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|Select Three Electives|Elective|Brownfield or greyfield site redevelopment or infill area
development|A5.103.2,
A5.103.2.1||||| |(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|Select Three Electives|Elective|Reduce development footprint and optimize open space|A5.104.1,
A5.104.1.1,
A5.104.1.2,
A5.104.1.3||||| |(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|Select Three Electives|Elective|Deconstruction and reuse of existing structures, Scope with
Exceptions, Reuse of existing building, Tier 2 and Verification
of compliance with Note|A5.105.1, A5.105.2,
A5.105.2.2 and
A5.105.2.3||||| |(continued)
DIVISION 5.1
Planning and Design
Select Three Electives|Select Three Electives|Elective|Storm water design|A5.106.2,
A5.106.2.1,
_A5.106.2.CALGreen § 203.1.1 High relevance — show source text
[OSHPD 1]**
**A6.203.1.1 CALGreen Tier 1. [OSHPD 1]**Buildings must comply with the latest edition of
“Savings By Design, Healthcare Modeling Procedures.”
A.5.203.1.2 CALGreen Tier 2. [OSHPD 1] Buildings must exceed the latest edition of “Savings
By Design, Healthcare Modeling Procedures” by 15 percent.||||| |SECTION A6.204 Prescriptive Measures||||| |**A6.204.1 ENERGY STAR equipment and appliances.**All equipment and appliances provided
by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment
or appliance.||||| |A6.204.4 Commissioning. Building commissioning for all building systems covered by T24,
Part 6, process systems and renewable energy systems shall be included in the design and
construction processes of the building project. Commissioning requirements shall include as
a minimum items listed in Section A6.204.4.
**A6.204.4.1 Owner’s Project Requirements (OPR).**Documented before the design phase of
the project begins the OPR shall include items listed in Section A6.204.4.
**A6.204.4.2 Basis of Design (BOD).**A written explanation of how the design of the building
systems meets the OPR shall be completed at the design phase of the building project and
updated periodically to cover the systems listed in Section A6.204.4.2.
**A6.204.4.3 Commissioning plan.**A commissioning plan describing how the project will be
commissioned shall be started during the design phase of the building project and shall
include as a minimum items listed in Section A6.204.4.3.
A6.204.4.4 Functional performance testingshall demonstrate the correct installation and
operation of each component, system and system-to-system interface in accordance with
the approved plans and specifications.
**A6.204.4.5 Post construction documentation and training.**A systems manual and
systems operations training are required.
**A6.204.4.5.1 Systems manual.**The systems manual shall be delivered to the building
owner and facilities operator and shall include the items listed in Section A6.204.4.5.1.
A6.204.4.5.2 Systems operations training. The training of the appropriate maintenance
staff for each equipment type and/or system shall include as a minimum items listed in
Section A6.204.4.5.2.
**A6.204.4.6 Commissioning report.**A complete report of commissioning process activities
undertaken through the design, construction and postconstruction phases of the building
project shall be completed and provided to the owner.||
|
|| |**A6.204.6 Building orientation and shading.CALGreen § 301.3 High relevance — show source text
Select the required number of additional electives from those categories shown on the table below and add a “ Y ” on the selected elective and add an “ N ” on the rest.
Count the total number of Tier 2 prerequisite measures plus the additional electives and write down the total number at the end of the checklist. Determine if the required number of Tier 2 measures have been selected to achieve Tier 2 compliance.
Y = Yes (section has been selected and/or included) N = No (section has not been selected and/or included) O = Other (provide explanation)
[N] = New construction pursuant to Section 301.3
[A] = Additions and/or Alterations pursuant to Section 301.3
CHAPTER 5
DIVISIONSCol2 SECTION TITLE CODE
SECTIONY N O PLAN SHEET,
SPEC OR
ATTACHDIVISION 5.1
Planning and
Design
(continued)Mandatory Deconstruction and reuse of existing structures,
Scope with Exception5.105.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Reuse of existing building & Verification of compliance with
note5.105.2 and 5.105.2.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Storm water pollution prevention for projects that disturb
less than 1 acre of land5.106.1 through
5.106.2DIVISION 5.1
Planning and
Design
(continued)Mandatory Short-term bicycle parking 5.106.4.1.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Long-term bicycle parking 5.106.4.1.2 through
5.106.4.1.5DIVISION 5.1
Planning and
Design
(continued)Tier 2
PrerequisiteDesignated parking—50% of parking capacity with future
charging spaces, parking stall markings and vehicle
designationA5.106.5.1,
A5.106.5.1.2,
A5.106.5.1.3,
A5.106.5.1.4,
A5.106.5.1.5DIVISION 5.1
Planning and
Design
(continued)Tier 2
PrerequisiteElectric vehicle (EV) charging [N] with Section 5.106.3.1,
Section 5.106.5.3.2 and associated Table A5.106.5.3.3 Tier 2
OR
Power Allocation Method:
Section A5.106.5.3.4 and associated Table A5.106.5.3.4 Tier 25.106.5.3.1,
5.106.5.3.2,
_Table A5.106.5.CALGreen § 5.508.2 High relevance — show source text
000 square feet or more|5.508.2
through
5.508.2.6.3||||| |||END OF MANDATORY PROVISIONS||||||Documentation Author's / Responsible Designer's Declaration Statement
□ Mandatory: I attest that this mandatory provisions checklist is accurate and complete.Col2 Signature: Signature: Company: Date: Address: License: City/State/Zip: Phone: 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-47
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A5 — NONRESIDENTIAL VOLUNTARY MEASURES
A5.602.1
CALGreen VERIFICATION GUIDELINES
TIER 1 CHECKLIST
Application: This checklist shall be used for nonresidential projects that meet the following: new construction, or building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3, AND are adopting Tier 1 voluntary measures.
Note: All applicable mandatory requirements in Chapter 5 shall be met prior to applying Tier 1 voluntary measures.
Instructions:
Comply with all Tier 1 prerequisite measures from the various categories shown on the table below.
Add a “ Y ” to all mandatory and Tier 1 prerequisite measures in the appropriate columns.
Select the required number of additional electives from those categories shown on the table below and add a “ Y ” on the selected elective and add an “ N ” on the rest.
Count the total number of Tier 1 prerequisite measures plus the additional electives and write down the total number at the end of the checklist. Determine if the required number of Tier 1 measures have been selected to achieve Tier 1 compliance.
Y = Yes (section has been selected and/or included) N = No (section has not been selected and/or included) O = Other (provide explanation)
[N] = New construction pursuant to Section 301.3
[A] = Additions and/or Alterations pursuant to Section 301.3
CHAPTER 5
DIVISIONSCol2 SECTION TITLE CODE
SECTIONY N O PLAN SHEET,
SPEC OR
ATTACHDIVISION 5.1
Planning and
Design
(continued)Mandatory Deconstruction and reuse of existing structures,
Scope with Exception5.105.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Reuse of existing building & Verification of compliance with note 5.105.2 and 5.105.2.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Storm water pollution prevention for projects that disturb
less than 1 acre of land5.106.1 through
5.106.2DIVISION 5.1
Planning and
Design
(continued)Mandatory Short-term bicycle parking 5.106.4.1. CALGreen § 1-5 High relevance — show source text
102 Construction Documents
and Installation Verification . . . . . . . . . . . . . . . . . . . .1-5
103 Building Standards Commission. . . . . . . . . . . . . . . . . . .1-5 104 Department of Housing and Community Development. . . . . . . . . . . . . . . . . .1-6 105 Division of the State Architect . . . . . . . . . . . . . . . . . . . . .1-6
106 Office of Statewide Health Planning and Development . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-6
CHAPTER 2 DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
201 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
202 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
CHAPTER 3 GREEN BUILDING . . . . . . . . . . . . . . . . . . . . . . . . 3-3
301 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
302 Mixed Occupancy Buildings . . . . . . . . . . . . . . . . . . . . . . .3-4 303 Phased Projects. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4 304 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4 305 CALGreen Tier 1 and CALGreen Tier 2 . . . . . . . . . . . . . .3-4
306 Voluntary Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
CHAPTER 4 RESIDENTIAL MANDATORY MEASURES . . . . . . 4-3
4.1 Planning and Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-3 4.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-7 4.3 Water Efficiency and Conservation . . . . . . . . . . . . . . . . .4-9 4.4 Material Conservation and Resource Efficiency . . . . 4-11 4.5 Environmental Quality . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
CHAPTER 5 NONRESIDENTIAL MANDATORY MEASURES . . 5-3
CALGreen § 8-40 High relevance — show source text
. . . . . . . . . . . . . 8-40
APPENDIX A4 RESIDENTIAL
VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A4-3
A4.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A4-3 A4.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . APPENDIX A4-9 A4.3 Water Efficiency and Conservation . . . APPENDIX A4-13 A4.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A4-15 A4.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A4-19 A4.6 Tier 1 and Tier 2 . . . . . . . . . . . . . . . . . . . . APPENDIX A4-21
Division A4.6—Residential Occupancies Application Checklist . . . . . . . . . . . . . APPENDIX A4-23 A4.7 Residential Model Ordinance . . . . . . . . . APPENDIX A4-31
APPENDIX A5 NONRESIDENTIAL
VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3
A5.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A5-3 A5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . APPENDIX A5-13 A5.3 Water Efficiency and Conservation . . . APPENDIX A5-19 A5.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-25 A5.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A5-35 A5.6 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-41 A5.601 CALGren Tier 1 and Tier 2. . . . . . . . . . APPENDIX A5-41
A5.602 CALGreen Verification Guidelines Mandatory Measures Checklist . . . . . . . . . . . . . . . APPENDIX A5-44
A5.602.1 CALGreen Verification Guidelines
Tier 1 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-48
A5.602.2 CALGreen Verification Guidelines
Tier 2 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-55
APPENDIX A6 VOLUNTARY STANDARDS FOR HEALTH
CALGreen § 0.5 High relevance — show source text
in.|≤ 100 sq. in. =
D-H-90
>100 sq. in.=
D-H-W-90|Not
Permitted|2|Not
Permitted|W-120| |Double fire walls
constructed in
accordance with
NFPA 221|2|1|1|100 sq. in.|≤ 100 sq. in. =
D-H-60
> 100 sq. in. =
D-H-W-60|Not
Permitted|1|Not
Permitted|W-60| |Enclosures for
shafts, interior exit
stairways and inte-
rior exit ramps.|2|2|11/ 2|100 sq. in.b|≤100 sq. in. =
D-H-90
> 100 sq. in.=
D-H-T-W-90|Not
Permitted|2|Not
Permitted|W-120| |Horizontal exits in
fire wallsg|4|4|3|100 sq. in.|≤100 sq. in. =
D-H-180
> 100 sq. in.=
D-H-W-240|Not
Permitted|4|Not
Permitted|W-240| |Horizontal exits in
fire wallsg|3|3|3d|100 sq. in.|≤100 sq. in. =
D-H-180
> 100 sq. in.=
D-H-W-180|Not
Permitted|3|Not
Permitted|W-180| |Fire barriers having
a required fire-
resistance rating of
1 hour: Enclosures
for shafts, exit
access stairways,
exit access ramps,
interior exit stair-
ways and interior
exit ramps; and exit
passageway walls|1|1|1|100 sq. in.|≤100 sq. in. =
D-H-60
>100 sq. in.=
D-H-T-W-60|Not
Permitted|1|Not
Permitted|W-60| |||||||Fire protection|Fire protection||| |Other fire barriers|1|1|3/ 4|Maximum
size tested|D-H-45|3/ 4
h|3/ 4
h|D-H-45h|D-H-45h| |Fire partitions:
Corridor walls|1|1|1/ 3
a|Maximum
size tested|D-20|3/ 4
a|3/ 4
a|D-H-OH-45|D-H-OH-45| |Fire partitions:
Corridor walls|0.5|0.5|1/ 3
a|Maximum
size tested|D-20|1/ 3|1/ 3|D-H-OH-20|D-H-OH-20|7-28 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FIRE AND SMOKE PROTECTION FEATURES
|TABLE 716.1(2)—OPENING FIRE PROTECTION ASSEMBLIES,
CALGreen § 0.099 High relevance — show source text
c, d, e Col2 Col3 Col4 Col5 Col6 MAXIMUM DESIGN
PRESSURE
(+ or - psf)MINIMUM
PANEL SPAN
RATINGMINIMUM PANEL
PERFORMANCE
CATEGORYNAIL TYPE
AND SIZEFASTENERa SPACINGe ALONG
EDGES AND INTERMEDIATE SUPPORTS
(inches)FASTENERa SPACINGe ALONG
EDGES AND INTERMEDIATE SUPPORTS
(inches)MAXIMUM DESIGN
PRESSURE
(+ or - psf)MINIMUM
PANEL SPAN
RATINGMINIMUM PANEL
PERFORMANCE
CATEGORYNAIL TYPE
AND SIZEGalvanized Steel Stainless Steel 30 24/0 3/8 6d box
(2 × 0.099 × 0.266 head diameter)6f 4 40 24/0 3/8 6d box
(2 × 0.099 × 0.266 head diameter)6 4 50 24/0 3/8 6d box
(2 × 0.099 × 0.266 head diameter)4 4 50 24/0 3/8 8d common
(21/2 × 0.131 × 0.281 head diameter)6 6 60 24/0 3/8 6d box
(2 × 0.099 × 0.266 head diameter)4 3 60 24/0 3/8 8d common
(21/2 × 0.131 × 0.281 head diameter)6 4 70 24/16 7/16 8d common
(21/2× 0.131 × 0.281 head diameter)4 4 70 24/16 7/16 10d box
(3 × 0.128 × 0.312 head diameter)6 4 80 24/16 7/16 8d common
(21/2 × 0.131 × 0.281 head diameter)4 4 80 24/16 7/16 10d box
(3 × 0.128 × 0.312 head diameter)6 4 90 32/16 15/32 8d common
(21/2 × 0.131 × 0.281 head diameter)4 3 90 32/16 15/32 10d box
(3 × 0.128 × 0.312 head diameter)6 4 For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa.
a. Fasteners shall comply with Sections R703.3.2 and R703.3.3.
b. Maximum spacing of exterior soffit framing members shall not exceed 24 inches.
c. Wood structural panels shall be of an exterior exposure grade.
d. Wood structural panels shall be installed with strength axis perpendicular to supports with not fewer than two continuous spans.
e.CALGreen § 602.2 High relevance — show source text
Documentation Author's / Responsible Designer's Declaration Statement
Check the appropriate box(es) for the list below.
□ Mandatory: I attest that the mandatory provisions checklist is accurate and complete.
□ Tier 1 compliant: I attest that the total number of voluntary measures selected meet or exceed the total number required
to achieve Tier 1 compliance.
□ Partial Tier 1 compliant: I attest that the total number of voluntary measures selected do not meet the total number
required to achieve Tier 1 compliance: however, partial Tier 1 compliance has been achieved.Col2 Signature: Company: Date: Address: License: City/State/Zip: Phone: APPENDIX A5-54 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A5 — NONRESIDENTIAL VOLUNTARY MEASURES
A5.602.2
CALGreen VERIFICATION GUIDELINES
TIER 2 CHECKLIST
Application: This checklist shall be used for nonresidential projects that meet the following: new construction, or building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3, AND are adopting Tier 2 voluntary measures.
Note: All applicable mandatory requirements in Chapter 5 shall be met prior to applying Tier 2 voluntary measures.
Instructions:
Comply with all Tier 2 prerequisite measures from the various categories shown on the table below.
Add a “ Y ” to all mandatory and Tier 2 prerequisite measures in the appropriate columns.
Select the required number of additional electives from those categories shown on the table below and add a “ Y ” on the selected elective and add an “ N ” on the rest.
Count the total number of Tier 2 prerequisite measures plus the additional electives and write down the total number at the end of the checklist. Determine if the required number of Tier 2 measures have been selected to achieve Tier 2 compliance.
Y = Yes (section has been selected and/or included) N = No (section has not been selected and/or included) O = Other (provide explanation)
[N] = New construction pursuant to Section 301.3
[A] = Additions and/or Alterations pursuant to Section 301.3
CHAPTER 5
DIVISIONSCol2 SECTION TITLE CODE
SECTIONY N O PLAN SHEET,
SPEC OR
ATTACHDIVISION 5.1
Planning and
Design
(continued)Mandatory Deconstruction and reuse of existing structures,
Scope with Exception5.105.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Reuse of existing building & Verification of compliance with
note5.105.2 and 5.105.2.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Storm water pollution prevention for projects that disturb
less than 1 acre of land5.106.1 through
5.106.
Frequently asked questions
What specific section covers site development and building orientation in A6.1?
Site development is addressed in Section A6.106; building orientation is specifically required and described in § A6.106.9.
How does Division A6.1 relate to the mandatory Chapter 5 planning provisions?
Division A6.1 (Appendix A6) parallels and cross-references Chapter 5 planning-and-design provisions (e.g., stormwater, bicycle/EV parking, shade and heat‑island measures) so health‑facility projects can apply the same site best practices found in Chapter 5.
When should designers consult A6.1 during a project?
Consult Division A6.1 during site selection and schematic design to set building orientation, landscape/ shading strategies, stormwater controls and parking/electrification planning — decisions that influence energy performance, water management and occupant health.
More in California Green Building Standards Code (CALGreen)
- Administration (Chapter 1)
- Nonresidential Voluntary Measures (Appendix A5 — divisions A5.1–A5.6, electives & verification)
- Residential Mandatory Measures — Planning & Design; Energy; Water; Materials; Environmental Quality (Chapter 4)
- Definitions (Chapter 2)
- Voluntary Standards for Health Facilities (Appendix A6 / OSHPD guidance)
- Green Building – scope, mixed occupancies, phased projects (Chapter 3)
- Residential Voluntary Measures (Appendix A4 — divisions A4.1–A4.6, tiers & model ordinance)
- Nonresidential Mandatory Measures — Planning & Design; Energy; Water; Materials; Environmental Quality (Chapter 5)
- Compliance verification, construction documents & checklists (Section 102, Chapter 7, Appendix checklists)