CALGreen · California Green Building Standards Code (CALGreen)

Which site planning items appear on the nonresidential application checklist?

For nonresidential projects under Appendix A6.1, the A6.1 application checklist explicitly lists one site‑planning item: **Building orientation (§ A6.106.9)**. On your site plan show the long façade oriented north–south when feasible and show landscape or other features that protect the building from thermal loss and wind‑driven materials; check the A6.1 checklist box and reference the plan sheet so the enforcing agency can verify compliance .

Last reviewed: July 6, 2026

What the code requires — 2–4 sentences

The Appendix A6.1 nonresidential Application Checklist calls out site‑planning under Division A6.1 — Planning and Design, and the only explicit site‑development item shown on that checklist is Building orientation at § A6.106.9. The text of § A6.106.9 requires orienting the building (where site and location permit) with the long sides facing north and south and protecting the building from thermal loss and wind‑driven materials. The checklist entry and the section text are shown in the Appendix A6.1 application checklist and the A6.106 site‑development section respectively .

The single site‑planning item explicitly listed in the A6.1 nonresidential checklist is Building orientation (see § A6.106.9) — orient long facades north/south and use orientation/landscape features to shield the building from wind and wind‑driven materials.


Requirements in detail

What appears on the Appendix A6.1 (nonresidential) checklist

  • The application checklist under Division A6.1 – Planning and Design lists A6.106.9 Building orientation as the site‑development item to check on the nonresidential occupancy checklist .
  • The A6.106 site‑development text spells out what that checklist item means in practice in § A6.106.9 .

What § A6.106.9 requires (plain English)

  • Orient the building, when feasible, so the long sides face north and south.
  • Use building siting and landscape features to protect the building from thermal loss, drafts and degradation of the envelope caused by wind and wind‑driven materials (dust, sand, snow, leaves).
    These two elements are the compliance content that corresponds to the checklist entry § A6.106.9 .

Cross‑references and related prescriptive entries

  • The prescriptive measures include a separate item on building orientation and shading that instructs designers to "locate, orient and shade the building as required in Section § A6.106.11" and is referenced in § A6.204.6 (building orientation and shading) on the A6.204 prescriptive checklist items; § A6.204.6 explicitly points back to the A6.106 orientation requirements . (Note: the A6.204.6 text is present in the checklist material returned; the underlying text of § A6.106.11 was referenced but not available in the retrieval set — see Exceptions & special cases.)

Quick decision table (what you must show on plans/submittal)

Decision item Required action / value Code reference
Building orientation (site plan) Orient long building facades north–south, show on plan; indicate landscape/structural features to block prevailing winds and reduce thermal loss § A6.106.9
Building orientation & shading (prescriptive cross‑check) If using A6 prescriptive measures, show shading strategy and note conformance with orientation/shading requirements § A6.204.6 → refers to § A6.106.11
Checklist box to complete Check the A6.1 "Site Development / Building orientation" box on the Application Checklist Appendix A6.1 Checklist table (Division A6.1)

Exceptions & special cases

  • The orientation requirement applies “when site and location permit.” That conditional phrase is part of § A6.106.9; if site constraints (lot shape, easements, access, preservation of historic resources, etc.) prevent north‑south long‑side orientation, document the constraint and the alternative measures used to mitigate solar/thermal/wind effects .
  • The A6.204.6 prescriptive item requires shading/ orientation per § A6.106.11; the checklist references that requirement, but the specific text of § A6.106.11 was not contained in the retrieved files. If you rely on A6.204 prescriptive measures, ensure you verify the A6.106.11 language with the complete code text or the enforcing agency (the checklist points designers to the section) .
  • Local agency adoptions can alter which subsections are mandatory or enforced. The Matrix/Adoption notes show § A6.106.9 as an adopted item for certain agencies — confirm local adoption before assuming voluntary status .

Common mistakes

  • Not showing the building orientation on the site plan: the checklist expects a plan sheet showing orientation and protective landscape or wind‑screening elements (trees, berms, walls). The checklist entry is § A6.106.9 .
  • Checking the checklist box without supporting documentation: the A6.1 checklist is a declaration; the enforcing agency may require plan references, notes, or calculations — include the plan sheet reference on the checklist entry.
  • Confusing A6.106.9 (orientation) with unrelated site items (e.g., stormwater, entry systems). Appendix A6.1’s checklist lists only the orientation entry under Division A6.1; other site measures appear elsewhere in A6 (or in A5) and must be documented under their own sections .
  • Relying on a referenced subsection that wasn’t inspected (e.g., A6.106.11): the checklist/prescriptive text refers to other subsections; don’t assume content — pull the definitive section text and cite it with your submittal .

Worked example

Scenario: New outpatient clinic, rectangular footprint 200 ft (long) × 80 ft (short). The site is an open lot with a prevailing winter wind from the northwest.

  1. Apply § A6.106.9: orient the long 200‑ft facades roughly north–south so the long sides face north and south. On the site plan show the building rotated so the 200‑ft sides run north–south and label the orientation (“long side — north/south”) — this addresses the first item in § A6.106.9 .
  2. Protect the building from prevailing wind: show a landscape buffer on the northwest side consisting of a two‑row wind‑screen planting and a low masonry wall near the mechanical intake; note on the plan that these features reduce wind‑driven dust and drafts into the envelope (addresses second item in § A6.106.9) .
  3. On the Appendix A6.1 application checklist, check the A6.106.9 Building orientation box and add a plan sheet reference (e.g., “See site plan sheet A1.0”) so the enforcing agency can verify your work .
  4. If you choose prescriptive shading measures under A6.204, document how the shading plan corresponds to the orientation (A6.204.6 points to A6.106.11 for orientation/shading details) and attach the required shading calculations or shading device details — confirm the text of § A6.106.11 when preparing submittal materials .

Related provisions (pull these when you compile your submittal)

  • § A6.106.9 — Building orientation (site‑development item listed on the A6.1 checklist)
  • § A6.204.6 — Building orientation and shading (prescriptive measures that reference A6.106.11)
  • Appendix A6.1 — Nonresidential application checklist table (Division A6.1 entries) — shows the checklist box for A6.106.9
  • Matrix/Adoption notes for Appendix A6 — shows local/state adoption status for A6.106.9 (confirm local enforcing agency)

Code references

Grounded in the retrieved California Green Building Standards Code (CALGreen) — click a citation to read the verbatim passage:

  • CALGreen § 405.4 High relevance — show source text
    1. From Division A5.4,

    a. Comply with recycled content of 15 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4.1. b. Comply with the 80-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with three elective measures selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 100 percent of resilient flooring in Section A5.504.4.7.1. Exception: Allowance may be permitted in Tier 2 for up to 5-percent specialty purpose flooring. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list and no added formaldehyde in Section A5.504.4.8.1.

    c. Comply with three elective measures selected from this division. 6. Comply with three additional elective measures selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.4 Compliance verification. Compliance with Section A5.601.2 or A5.601.3 shall be as required in Chapter 7 of this code. Compliance documentation shall be made part of the project record as required in Section 5.410.2 or 5.410.3.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-43

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    A5.602

    CALGreen VERIFICATION GUIDELINES MANDATORY MEASURES CHECKLIST

    Application: This checklist shall be used for nonresidential projects that meet one of the following: new construction, building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3 AND do not trigger a Tier 1 or Tier 2 requirement:

    Y = Yes (section has been selected and/or included)

    N/A = Not Applicable (code section does not apply to the project mainly used for additions and alterations) O = Other (provide explanation)

    [N] = New construction pursuant to Section 301.3

    [A ] = Additions and/or Alterations pursuant to Section 301.3

    CHAPTER 5
    DIVISIONS
    Col2 SECTION TITLE CODE
    SECTION
    Y N/A O PLAN SHEET,
    SPEC OR
    ATTACH
    DIVISION 5.1
    Planning and
    Design
    Mandatory Deconstruction and reuse of existing structures,
    Scope with Exception
    5.105.1
    DIVISION 5.1
    Planning and
    Design
    Mandatory Reuse of existing building & Verification of compliance with
    note
    5.105.2 and
    5.105.2.1
    DIVISION 5.1
    Planning and
    Design
    Mandatory Storm water pollution prevention for projects that disturb less
    than 1 acre of land
    5.106.
  • CALGreen § 602.1 High relevance — show source text

    )_|TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)| |CATEGORY|ENVIRONMENTAL
    PERFORMANCE GOAL|TIER 1|TIER 2| |All|Minimum Mandatory
    (See Mandatory Checklist)|Meet all of the provisions
    of Chapter 5 (See Tier 1 Checklist)|Meet all of the provisions
    of Chapter 5 (See Tier 2 Checklist)| |DIVISION 5.1
    Planning and Design|Reuse of existing building|See Section A5.105.1 and Section
    A5.105.2 requirements|See Section A5.105.1 and Section
    A5.105.2 requirements| |DIVISION 5.1
    Planning and Design|Designated Parking for
    Fuel Efficient Vehicles
    (Tier 1 and Tier 2 only)|Approx. 35% of total spaces|Approx. 50% of total spaces| |DIVISION 5.1
    Planning and Design|Electric Vehicle Charging|Approx. 30% of total spaces|Approx. 45% of total spaces| |DIVISION 5.1
    Planning and Design|Cool Roof to Reduce
    Heat Island Effect|Roof Slope < 2:12 SRI 75
    Roof Slope > 2:12 SRI 16|Roof Slope < 2:12 SRI 82
    Roof Slope > 2:12 SRI 27| |DIVISION 5.1
    Planning and Design||1 additional Elective from Division A5.1|3 additional Electives from Division A5.1| |DIVISION 5.2
    Energy Efficiency|Energy Performance2a, 2b|Outdoor lighting power 90%
    of Part 6 allowance|Outdoor lighting power 90%
    of Part 6 allowance| |||If applicable, solar water-heating system
    with minimum solar savings fraction of 0.15|If applicable, solar water-heating system
    with minimum solar savings fraction of 0.15| |||Warehouse door seals|Warehouse door seals| |||Comply with day lighting requirements|Comply with day lighting requirements| |||Exhaust heat recovery|Exhaust heat recovery| |||Energy Budget 95% or 90%
    of Part 6 calculated value of allowance|Energy Budget 90% or 85%
    of Part 6 calculated value of allowance| |DIVISION 5.3
    Water Efficiency
    and Conservation|Indoor Water Use|12% Savings|20% Savings| |DIVISION 5.3
    Water Efficiency
    and Conservation||1 additional Elective from Division A5.3|3 additional Electives from Division A5.3| |DIVISION 5.4
    Material Conservation
    and Resource Efficiency3|Construction Waste Reduction|At least 65% reduction|At least 80% reduction| |**DIVISION 5.

  • CALGreen § 602.1 High relevance — show source text

    VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3

    A5.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A5-3 A5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . APPENDIX A5-13 A5.3 Water Efficiency and Conservation . . . APPENDIX A5-19 A5.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-25 A5.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A5-35 A5.6 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-41 A5.601 CALGren Tier 1 and Tier 2. . . . . . . . . . APPENDIX A5-41

    A5.602 CALGreen Verification Guidelines Mandatory Measures Checklist . . . . . . . . . . . . . . . APPENDIX A5-44

    A5.602.1 CALGreen Verification Guidelines

    Tier 1 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-48

    A5.602.2 CALGreen Verification Guidelines

    Tier 2 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-55

    APPENDIX A6 VOLUNTARY STANDARDS FOR HEALTH

    FACILITIES [OSHPD 1, 2 & 4] . . . . . . . . . . . APPENDIX A6.1-3 A6.1 Site Planning and Design . . . . . . . . . . . APPENDIX A6.1-3 A6.2 Energy Efficiency . . . . . . . . . . . . . . . . . . APPENDIX A6.1-3 A6.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . APPENDIX A6.1-32 A6.5 Environmental Quality . . . . . . . . . . . . APPENDIX A6.1-33

    INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INDEX-1

    HISTORY NOTE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HIST-1

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE vii

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    viii 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE

    CHAPTER 1 – ADMINISTRATION

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    |Adopting

  • CALGreen § 8-40 High relevance — show source text

    . . . . . . . . . . . . . 8-40

    APPENDIX A4 RESIDENTIAL

    VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A4-3

    A4.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A4-3 A4.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . APPENDIX A4-9 A4.3 Water Efficiency and Conservation . . . APPENDIX A4-13 A4.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A4-15 A4.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A4-19 A4.6 Tier 1 and Tier 2 . . . . . . . . . . . . . . . . . . . . APPENDIX A4-21

    Division A4.6—Residential Occupancies Application Checklist . . . . . . . . . . . . . APPENDIX A4-23 A4.7 Residential Model Ordinance . . . . . . . . . APPENDIX A4-31

    APPENDIX A5 NONRESIDENTIAL

    VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3

    A5.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A5-3 A5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . APPENDIX A5-13 A5.3 Water Efficiency and Conservation . . . APPENDIX A5-19 A5.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-25 A5.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A5-35 A5.6 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-41 A5.601 CALGren Tier 1 and Tier 2. . . . . . . . . . APPENDIX A5-41

    A5.602 CALGreen Verification Guidelines Mandatory Measures Checklist . . . . . . . . . . . . . . . APPENDIX A5-44

    A5.602.1 CALGreen Verification Guidelines

    Tier 1 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-48

    A5.602.2 CALGreen Verification Guidelines

    Tier 2 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-55

    APPENDIX A6 VOLUNTARY STANDARDS FOR HEALTH

  • CALGreen § 602.2 High relevance — show source text
    Documentation Author's / Responsible Designer's Declaration Statement
    Check the appropriate box(es) for the list below.
    □ Mandatory: I attest that the mandatory provisions checklist is accurate and complete.
    □ Tier 1 compliant: I attest that the total number of voluntary measures selected meet or exceed the total number required
    to achieve Tier 1 compliance.
    □ Partial Tier 1 compliant: I attest that the total number of voluntary measures selected do not meet the total number
    required to achieve Tier 1 compliance: however, partial Tier 1 compliance has been achieved.
    Col2
    Signature:
    Company: Date:
    Address: License:
    City/State/Zip: Phone:

    APPENDIX A5-54 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    A5.602.2

    CALGreen VERIFICATION GUIDELINES

    TIER 2 CHECKLIST

    Application: This checklist shall be used for nonresidential projects that meet the following: new construction, or building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3, AND are adopting Tier 2 voluntary measures.

    Note: All applicable mandatory requirements in Chapter 5 shall be met prior to applying Tier 2 voluntary measures.

    Instructions:

    Comply with all Tier 2 prerequisite measures from the various categories shown on the table below.

    Add a “ Y ” to all mandatory and Tier 2 prerequisite measures in the appropriate columns.

    Select the required number of additional electives from those categories shown on the table below and add a “ Y ” on the selected elective and add an “ N ” on the rest.

    Count the total number of Tier 2 prerequisite measures plus the additional electives and write down the total number at the end of the checklist. Determine if the required number of Tier 2 measures have been selected to achieve Tier 2 compliance.

    Y = Yes (section has been selected and/or included) N = No (section has not been selected and/or included) O = Other (provide explanation)

    [N] = New construction pursuant to Section 301.3

    [A] = Additions and/or Alterations pursuant to Section 301.3

    CHAPTER 5
    DIVISIONS
    Col2 SECTION TITLE CODE
    SECTION
    Y N O PLAN SHEET,
    SPEC OR
    ATTACH
    DIVISION 5.1
    Planning and
    Design
    (continued)
    Mandatory Deconstruction and reuse of existing structures,
    Scope with Exception
    5.105.1
    DIVISION 5.1
    Planning and
    Design
    (continued)
    Mandatory Reuse of existing building & Verification of compliance with
    note
    5.105.2 and 5.105.2.1
    DIVISION 5.1
    Planning and
    Design
    (continued)
    Mandatory Storm water pollution prevention for projects that disturb
    less than 1 acre of land
    5.106.1 through
    5.106.
  • CALGreen § 507.4.1.1 High relevance — show source text

    507.4.1.1||||| |(continued)
    DIVISION 5.5
    Environmental
    Quality|Mandatory|Performance method|5.507.4.2||||| |(continued)
    DIVISION 5.5
    Environmental
    Quality|Mandatory|Site features|5.507.4.2.1||||| |(continued)
    DIVISION 5.5
    Environmental
    Quality|Mandatory|Documentation of compliance|5.507.4.2.2||||| |(continued)
    DIVISION 5.5
    Environmental
    Quality|Mandatory|Interior sound transmission (with note)|5.507.4.3||||| |(continued)
    DIVISION 5.5
    Environmental
    Quality|Mandatory|Ozone depletion and greenhouse gas reductions|5.508.1||||| |(continued)
    DIVISION 5.5
    Environmental
    Quality|Mandatory|Chlorofluorocarbons (CFCs)|5.508.1.1||||| |(continued)
    DIVISION 5.5
    Environmental
    Quality|Mandatory|Halons|5.508.1.2||||| |(continued)
    DIVISION 5.5
    Environmental
    Quality|Mandatory|Supermarket refrigerant leak reduction for retail food
    stores 8,000 square feet or more|5.508.2
    through
    5.508.2.6.3||||| |||END OF MANDATORY PROVISIONS||||||

    Documentation Author's / Responsible Designer's Declaration Statement
    □ Mandatory: I attest that this mandatory provisions checklist is accurate and complete.
    Col2
    Signature: Signature:
    Company: Date:
    Address: License:
    City/State/Zip: Phone:

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-47

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    A5.602.1

    CALGreen VERIFICATION GUIDELINES

    TIER 1 CHECKLIST

    Application: This checklist shall be used for nonresidential projects that meet the following: new construction, or building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3, AND are adopting Tier 1 voluntary measures.

    Note: All applicable mandatory requirements in Chapter 5 shall be met prior to applying Tier 1 voluntary measures.

    Instructions:

    Comply with all Tier 1 prerequisite measures from the various categories shown on the table below.

    Add a “ Y ” to all mandatory and Tier 1 prerequisite measures in the appropriate columns.

    Select the required number of additional electives from those categories shown on the table below and add a “ Y ” on the selected elective and add an “ N ” on the rest.

  • CALGreen § 301.3 High relevance — show source text

    A5.602

    CALGreen VERIFICATION GUIDELINES MANDATORY MEASURES CHECKLIST

    Application: This checklist shall be used for nonresidential projects that meet one of the following: new construction, building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3 AND do not trigger a Tier 1 or Tier 2 requirement:

    Y = Yes (section has been selected and/or included)

    N/A = Not Applicable (code section does not apply to the project mainly used for additions and alterations) O = Other (provide explanation)

    [N] = New construction pursuant to Section 301.3

    [A ] = Additions and/or Alterations pursuant to Section 301.3

    CHAPTER 5
    DIVISIONS
    Col2 SECTION TITLE CODE
    SECTION
    Y N/A O PLAN SHEET,
    SPEC OR
    ATTACH
    DIVISION 5.1
    Planning and
    Design
    Mandatory Deconstruction and reuse of existing structures,
    Scope with Exception
    5.105.1
    DIVISION 5.1
    Planning and
    Design
    Mandatory Reuse of existing building & Verification of compliance with
    note
    5.105.2 and
    5.105.2.1
    DIVISION 5.1
    Planning and
    Design
    Mandatory Storm water pollution prevention for projects that disturb less
    than 1 acre of land
    5.106.1 through
    5.106.2
    DIVISION 5.1
    Planning and
    Design
    Mandatory Short-term bicycle parking (with exception) 5.106.4.1.1
    DIVISION 5.1
    Planning and
    Design
    Mandatory Long-term bicycle parking 5.106.4.1.2
    through
    5.106.4.1.2.3
    DIVISION 5.1
    Planning and
    Design
    Mandatory Electric vehicle (EV) charging [N] with Section 5.106.3.1,
    5.106.5.3.2 and associated Table 5.106.5.3.1
    OR Independently
    Power Allocation Method:
    Section 5.106.5.3.6 and associated Table 5.106.5.3.6
    5.106.5.3.1,
    5.106.5.3.2,
    Table 5.106.5.3.1,
    5.106.5.3.2.1,
    5.106.5.3.2.2,
    5.106.5.3.2.3,
    5.106.5.3.2.4,
    5.106.5.3.3,
    5.106.5.3.4 and
    5.106.5.3.5
    OR
    5.106.5.3.3,
    5.106.5.3.4,
    5.106.5.3.5,
    5.106.5.3.6,
  • CALGreen § 602.1 High relevance — show source text

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-39

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5-40 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    A5 NONRESIDENTIAL VOLUNTARY MEASURES

    DIVISION A5.6 – VOLUNTARY TIERS

    SECTION A5.601—CALGreen TIER 1 AND TIER 2 Col2 Col3 Col4
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    TABLE A5.601 NONRESIDENTIAL BUILDINGS: Green Building Standards Code Proposed Performance Approach
    Note: This table is intended only as an aid in illustrating the nonresidential tier structure (Refer to Checklists A5.602, A5.602.1 and A5.602.2 for
    CALGreen verification guidelines for Mandatory Checklist, Tier 1 Checklist and Tier 2 Checklist.)
    CATEGORY ENVIRONMENTAL
    PERFORMANCE GOAL
    TIER 1 TIER 2
    All Minimum Mandatory
    (See Mandatory Checklist)
    Meet all of the provisions
    of Chapter 5 (See Tier 1 Checklist)
    Meet all of the provisions
    of Chapter 5 (See Tier 2 Checklist)
    DIVISION 5.1
    Planning and Design
    Reuse of existing building See Section A5.105.1 and Section
    A5.105.2 requirements
    See Section A5.105.1 and Section
    A5.105.2 requirements
    DIVISION 5.1
    Planning and Design
    Designated Parking for
    Fuel Efficient Vehicles
    (Tier 1 and Tier 2 only)
    Approx. 35% of total spaces Approx. 50% of total spaces
    DIVISION 5.1
    Planning and Design
    Electric Vehicle Charging Approx. 30% of total spaces Approx. 45% of total spaces
    **DIVISION 5.
  • CALGreen § 507.3 High relevance — show source text

    5**
    Environmen-
    tal
    Quality|Select One|Elective|Views|A5.507.3||||| |(continued)
    DIVISION 5.5
    Environmen-
    tal
    Quality|Select One|Elective|Interior office spaces|A5.507.3.1||||| |(continued)
    DIVISION 5.5
    Environmen-
    tal
    Quality|Select One|Elective|Multi-occupant spaces (with exceptions)|A5.507.3.2||||| |(continued)
    DIVISION 5.5
    Environmen-
    tal
    Quality|Select One|Elective|Hydrochlorofluorocarbons (HCFCs)|A5.508.1.3||||| |(continued)
    DIVISION 5.5
    Environmen-
    tal
    Quality|Select One|Elective|Hydrofluorocarbons (HFCs)|A5.508.1.4||||| |Additional
    Measures|Additional
    Measures||Select 1 additional measure from any division|Add section #||||| |Total number of Measures required|Total number of Measures required|Total number of Measures required|Total number of Measures required|15||||| |Total number of Measures selected|Total number of Measures selected|Total number of Measures selected|Total number of Measures selected||||||

    Documentation Author's / Responsible Designer's Declaration Statement
    Check the appropriate box(es) for the list below.
    □ Mandatory: I attest that the mandatory provisions checklist is accurate and complete.
    □ Tier 1 compliant: I attest that the total number of voluntary measures selected meet or exceed the total number required
    to achieve Tier 1 compliance.
    □ Partial Tier 1 compliant: I attest that the total number of voluntary measures selected do not meet the total number
    required to achieve Tier 1 compliance: however, partial Tier 1 compliance has been achieved.
    Col2
    Signature:
    Company: Date:
    Address: License:
    City/State/Zip: Phone:

    APPENDIX A5-54 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    A5.602.2

    CALGreen VERIFICATION GUIDELINES

    TIER 2 CHECKLIST

    Application: This checklist shall be used for nonresidential projects that meet the following: new construction, or building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3, AND are adopting Tier 2 voluntary measures.

    Note: All applicable mandatory requirements in Chapter 5 shall be met prior to applying Tier 2 voluntary measures.

    Instructions:

    Comply with all Tier 2 prerequisite measures from the various categories shown on the table below.

    Add a “ Y ” to all mandatory and Tier 2 prerequisite measures in the appropriate columns.

  • CALGreen § 5.508.2 High relevance — show source text

    000 square feet or more|5.508.2
    through
    5.508.2.6.3||||| |||END OF MANDATORY PROVISIONS||||||

    Documentation Author's / Responsible Designer's Declaration Statement
    □ Mandatory: I attest that this mandatory provisions checklist is accurate and complete.
    Col2
    Signature: Signature:
    Company: Date:
    Address: License:
    City/State/Zip: Phone:

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-47

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    A5.602.1

    CALGreen VERIFICATION GUIDELINES

    TIER 1 CHECKLIST

    Application: This checklist shall be used for nonresidential projects that meet the following: new construction, or building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3, AND are adopting Tier 1 voluntary measures.

    Note: All applicable mandatory requirements in Chapter 5 shall be met prior to applying Tier 1 voluntary measures.

    Instructions:

    Comply with all Tier 1 prerequisite measures from the various categories shown on the table below.

    Add a “ Y ” to all mandatory and Tier 1 prerequisite measures in the appropriate columns.

    Select the required number of additional electives from those categories shown on the table below and add a “ Y ” on the selected elective and add an “ N ” on the rest.

    Count the total number of Tier 1 prerequisite measures plus the additional electives and write down the total number at the end of the checklist. Determine if the required number of Tier 1 measures have been selected to achieve Tier 1 compliance.

    Y = Yes (section has been selected and/or included) N = No (section has not been selected and/or included) O = Other (provide explanation)

    [N] = New construction pursuant to Section 301.3

    [A] = Additions and/or Alterations pursuant to Section 301.3

    CHAPTER 5
    DIVISIONS
    Col2 SECTION TITLE CODE
    SECTION
    Y N O PLAN SHEET,
    SPEC OR
    ATTACH
    DIVISION 5.1
    Planning and
    Design
    (continued)
    Mandatory Deconstruction and reuse of existing structures,
    Scope with Exception
    5.105.1
    DIVISION 5.1
    Planning and
    Design
    (continued)
    Mandatory Reuse of existing building & Verification of compliance with note 5.105.2 and 5.105.2.1
    DIVISION 5.1
    Planning and
    Design
    (continued)
    Mandatory Storm water pollution prevention for projects that disturb
    less than 1 acre of land
    5.106.1 through
    5.106.2
    DIVISION 5.1
    Planning and
    Design
    (continued)
    Mandatory Short-term bicycle parking 5.106.4.1.
  • CALGreen § 0.5 High relevance — show source text

    in.|≤ 100 sq. in. =
    D-H-90
    >100 sq. in.=
    D-H-W-90|Not
    Permitted|2|Not
    Permitted|W-120| |Double fire walls
    constructed in
    accordance with
    NFPA 221|2|1|1|100 sq. in.|≤ 100 sq. in. =
    D-H-60
    > 100 sq. in. =
    D-H-W-60|Not
    Permitted|1|Not
    Permitted|W-60| |Enclosures for
    shafts, interior exit
    stairways and inte-
    rior exit ramps.|2|2|11/ 2|100 sq. in.b|≤100 sq. in. =
    D-H-90
    > 100 sq. in.=
    D-H-T-W-90|Not
    Permitted|2|Not
    Permitted|W-120| |Horizontal exits in
    fire wallsg|4|4|3|100 sq. in.|≤100 sq. in. =
    D-H-180
    > 100 sq. in.=
    D-H-W-240|Not
    Permitted|4|Not
    Permitted|W-240| |Horizontal exits in
    fire wallsg|3|3|3d|100 sq. in.|≤100 sq. in. =
    D-H-180
    > 100 sq. in.=
    D-H-W-180|Not
    Permitted|3|Not
    Permitted|W-180| |Fire barriers having
    a required fire-
    resistance rating of
    1 hour: Enclosures
    for shafts, exit
    access stairways,
    exit access ramps,
    interior exit stair-
    ways and interior
    exit ramps; and exit
    passageway walls|1|1|1|100 sq. in.|≤100 sq. in. =
    D-H-60
    >100 sq. in.=
    D-H-T-W-60|Not
    Permitted|1|Not
    Permitted|W-60| |||||||Fire protection|Fire protection||| |Other fire barriers|1|1|3/ 4|Maximum
    size tested|D-H-45|3/ 4
    h|3/ 4
    h|D-H-45h|D-H-45h| |Fire partitions:
    Corridor walls|1|1|1/ 3
    a|Maximum
    size tested|D-20|3/ 4
    a|3/ 4
    a|D-H-OH-45|D-H-OH-45| |Fire partitions:
    Corridor walls|0.5|0.5|1/ 3
    a|Maximum
    size tested|D-20|1/ 3|1/ 3|D-H-OH-20|D-H-OH-20|

    7-28 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    |TABLE 716.1(2)—OPENING FIRE PROTECTION ASSEMBLIES,

  • CALGreen § 8-6 High relevance — show source text

    . . . . . . . . . . . . . . . 8-6 Worksheet (WS-9) 5.409.2 and A5.409.2 Whole Building Life Cycle Assessment: . . . . . . . . . . . . . . . . 8-7 Construction Waste Management (CWM) Plan . . . . . . . . . . . 8-8 Construction Waste Management (CWM) Worksheet. . . . . . 8-9 Construction Waste Management (CWM) Acknowledgment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10 Title 23, Waters, California Code of Regulations . . . . . . . . . 8-11 Commissioning Referenced Standards for Non-energy Systems. . . . . . . . . . . . . . . . . . . . . . . . . 8-13 IES TM-15-11 Table A-1, Table 130.2-A and Table 130.2-B Uplight and Glare Ratings Tables. . . . . . . . . . . . . . 8-40

    APPENDIX A4 RESIDENTIAL

    VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A4-3

    A4.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A4-3 A4.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . APPENDIX A4-9 A4.3 Water Efficiency and Conservation . . . APPENDIX A4-13 A4.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A4-15 A4.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A4-19 A4.6 Tier 1 and Tier 2 . . . . . . . . . . . . . . . . . . . . APPENDIX A4-21

    Division A4.6—Residential Occupancies Application Checklist . . . . . . . . . . . . . APPENDIX A4-23 A4.7 Residential Model Ordinance . . . . . . . . . APPENDIX A4-31

    APPENDIX A5 NONRESIDENTIAL

    VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3

  • CALGreen § 207.1 High relevance — show source text

    Exceptions:

    1. Heat rejection devices included as an integral part of the equipment listed in Tables A6.207.1-A through A6.207.1-E.
    2. Condenser fans serving multiple refrigerant circuits.
    3. Condenser fans serving flooded condensers.
    4. Up to [1] / 3 of the fans on a condenser or tower with multiple fans where the lead fans comply with the speed control requirement.

    A6.207.2.3.3 Tower flow turndown. Open cooling towers configured with multiple condenser water pumps shall be designed so that all cells can be run in parallel with the larger of:

    1. The flow that’s produced by the smallest pump or
    2. 33 percent of the design flow for the cell.

    A6.207.2.3.4 Limitation on centrifugal fan cooling towers. Open cooling towers with a combined rated capacity of 900 gpm and greater at 95°F condenser water return, 85°F condenser water supply and 75°F outdoor wet-bulb temperature shall use propeller fans and shall not use centrifugal fans.

    Exceptions:

    1. Cooling towers that are ducted (inlet or discharge) or have an external sound trap that requires external static pressure capability.
    2. Cooling towers that meet the energy efficiency requirement for propeller fan towers in Section A6.207.1, Table A6.207.1-G.

    APPENDIX A6.1-18 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A6.1VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

    A6.207.2.4 Hydronic system measures.

    A6.207.2.4.1 Hydronic variable flow systems. HVAC chilled and hot water pumping shall be designed for variable fluid flow and shall be capable of reducing pump flow rates to no more than the larger of: a) 50 percent or less of the design flow rate; or b) the minimum flow required by the equipment manufacturer for the proper operation of equipment served by the system.

    Exceptions:

    1. Systems that include no more than three control valves.
    2. Systems having a total pump system power less than or equal to 1 [1] / 2 HP.

    A6.207.2.4.2 Chiller isolation. When a chilled water plant includes more than one chiller, provisions shall be made so that flow through any chiller is automatically shut off when that chiller is shut off while still maintaining flow through other operating chiller(s). Chillers that are piped in series for the purpose of increased temperature differential shall be considered as one chiller.

    A6.207.2.4.3 Boiler isolation. When a hot water plant includes more than one boiler, provisions shall be made so that flow through any boiler is automatically shut off when that boiler is shut off while still maintaining flow through other operating boiler(s).

    A6.207.2.4.4 Chilled and hot water temperature reset controls. Chilled and hot water systems with a design capacity exceeding 500,000 Btu/hr supplying chilled or heated water (or both) shall include controls that automatically reset supply water temperatures as a function of representative building loads or outside air temperature.

    Exception: Hydronic systems that use variable flow to reduce pumping energy in accordance with Section A6.207.2.4.1.

  • CALGreen § 3.1. High relevance — show source text
    1. From Division A4.3, Water Efficiency and Conservation. 3.1. Comply with at least three elective measures selected from Division A4.3.
    2. From Division A4.4, Material Conservation and Resource Efficiency. 4.1. Comply with the 25 percent cement reduction requirements in Section A4.403.2. 4.2. Comply with the 15 percent recycled content requirements in Section A4.405.3.1. 4.3. Comply with the 75 percent reduction in construction waste in Section A4.408.1. 4.4. Comply with at least four elective measures selected from Division A4.4.
    3. From Division A4.5, Environmental Quality. 5.1. Comply with the 100 percent resilient flooring systems requirements in Section A4.504.2. 5.2. Comply with the thermal insulation requirements for Tier 1 and Tier 2 in Section A4.504.3. 5.3. Comply with at least one elective measure selected from Division A4.5.

    Note: The Residential Occupancies Application Checklist contained in Section A4.602 may be used to show which elective measures are selected.

    APPENDIX A4-22 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    DIVISION A4.6 – TIER 1 AND TIER 2

    SECTION A4.602 RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST

    FEATURE OR MEASURE LEVELS
    APPLICANT TO SELECT ELECTIVE MEASURES
    Col3 Col4 VERIFICATIONS
    ENFORCING AGENCY TO SPECIFY
    VERIFICATION METHOD
    Col6 Col7
    FEATURE OR MEASURE Mandatory Prerequisites and electives1 Prerequisites and electives1 Enforcing
    Agency

    All
    Installer or
    Designer

    All
    Third
    party

    All
    FEATURE OR MEASURE Mandatory Tier 1 Tier 2 Tier 2 Tier 2 Tier 2
    PLANNING AND DESIGN
    Site Selection
    A4.103.1 A site which complies with at least one of the following
    characteristics is selected:
    1. An infill site is selected.
    2. A greyfield site is selected.
    3. An EPA-recognized Brownfield site is selected.










    A4.103.2 Facilitate community connectivity by one of the following
    methods:
    1. Locate project within a1/4-mile true walking distance of at least 4
    basic services;
    2.
  • CALGreen § 1023.7 High relevance — show source text

    In each case, openings into the fire-resistance-rated construction shall be limited to those needed for maintenance and operation and shall be protected by opening protectives in accordance with Section 716 of the California Building Code for shaft enclosures.

    The interior exit stairway and ramp ventilation systems shall be independent of other building ventilation systems.

    [BE] 1023.7 Interior exit stairway and ramp exterior walls. Exterior walls of the interior exit stairway or ramp shall comply with the requirements of Section 705 of the California Building Code for exterior walls. Where nonrated walls or unprotected openings enclose the exterior of the stairway or ramps and the walls or openings are exposed by other parts of the building at an angle of less than 180 degrees (3.14 rad), building construction within 10 feet (3048 mm) of the exterior walls of the interior exit stairway or ramp shall comply with Sections 1023.7.1 and 1023.7.2.

    2025 CALIFORNIA FIRE CODE 10-47

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    [BE] 1023.7.1 Building exterior walls. Building exterior walls within 10 feet (3048 mm) horizontally of a nonrated wall or unprotected opening in an interior exit stairway or ramp shall have a fire-resistance rating of not less than 1 hour. Openings within such exterior walls shall be protected by opening protectives having a fire protection rating of not less than [3] / 4 hour. This construction shall extend vertically from the ground to a point 10 feet (3048 mm) above the topmost landing of the stairway or ramp, or to the roof line, whichever is lower.

    [BE] 1023.7.2 Roof assemblies. Where the interior exit stairway or ramp extends above an adjacent roof of the same building, the adjacent roof assembly shall have a fire-resistance rating of not less than 1 hour and openings shall be protected by opening protectives having a fire protection rating of not less than [3] / 4 hour. The fire-resistance rating and opening protection shall extend horizontally not less than 10 feet (3048 mm) from the exterior wall of the stairway or ramp, or to the perimeter of the adjacent roof, whichever is less.

    Exceptions:

    1. The roof assembly need not be rated and openings in the roof need not be protected where they are adjacent to the penthouse of the stairway or ramp, unless otherwise required by this code.
    2. The adjacent roof assembly need not be rated and adjacent openings in the roof need not be protected where the exterior wall of the stairway or ramp has a fire-resistance rating of 1 hour and openings are protected by opening protectives having a fire protection rating of not less than [3] / 4 hour, extending not less than 10 feet (3048 mm) above the roof.

    [BE] 1023.8 Barriers at level of exit discharge. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1013.

  • CALGreen § 207.1 High relevance — show source text

    APPENDIX A6.1VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

    TABLE A6.207.1-D—WATER CHILLING PACKAGES—MINIMUM EFFICIENCY REQUIREMENTS Col2 Col3 Col4
    EQUIPMENT TYPE SIZE CATEGORY EFFICIENCY TEST PROCEDURE
    Air cooled, with condenser < 150 Tons 2.80 COP ARI 550/590
    Electrically operated ≥ 150 Tons 3.05 IPLV 3.05 IPLV
    Air cooled, without condenser All Capacities 3.10 COP
    Electrically operated Electrically operated 3.45 IPLV 3.45 IPLV
    Water cooled, electrically operated, positive displacement All Capacities 4.20 COP ARI 550/590
    (Reciprocating) (Reciprocating) 5.05 IPLV 5.05 IPLV
    Water cooled, < 150 Tons
    4.45 COP ARI 550/590
    Water cooled, < 150 Tons
    5.20 IPLV 5.20 IPLV
    Electrically operated, ≥ 150 Tons and 4.90 COP 4.90 COP
    Positive displacement < 300 Tons
    ≥ 300 Tons
    5.60 IPLV 5.60 IPLV
    Positive displacement < 300 Tons
    ≥ 300 Tons
    5.50 COP 5.50 COP
    (Rotary screw and scroll) 6.15 IPLV 6.15 IPLV
    Water cooled, electrically operated, centrifugal < 150 Tons 5.00 COP ARI 550/590
    Water cooled, electrically operated, centrifugal < 150 Tons 5.25 IPLV 5.25 IPLV
    Water cooled, electrically operated, centrifugal ≥ 150 Tons and
    < 300 Tons
    5.55 COP 5.55 COP
    Water cooled, electrically operated, centrifugal ≥ 150 Tons and
    < 300 Tons
    5.90 IPLV 5.90 IPLV
    Water cooled, electrically operated, centrifugal ≥ 300 Tons 6.10 COP 6.10 COP
    Water cooled, electrically operated, centrifugal ≥ 300 Tons 6.40 IPLV 6.40 IPLV
    Air cooled absorption, single effect All Capacities 0.60 COP ARI 560
    Water cooled absorption, single effect All Capacities 0.70 COP 0.70 COP
    Absorption double effect, indirect-fired All Capacities 1.00 COP 1.00 COP
    Absorption double effect, indirect-fired All Capacities 1.05 IPLV 1.05 IPLV
    Absorption double effect, direct-fired All Capacities 1.00 COP 1.00 COP
    Absorption double effect, direct-fired All Capacities 1.00 IPLV 1.00 IPLV
    Water cooled gas engine driven chiller All Capacities 1.2 COP ANSI Z21.40.4
    Water cooled gas engine driven chiller All Capacities 2.0 IPLV 2.0 IPLV

    |TABLE A6.207.

  • CALGreen § 504.8.5.2 High relevance — show source text

    A6.504.8.5.2 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following:

    1. Product certifications and specifications.
    2. Chain of custody certifications.
    3. Other methods acceptable to the enforcing agency.

    A6.504.9 Environmental tobacco smoke (ETS) control. [OSHPD 1, 2 & 4] Where outdoor areas are provided for smoking, prohibit smoking within 25 feet of building entries, outdoor air intakes and operable windows and within the building, if not already prohibited by other laws or regulations, or as enforced by ordinances, regulations or policies of any city, county, city and county, California Community College, campus of the California State University or campus of the University of California, whichever are more stringent. When ordinances, regulations or policies are not in place, post signage to inform building occupants of the prohibitions.

    SECTION A6.505 [OSHPD 1, 2 & 4]—INDOOR MOISTURE CONTROL

    A6.505.2 Indoor moisture control. Buildings shall meet or exceed the provisions of California Building Code, CCR, Title 24, Part 2, Sections 1203 and Chapter 14.

    APPENDIX A6.1-36 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A6.1VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

    NONRESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST [OSHPD 1, 2 and 4]

    FEATURE OR MEASURE COMPLIANCE LEVELS Col3 Col4 NOTES
    FEATURE OR MEASURE Mandatory
    CALGreen
    VOLUNTARY
    CALGreen
    VOLUNTARY
    CALGreen
    VOLUNTARY
    CALGreen
    FEATURE OR MEASURE Mandatory
    CALGreen
    Tier 1 Tier 2 Tier 2
    DIVISION A6.1 – PLANNING AND DESIGN
    SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development
    **A6.106.9 Building orientation.**Locate and orient the building as follows:
    1. When site and location permit, orient the building with the long sides facing north and
    south.
    2. Protect the building from thermal loss, drafts and degradation of the building envelope
    caused by wind and wind-driven materials such as dust.
    DIVISION A6.2 – ENERGY EFFICIENCY
    SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures
    A6.203.1 Energy performance. [OSHPD 1]
    **A6.203.1.1 CALGreen Tier 1.
  • CALGreen § 65080.1 High relevance — show source text

    (2) be consistent with the prevailing sustainable communities strategy or alternative planning strategy, whichever meets the greenhouse gas target established by the California Air Resources Board, including the general location of uses, residential densities and building intensities; and

    (3) have all necessary entitlements required by the applicable local government.

    Note: For additional information, see Government Code Sections 65080, 65080.1 and 65400 and Public Resources Code Sections 21061.3 and 21155.

    SECTION A5.101—GENERAL

    A5.101.1 Scope. The provisions of this chapter outline planning, design and development methods that include environmentally responsible site selection, building design, building siting and development to protect, restore and enhance the environmental quality of the site and respect the integrity of adjacent properties.

    SECTION A5.102—DEFINITIONS

    A5.102.1 Definitions. The following terms are defined in Chapter 2.

    2 X 2 RULE.

    ADHESIVE MARKER.

    BIORETENTION.

    BROWNFIELD SITE.

    CAV.

    DEVELOPMENT FOOTPRINT.

    FILM.

    FLOOR AREA RATIO.

    GLASS, ACID ETCHED. GLASS, FRITTED.

    GLASS SURFACE.

    GREENFIELDS.

    GREYFIELD SITE.

    INFILL SITE.

    LOW-EMITTING AND FUEL EFFICIENT VEHICLES.

    LOW IMPACT DEVELOPMENT (LID).

    MATURE TREE CANOPY.

    PERMEABLE PAVING.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    SOLAR REFLECTANCE.

    SOLAR REFLECTANCE INDEX (SRI).

    THERMAL EMITTANCE.

    ULTRAVIOLET (UV).

    VANPOOL VEHICLE.

    VEGETATED SPACE.

    VISUAL MARKER.

    SECTION A5.103—SITE SELECTION

    A5.103.1 Community connectivity. Where feasible, locate project on a previously developed site within a [ 1] / 2 mile radius of at least ten basic services, readily accessible by pedestrians, including, but not limited, to one each of bank, place of worship, convenience grocery, day care, cleaners, fire station, barber shop, beauty shop, hardware store, laundry, library, medical clinic, dental clinic, senior care facility, park, pharmacy, post office, restaurant (two may be counted), school, supermarket, theater, community center, fitness center, museum or farmers market. Other services may be considered on a case-by-case basis.

    A5.103.2 Brownfield or greyfield site redevelopment or infill area development. If feasible, select for development a brownfield in accordance with Section A5.103.2.1 or on a greyfield or infill site as defined in Section A5.102.

  • CALGreen § 3103F.3 High relevance — show source text

    Major equipment weight shall be established and added into this weight_
    for piping manifold, valves, deck crane, fire monitor tower, gangway structure and similar ma/or equipment.
    *** pounds per square foot|*
    Allowance for incidental items such as railings, lighting, miscellaneous equipment, etc.
    **35 psf is for miscellaneous general items such as walkways, pipe supports, lighting and instrumentation. Major equipment weight shall be established and added into this weight
    for piping manifold, valves, deck crane, fire monitor tower, gangway structure and similar ma/or equipment.
    *** pounds per square foot|

    3103F.3 Live loads and buoyancy. The following vertical live loading shall be considered, where appropriate: uniform loading, truck loading, crane loading and buoyancy. Additionally, MOT specific, nonpermanent equipment shall be identified and used in loading computations.

    3103F.4 Earthquake loads.

    3103F.4.1 General. Earthquake loads are described in terms of Peak Ground Acceleration (PGA), spectral acceleration and earth- quake magnitude. The required seismic analysis procedures (Tables 31F-4-1 and 31F-4-2) are dependent on the spill classification obtained from Table 31F-1-1.

    3103F.4.2 Design earthquake motion parameters. The earthquake ground motion parameters of peak ground acceleration, spec- tral acceleration and earthquake magnitude are modified for site amplification and near fault directivity effects. The resulting values are the Design Peak Ground Acceleration (DPGA), Design Spectral Acceleration (DSA) and Design Earthquake Magnitude (DEM).

    For Site Classes A through E (Section 3103F.4.2.1), peak ground and design spectral accelerations shall be obtained from: 1. U.S. Geological Survey (USGS) published data as discussed in Section 3103F.4.2.2, or 2. A site-specific probabilistic seismic hazard analysis (PSHA) as discussed in Section 3103F.4.2.3.

    Site-specific PSHA is required for Site Class F.

    Unless stated otherwise, the DSA values are for 5 percent damping; values at other levels may be obtained as per Section 3103F.4.2.9.

    2025 CALIFORNIA BUILDING CODE 31F-19

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MARINE OIL TERMINALS

    The appropriate probability levels associated with DPGA and DSA for different seismic performance levels are provided in Table 31F-4-1. Deterministic earthquake motions, which are used only for comparison to the probabilistic results, are addressed in Section 3103F.4.2.7.

    The evaluation of Design Earthquake Magnitude (DEM), is discussed in Section 3103F.4.2.8. This parameter is required when accel- eration time histories (Section 3103F.4.2.10) are addressed or if liquefaction potential (Section 3106F.4) is being evaluated.

    3103F.4.2.1 Site classes. The following Site Classes, defined in Section 3106F.2.1, shall be used in developing values of DSA and DPGA:

    A, B, C, D, E and F

    For Site Class F, a site-specific response analysis is required per Section 3103F.4.2.5.

  • CALGreen § 101.7 High relevance — show source text

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    A5 NONRESIDENTIAL VOLUNTARY MEASURES

    The measures contained in this appendix are not mandatory unless adopted by a city, county, or city and county as specified in Section 101.7 and provide additional measures that designers, builders and property owners may wish to consider during the planning, design and construction process.

    DIVISION A5.1 – PLANNING AND DESIGN

    PREFACE

    Given that land use and planning are largely regulated locally, cities, counties and cities and counties should consider reducing greenhouse gas emissions associated with development through local land-use practices in conjunction with enforcing the provisions of this code. Specific land use strategies a city, county or city and county may wish to consider include but are not limited to the following:

    Site selection. Develop sites for buildings, hardscape, roads or parking areas consistent with the local general plan and regional transportation plan pursuant to SB 375 (Stats. 2008, Ch. 728).

    Regional sustainable communities strategy. Site selection and building design and use shall conform the project with the prevailing regional sustainable communities strategy or alternative planning strategy, whichever meets the greenhouse gas target established by the California Air Resources Board pursuant to SB375 (Stats. 2008, Ch. 728), including the general location of uses, residential densities and building intensities.

    Transit priority projects. To qualify as a transit priority project, the project shall meet three criteria:

    (1) (a) contain at least 50 percent residential use, based on total building square footage and, if the project contains between 26 and 50 percent nonresidential uses, a floor area ratio of not less than 0.75; (b) provide a minimum net density of at least 20 dwelling units per acre; and (c) be within one-half mile of a major transit stop or high-quality transit corridor included in a regional transportation plan as described in Section 21155 of Stats. 2008, Ch. 728;

    (2) be consistent with the prevailing sustainable communities strategy or alternative planning strategy, whichever meets the greenhouse gas target established by the California Air Resources Board, including the general location of uses, residential densities and building intensities; and

    (3) have all necessary entitlements required by the applicable local government.

    Note: For additional information, see Government Code Sections 65080, 65080.1 and 65400 and Public Resources Code Sections 21061.3 and 21155.

    SECTION A5.101—GENERAL

    A5.101.1 Scope. The provisions of this chapter outline planning, design and development methods that include environmentally responsible site selection, building design, building siting and development to protect, restore and enhance the environmental quality of the site and respect the integrity of adjacent properties.

    SECTION A5.102—DEFINITIONS

    A5.102.1 Definitions. The following terms are defined in Chapter 2.

    2 X 2 RULE.

    ADHESIVE MARKER.

    BIORETENTION.

    BROWNFIELD SITE.

    CAV.

    DEVELOPMENT FOOTPRINT.

    FILM.

    FLOOR AREA RATIO.

    GLASS, ACID ETCHED. GLASS, FRITTED.

    GLASS SURFACE.

  • CALGreen § 101.7 High relevance — show source text

    The state agency does not adopt sections identified by the following symbol: †.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A4-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A4-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    A4 RESIDENTIAL VOLUNTARY MEASURES

    Some of the measures contained in this appendix are not mandatory unless adopted by a city, county, or city and county as specified in Section 101.7 and provide additional measures that designers, builders and property owners may wish to consider during the planning, design and construction process.

    DIVISION A4.1 – PLANNING AND DESIGN

    PREFACE

    Given that land use and planning are largely regulated locally, cities, counties, and cities and counties should consider reducing greenhouse gas emissions associated with development through local land-use practices in conjunction with enforcing the provisions of this code. Specific land use strategies a city, county, or city and county may wish to consider include but are not limited to the following:

    Site selection. Develop sites for buildings, hardscape, roads or parking areas consistent with the local general plan and regional transportation plan pursuant to SB 375 (Stats 2008, Ch. 728).

    Regional sustainable communities strategy. Site selection and building design and use shall conform the project with the prevailing regional sustainable communities strategy or alternative planning strategy, whichever meets the greenhouse gas target established by the California Air Resources Board pursuant to SB 375 (Stats. 2008, Ch. 728), including the general location of uses, residential densities and building intensities.

    Transit priority projects. To qualify as a transit priority project, the project shall meet three criteria:

    (1) (a) contain at least 50 percent residential use, based on total building square footage and, if the project contains between 26 and 50 percent nonresidential uses, a floor area ratio of not less than 0.75; (b) provide a minimum net density of at least 20 dwelling units per acre; and (c) be within one-half mile of a major transit stop or high-quality transit corridor included in a regional transportation plan as described in Section 21155 of Stats. 2008, Ch. 728;

    (2) be consistent with the prevailing sustainable communities strategy or alternative planning strategy, whichever meets the greenhouse gas target established by the California Air Resources Board, including the general location of uses, residential densities and building intensities; and

    (3) have all necessary entitlements required by the applicable local government.

    Note: For additional information, see Government Code Sections 65080, 65080.1, 65400 and 65470, and Public Resources Code Sections 21061.3 and 21155.

    SECTION A4.101—GENERAL

    A4.101.1 Scope. The provisions of this division outline planning, design and development methods that include environmentally responsible site selection, building design, building siting and development to protect, restore and enhance the environmental quality of the site and respect the integrity of adjacent properties.

    SECTION A4.102—DEFINITIONS

    A4.102.1 Definitions. The following terms are defined in Chapter 2.

    BROWNFIELD SITE.

    DEVELOPMENT FOOTPRINT.

    GREENFIELDS.

    GREYFIELD SITE.

  • CALGreen § 7.12 High relevance — show source text

    SECTION 303 A RESERVED

    SECTION 304 A —STRUCTURAL DESIGN LOADS AND EVALUATION AND DESIGN PROCEDURES

    304 A .1 Live loads. Where an addition or alteration does not result in increased design live load, existing gravity load-carrying structural elements shall be permitted to be evaluated and designed for live loads approved prior to the addition or alteration. If the approved live load is less than that required by Section 1607 A of the California Building Code, the area designated for the nonconforming live load shall be posted with placards of approved design indicating the approved live load. Where the addition or alteration results in increased design live load, the live load required by Section 1607 A of the California Building Code shall be used.

    304 A .2 Snow loads on adjacent buildings. Where an alteration or addition changes the potential snow drift effects on an adjacent building, the code official is authorized to enforce Section 7.12 of ASCE 7.

    304 A .3 Additions, alterations, repairs and seismic retrofit to existing buildings or structures.

    304 A .3.1 Structures designed in accordance with pre-1973 building code. Provisions of this section shall apply to hospital build- ings which were originally designed to pre-1973 building codes and not designated as SPC 3 or higher in accordance with Chapter 6 of the California Administrative Code.

    304A.3.1.1 Incidental and minor structural alteration, additions, or repairs. Incidental and minor structural additions shall be permitted, provided the additions meet the California Building Code for new construction using importance factor, I e , equal to or greater than 1.0. Alterations or repair to existing gravity and lateral force-resisting systems shall be made to conform to the requirements of Section 503A or Chapter 4A, respectively, using importance factor, I e , equal to or greater than 1.0. 1. Nonstructural components. Component importance factor, I p , shall be permitted to be 1.0.

    Exception: Components required for life-safety purposes after an earthquake, including emergency and standby power systems, mechanical smoke removal systems, fire protection sprinkler systems, fire alarm control panels and egress stairways shall have a component importance factor (I p ) of 1.5.

    304A.3.1.2 Major structural alteration, additions or repairs. Major structural alterations, additions or repairs shall be in accor- dance with Section 304A.3.4.1 or 304A.3.4.3 as applicable.

    304A.3.2 Seismic evaluation and retrofit of general acute care hospitals for compliance with the California Administrative Code, Chapter 6. Notwithstanding any other requirements of this code, existing general acute care hospitals shall comply with the seismic evaluation requirements specified in Chapter 6, of the California Administrative Code, when applicable. Seismic retrofit to comply with requirements specified in Chapter 6 of the California Administrative Code shall be permitted to be in accordance with these provisions. When load combinations which do not include seismic forces are required, the new building provisions of this code shall be applicable.

  • CALGreen § 7-104 High relevance — show source text
    1. Section 7-104 in the California Administrative Code for the Office of the Statewide Health Planning and Development.

    1-4 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ADMINISTRATION

    101.9 Effective date of this code. Only those standards approved by the California Building Standards Commission that are effective at the time an application for a building permit is submitted shall apply to the plans and specifications for, and to the construction performed under, that permit. For the effective dates of the provisions contained in this code, see the appropriate application checklist and the History Note page of this code.

    101.10 Mandatory requirements. This code contains both mandatory and voluntary green building measures. Mandatory and voluntary measures are identified in the appropriate application checklist contained in this code.

    101.11 Effective use of this code. The following steps shall be used to establish which provisions of this code are applicable to a specific occupancy:

    1. Establish the type of occupancy.
    2. Verify which state agency has authority for the established occupancy by reviewing the authorities list in Sections 103 through 106.
    3. Once the appropriate agency has been identified, find the chapter which covers the established occupancy.
    4. The Matrix Adoption Tables at the beginning of Chapters 4 and 5 identify the mandatory green building measures necessary to meet the minimum requirements of this code for the established occupancy.
    5. Voluntary tier measures are contained in Appendix Chapters A4 and A5. A checklist containing each green building measure, both required and voluntary, is provided at the end of each appendix chapter. Each measure listed in the application checklist has a section number which correlates to a section where more information about the specific measure is available.
    6. The application checklist identifies which measures are required by this code and allows users to check off which voluntary items have been selected to meet voluntary tier levels if desired or mandated by a city, county, or city and county.

    SECTION 102—CONSTRUCTION DOCUMENTS AND INSTALLATION VERIFICATION

    102.1 Submittal documents. Construction documents and other data shall be submitted in one or more sets with each application for a permit. Where special conditions exist, the enforcing agency is authorized to require additional construction documents to be prepared by a licensed design professional and may be submitted separately.

    Exception: The enforcing agency is authorized to waive the submission of construction documents and other data not required to be prepared by a licensed design professional.

    102.2 Information on construction documents. Construction documents shall be of sufficient clarity to indicate the location, nature and scope of the proposed green building feature and show that it will conform to the provisions of this code, the California Building Standards Code and other relevant laws, ordinances, rules and regulations as determined by the enforcing agency.

    102.3 Verification. Documentation of conformance for applicable green building measures shall be provided to the enforcing agency. Alternate methods of documentation shall be acceptable when the enforcing agency finds that the proposed alternate documentation is satisfactory to demonstrate substantial conformance with the intent of the proposed green building measure.

    [HCD] Documentation of conformance for applicable green building measures shall be provided to the enforcing agency. All projects shall submit a completed Residential Occupancies Application Checklist that includes Chapter 4 residential mandatory measures and Tier 1 or Tier 2, as applicable. References to the measure-specific documentation used to show compliance shall be included. Alternate methods of documentation shall be acceptable when the enforcing agency f

  • CALGreen § 11-01 High relevance — show source text
    1. Trench depth shall be 30 inches (minimum) with or without gas service, and greater if joint with a gas main.

    Street

    36” Min Mobile Home (see Note 4 Being Served on Page 1)

    See Note 3

    Secondary Distribution Trench

    Figure 2 Pedestal (preferred location)

    Secondary Distribution Trench Secondary Distribution Trench

    Figure 4 Pedestal (alternate location)

    36” Min., See Note 4 on Page 1

    Mobile Home Being Served

    Mobile Home Being Served

    18” Approximate

    able
    .
    Col2 Col3 Col4 Col5
    .
    able
    .
    able
    .

    Detail B Plan

    Trench (Figure 2 or Figure 3)

    Cable

    Pedestal

    Utility Island Pad

    6” Min.

    Temporary pedestal Support

    Figure 5 Pedestal

    Rev. #06: 11-01-18 052521 Page 5 of 8

    Greenbook EMWP Electrical Service Requirements for Mobile Home Developments

    Material

    Notes

    1. It is recommended that the main circuit breakers used in pedestals have a 10,000-amp short-circuit current rating to insure compliance with state and local codes. These codes require that the main breaker of service equipment be rated at the available short-circuit current. PG&E shall design its facilities to supply all new mobile home customers so that the short circuit duty at the pedestal will not exceed 10,000 amps.

    2. See Table 2 on Page 6 for a list of approved meter pedestal manufacturers and catalog numbers.

    3. Pedestals are allowed to have rear connection kit.

    Table 1 List of Material for Supplying Electric Service to Mobile Home Developments
    Item Description
    Material to Be Supplied by Applicant Material to Be Supplied by Applicant
    1 Meter Pedestal (as required, see Table 2 on Page 6 for the approved list)
    2 Conduit, Rigid Steel, Galvanized, with Pipe Strap (for bare ground wire, omit if armor clad wire is used)
    3 Hub and Clamp, Grounding (to suit Item 3)
    4 Conduit Fitting, Threaded, With Cover and Gasket (size to suit Item 3)
    5 Ground Rod (see Instruction 5B on Page 1)
    6 Ground Wire, Copper, Bare, or Armor Clad (size in accordance with applicable electrical codes and local
    requirements)
    7 Conduit and Cap (as required)
    Material to Be Furnished by PG&E Material to Be Furnished by PG&E
    8 Cable, XLP, 600-V (as required), seeDocument 039955 (see Table 2)

    Table 2 Approved Meter Pedestals [3]

  • CALGreen § 1.2 High relevance — show source text

    For questions on California state agency amendments, please refer to the contact list on page v.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE iii

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    LEGEND FOR AGENCY ADOPTIONS

    Unless otherwise noted, state agency adoptions are indicated by the following banners in the section leaders: Department of Housing and Community Development: [HCD]

    California Building Standards Commission, CALGreen: [BSC-CG]

    Division of the State Architect, Structural Safety: [DSA-SS]

    Office of Statewide Hospital Planning and Development: [OSHPD 1, 2 & 4]

    See Chapter 1, Sections 103–106 for applications regulated by the respective state agencies.

    EFFECTIVE USE OF THIS CODE

    The format of this code is common to other parts of the California Building Standards Code and contains building standards applicable to occupancies which fall under the authority of different state agencies. Occupancies and applications under the authority of a specific state agency are identified in Chapter 1, Sections 103 through 106. Sections of this code which are applicable and adopted by each state agency are identified in the Matrix Adoption Tables located at the beginning of each chapter. The following outline is provided as a guide to establish which provisions are applicable to a specific occupancy.

    1. Establish the type of occupancy.

    2. Verify which state agency has authority for the established occupancy by reviewing the authorities list in Sections 103 through

    3. Once the appropriate agency has been identified, find the chapter which covers the established occupancy.

    4. The Matrix Adoption Tables at the beginning of Chapters 4 and 5 identify the required green building measures necessary to meet the minimum requirements of this code for the established occupancy.

    5. Voluntary tier measures are contained in Appendix Chapters A4 and A5. A Checklist containing each green building measure, both required and voluntary is provided at the end of each appendix chapter. Each measure listed in the application checklist has a section number which correlates to a section where more information about the specific measure is available.

    6. The Application Checklist identifies which measures are required by this code and allows users to check-off which voluntary items have been selected to meet voluntary tier levels if desired or mandated by a city, county, or city and county.

    iv 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA CODE OF REGULATIONS, TITLE 24

    California State Agency Contact List

    The following state agencies may propose building standards for buildings, structures and applications under their authority for publication in Title 24. Notice of such proposals may be requested from each agency. See Sections 1.2 through 1.14 of the California Building Code (Part 2, T24) for detailed information on the regulatory authority of most state agencies summarized below. Note [agency acronyms] shown in banners/Matrix Adoption Tables in T24.

    Board of State and Community Corrections [BSCC] bscc.ca.gov BSCC-Mail@bscc.ca.gov

    (916) 445-5073 Local Detention Facilities

    Building Standards Commission [BSC, BSC-CG]

    dgs.ca.gov/BSC cbsc@dgs.ca.gov

    (916) 263-0916 State Buildings including UC & CSU Nonresidential Green Buildings Standards

    Department of Consumer Affairs Boards/Bureaus:

    Acupuncture Board [CA]

  • CALGreen § 03-25 High relevance — show source text

    1 Current standard design and may be purchased. 2

    3

    4 Use for replacement only and may be purchased. E Included in Emergency Stock

    Rev. #27: 03-25-22 062111 Page 17 of 26

    UG-1: Transformers Greenbook Application of Underground Distribution Transformers EDM

    Designation of Voltage Ratings of Windings - Single-Phase Transformers

    Table 47 Designation of Voltage Ratings of Windings − Single-Phase Transformers

    Item Designation Typical Voltage
    Rating
    Typical Winding
    Diagram
    Description
    1 E 12,000 Indicates a winding of E volts which is suitable
    for delta connection on an E volt system.
    2 E/E1Y 1 2,400/4,160Y Indicates a winding of E volts which is suitable
    for delta connection on an E volt system or for
    wye connection on an E1 volt system.
    3 E/E1Grd.Y1 12,000/20,780 Grd. Y
    or
    2,400/4,160 Grd.Y
    Indicates a winding of E volts having insulation
    suitable for delta connection on an E volt system
    or for wye connection on an E1 volt effectively
    grounded system.
    4 E1Grd.Y/E1 20,780 Grd. Y/12,000
    or
    12,000 Grd. Y/6,930
    Indicates a winding of E volts which has one
    end of the winding grounded internally. Windings
    with one end grounded internally are suitable for
    single-phase or wye operation on a three-phase
    E1 volt effectively grounded system.
    5 E/2E 120/240
    or
    240/480
    Indicates a winding, the sections of which can
    be connected in parallel for operation at E volts,
    connected in series for operation at 2E volts, or
    connected in series with a center terminal for
    3-wire operation at 2E volts between the
    extreme terminals and E volts between the
    center terminal and each of the extreme
    terminals.
    6 2E/E 240/120 Indicates a winding having a mid-tap and
    suitable for 3-wire operation at 2E volts between
    extreme terminals and at E volts between the
    mid-tap and each of the extreme terminals
    (not reconnectable).

    1 E 1 � 3 E

    062111 Page 18 of 26 Rev. #27: 03-25-22

    UG-1: Transformers Greenbook Application of Underground Distribution Transformers EDM

    Designation of Voltage Ratings of Windings Three-Phase Transformers

    Table 48 Designation of Voltage Ratings of Windings − Three-Phase Transformers

    Item Designation Typical Voltage
    Rating
    Typical Winding
    Diagram
    Description
    7 E 12,000 Indicates a winding that is permanently
    delta connected for operation on an
    E volt system.
    8 E1Grd.Y/E1 20,780
    Grd.Y/12,000
    or
    34,
  • CALGreen § 106.9 High relevance — show source text
    FEATURE OR MEASURE COMPLIANCE LEVELS Col3 Col4 NOTES
    FEATURE OR MEASURE Mandatory
    CALGreen
    VOLUNTARY
    CALGreen
    VOLUNTARY
    CALGreen
    VOLUNTARY
    CALGreen
    FEATURE OR MEASURE Mandatory
    CALGreen
    Tier 1 Tier 2 Tier 2
    DIVISION A6.1 – PLANNING AND DESIGN
    SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development
    **A6.106.9 Building orientation.**Locate and orient the building as follows:
    1. When site and location permit, orient the building with the long sides facing north and
    south.
    2. Protect the building from thermal loss, drafts and degradation of the building envelope
    caused by wind and wind-driven materials such as dust.
    DIVISION A6.2 – ENERGY EFFICIENCY
    SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures
    A6.203.1 Energy performance. [OSHPD 1]
    **A6.203.1.1 CALGreen Tier 1. [OSHPD 1]**Buildings must comply with the latest edition of
    “Savings By Design, Healthcare Modeling Procedures.”
    A.5.203.1.2 CALGreen Tier 2. [OSHPD 1] Buildings must exceed the latest edition of “Savings
    By Design, Healthcare Modeling Procedures” by 15 percent.
    SECTION A6.204 Prescriptive Measures
    **A6.204.1 ENERGY STAR equipment and appliances.**All equipment and appliances provided
    by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment
    or appliance.
    A6.204.4 Commissioning. Building commissioning for all building systems covered by T24,
    Part 6, process systems and renewable energy systems shall be included in the design and
    construction processes of the building project. Commissioning requirements shall include as
    a minimum items listed in Section A6.204.4.
    **A6.204.4.1 Owner’s Project Requirements (OPR).**Documented before the design phase of
    the project begins the OPR shall include items listed in Section A6.204.4.
    **A6.204.4.2 Basis of Design (BOD).**A written explanation of how the design of the building
    systems meets the OPR shall be completed at the design phase of the building project and
    updated periodically to cover the systems listed in Section A6.204.4.2.
    **A6.204.4.3 Commissioning plan.

Frequently asked questions

What exactly do I need to put on the site plan to satisfy the A6.1 checklist?

Show building orientation (indicate which façade is the “long side” and its compass direction), show any landscape or wind‑screening features used to protect the envelope, and reference the plan sheet on the Appendix A6.1 checklist entry for § A6.106.9 .

Is building orientation mandatory or voluntary for all projects?

Appendix A6.1 lists § A6.106.9 on the nonresidential checklist. Whether it is mandatory or enforced depends on the adopting/enforcing agency and local adoption (see the Matrix/Adoption notes for agency adoption status) .

My lot prevents perfect north–south orientation. What do I submit?

Document the site constraint, show the best feasible orientation, and show the mitigation measures (landscape, shading, intake placement). The code language of § A6.106.9 conditions the orientation requirement with “when site and location permit” — include explanation and design rationale on your plans .

Where do I find the prescriptive shading/orientation details referenced by the checklist?

The prescriptive measure § A6.204.6 refers to orientation and shading requirements in § A6.106.11; include those sections and associated calculations if using prescriptive compliance. Confirm § A6.106.11 text with the full code since it was referenced by A6.204.6 in the materials returned here .

Who verifies the A6.1 checklist?

The enforcing agency reviews the application checklist and may require the plan sheet references and supporting documentation identified on the checklist entry; the checklist is the submittal verification tool in Appendix A6.1 .

More in California Green Building Standards Code (CALGreen)

Ask about the CALGreen

Get cited, plain-English answers on the California Green Building Standards Code (CALGreen) for your project — any code section, any scenario.

Start Free Trial

Related in the CALGreen