CALGreen · California Green Building Standards Code (CALGreen)
Construction Documents & Verification
CALGreen’s Construction Documents & Verification sets what must be submitted and how green measures are documented, tested, and verified for permit approval.
Last reviewed: July 6, 2026
Overview
This portion of CALGreen (Chapter 1, Section 102) sets the rules for what green‑building information must be shown on permit submittals and how compliance must be documented for enforcement. Section 102.1 requires construction documents to be submitted with each permit application, §102.2 requires those documents to clearly show the location, nature and scope of proposed green features, and §102.3 requires documentation of conformance (with alternatives allowed where the enforcing agency accepts them) .
The code also ties verification to project delivery and commissioning: mandatory commissioning elements (Owner’s Project Requirements, Basis of Design, and a Commissioning Plan) and the requirement to show commissioning measures in the construction documents are found in Chapter 5 (for example §5.410.2 and §5.410.2.3), and functional performance testing, commissioning reports and O&M documentation are included as deliverables . CALGreen supplies compliance forms, checklists and sample templates (including verification checklists and documentation author declarations) to help applicants meet these submittal and verification requirements .
Practically, expect to provide plan notes and attachments that cross‑reference the applicable CALGreen sections, commissioning specifications and plan, completed application checklists (residential or nonresidential), product/chain‑of‑custody documentation where required, executed installation checklists, and FPT forms as part of plan intake and inspections .
In this section
Code references
Grounded in the retrieved California Green Building Standards Code (CALGreen) — click a citation to read the verbatim passage:
CALGreen § 102.1 High relevance — show source text
- The application checklist identifies which measures are required by this code and allows users to check off which voluntary items have been selected to meet voluntary tier levels if desired or mandated by a city, county, or city and county.
SECTION 102—CONSTRUCTION DOCUMENTS AND INSTALLATION VERIFICATION
102.1 Submittal documents. Construction documents and other data shall be submitted in one or more sets with each application for a permit. Where special conditions exist, the enforcing agency is authorized to require additional construction documents to be prepared by a licensed design professional and may be submitted separately.
Exception: The enforcing agency is authorized to waive the submission of construction documents and other data not required to be prepared by a licensed design professional.
102.2 Information on construction documents. Construction documents shall be of sufficient clarity to indicate the location, nature and scope of the proposed green building feature and show that it will conform to the provisions of this code, the California Building Standards Code and other relevant laws, ordinances, rules and regulations as determined by the enforcing agency.
102.3 Verification. Documentation of conformance for applicable green building measures shall be provided to the enforcing agency. Alternate methods of documentation shall be acceptable when the enforcing agency finds that the proposed alternate documentation is satisfactory to demonstrate substantial conformance with the intent of the proposed green building measure.
[HCD] Documentation of conformance for applicable green building measures shall be provided to the enforcing agency. All projects shall submit a completed Residential Occupancies Application Checklist that includes Chapter 4 residential mandatory measures and Tier 1 or Tier 2, as applicable. References to the measure-specific documentation used to show compliance shall be included. Alternate methods of documentation shall be acceptable when the enforcing agency finds that the proposed alternate documentation is satisfactory to demonstrate substantial conformance with the intent of the proposed green building measure.
Note: HCD’s Residential Occupancies Application Checklist that includes the minimum criteria for documentation is available at: http://www.hcd.ca.gov/building-standards/calgreen/cal-green-forms.shtml.
SECTION 103—BUILDING STANDARDS COMMISSION
103.1 BSC-CG. Specific scope of application of the agency responsible for enforcement, the enforcement agency, and the specific authority to adopt and enforce such provisions of this code, unless otherwise stated.
- Application— All occupancies where no state agency has the authority to adopt green building standards applicable to those occupancies. Enforcing agency— State or local agency specified by the applicable provisions of law. Authority cited— Health and Safety Code Sections 18930.5(a), 18938 and 18940.5. Reference— Health and Safety Code, Division 13, Part 2.5, commencing with Section 18901.
- Graywater systems. The construction, installation and alteration of graywater systems for indoor and outdoor uses in nonresidential occupancies. Application— All occupancies where no state agency has the authority to adopt green building standards applicable to those occupancies. Enforcing agency— State or local agency specified by the applicable provisions of law. Authority cited— Health and Safety Code Section 18941.8. Reference— Health and Safety Code Section 18941.8.
103.1.1 Adopting agency identification. The provisions of this code applicable to buildings identified in this section will be identified in the Matrix Adoption Tables under the acronym BSC-CG.
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 1-5
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ADMINISTRATION
CALGreen § 110.3.4.1 High relevance — show source text
110.3.4.1 [HCD 1] Moisture content verification. Moisture content of framing members shall be verified in accordance with the California Green Building Standards Code (CALGreen), Chapter 4, Division 4.5.
[A] 110.3.5 Types IV-A, IV-B and IV-C connection protection inspection. In buildings of Types IV-A, IV-B and IV-C construction, where connection fire-resistance ratings are provided by wood cover calculated to meet the requirements of Section 2304.10.1, inspection of the wood cover shall be made after the cover is installed, but before any other coverings or finishes are installed.
[A] 110.3.6 Lath and gypsum panel product inspection. Lath and gypsum panel product inspections shall be made after lathing and gypsum panel products, interior and exterior, are in place, but before any plastering is applied or gypsum panel product joints and fasteners are taped and finished.
Exception: Gypsum panel products that are not part of a fire-resistance-rated assembly or a shear assembly.
[A] 110.3.7 Weather-exposed balcony and walking surface waterproofing. Where balconies or other elevated walking surfaces have weather-exposed surfaces, and the structural framing is protected by an impervious moisture barrier, all elements of the impervious moisture barrier system shall not be concealed until inspected and approved.
Exception: Where special inspections are provided in accordance with Section 1705.1.1, Item 3.
[A] 110.3.8 Fire- and smoke-resistant penetrations. Protection of joints and penetrations in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall not be concealed from view until inspected and approved.
[A] 110.3.9 Energy efficiency inspections. Inspections shall be made to determine compliance with Chapter 13 and shall include, but not be limited to, inspections for: envelope insulation R- and U-values, fenestration U-value, duct system R-value, and HVAC and water-heating equipment efficiency.
[A] 110.3.10 Other inspections. In addition to the inspections specified in Sections 110.3.1 through 110.3.9, the building official is authorized to make or require other inspections of any construction work to ascertain compliance with the provisions of this code and other laws that are enforced by the department of building safety.
[A] 110.3.11 Special inspections. For special inspections, see Chapter 17.
[A] 110.3.12 Final inspection. The final inspection shall be made after all work required by the building permit is completed.
[A] 110.3.12.1 Flood hazard documentation. If located in a flood hazard area, documentation of the elevation of the lowest floor or the elevation of dry floodproofing, if applicable, as required in Section 1612.4 shall be submitted to the building official prior to the final inspection.
110.3.12.2 [HCD 1] Operation and maintenance manual. At the time of final inspection, a manual, compact disc, web-based reference or other media acceptable to the enforcing agency shall be placed in the building in accordance with the California Green Building Standards Code (CALGreen), Chapter 4, Division 4.4.
[A] 110.4 Inspection agencies. The building official is authorized to accept reports of approved inspection agencies, provided that such agencies satisfy the requirements as to qualifications and reliability.
CALGreen § 504.8.5.2 High relevance — show source text
A6.504.8.5.2 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following:
- Product certifications and specifications.
- Chain of custody certifications.
- Other methods acceptable to the enforcing agency.
A6.504.9 Environmental tobacco smoke (ETS) control. [OSHPD 1, 2 & 4] Where outdoor areas are provided for smoking, prohibit smoking within 25 feet of building entries, outdoor air intakes and operable windows and within the building, if not already prohibited by other laws or regulations, or as enforced by ordinances, regulations or policies of any city, county, city and county, California Community College, campus of the California State University or campus of the University of California, whichever are more stringent. When ordinances, regulations or policies are not in place, post signage to inform building occupants of the prohibitions.
SECTION A6.505 [OSHPD 1, 2 & 4]—INDOOR MOISTURE CONTROL
A6.505.2 Indoor moisture control. Buildings shall meet or exceed the provisions of California Building Code, CCR, Title 24, Part 2, Sections 1203 and Chapter 14.
APPENDIX A6.1-36 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A6.1 — VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]
NONRESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST [OSHPD 1, 2 and 4]
FEATURE OR MEASURE COMPLIANCE LEVELS Col3 Col4 NOTES FEATURE OR MEASURE Mandatory
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenFEATURE OR MEASURE Mandatory
CALGreenTier 1 Tier 2 Tier 2 DIVISION A6.1 – PLANNING AND DESIGN SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development **A6.106.9 Building orientation.**Locate and orient the building as follows:
1. When site and location permit, orient the building with the long sides facing north and
south.
2. Protect the building from thermal loss, drafts and degradation of the building envelope
caused by wind and wind-driven materials such as dust. DIVISION A6.2 – ENERGY EFFICIENCY SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures A6.203.1 Energy performance. [OSHPD 1]
**A6.203.1.1 CALGreen Tier 1.CALGreen § 5-26 High relevance — show source text
5-26 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL MANDATORY MEASURES
dance with this section by trained personnel with experience on projects of comparable size and complexity. For I-occupancies that are not regulated by OSHPD or for I-occupancies and L-occupancies that are not regulated by the California Energy Code Section 100.0 Scope, all requirements in Sections 5.410.2 through 5.410.2.6 shall apply.
Note: For energy-related systems under the scope (Section 100) of the California Energy Code, including heating, ventilation, air conditioning (HVAC) systems and controls, indoor lighting systems and controls, as well as water heating systems and controls, refer to California Energy Code Section 120.8 for commissioning requirements.
Commissioning requirements shall include:
- Owner’s or owner representative’s project requirements.
- Basis of design.
- Commissioning measures shown in the construction documents.
- Commissioning plan.
- Functional performance testing.
- Documentation and training.
- Commissioning report.
Exceptions:
Unconditioned warehouses of any size.
Areas less than 10,000 square feet used for offices or other conditioned accessory spaces within unconditioned warehouses.
Tenant improvements less than 10,000 square feet as described in Section 303.1.1.
Open parking garages of any size, or open parking garage areas, of any size, within a structure.
Note: For the purposes of this section, unconditioned shall mean a building, area or room which does not provide heating and/or air conditioning.
Informational Note:
- Functional performance testing for heating, ventilation, air conditioning systems and lighting controls must be performed in compliance with the California Energy Code.
5.410.2.1 Owner’s or Owner representative’s Project Requirements (OPR). [N] The expectations and requirements of the building appropriate to its phase shall be documented before the design phase of the project begins. This documentation shall include the following:
- Environmental and sustainability goals.
- Building sustainable goals.
- Indoor environmental quality requirements.
- Project program, including facility functions and hours of operation, and need for after hours operation.
- Equipment and systems expectations.
- Building occupant and operation and maintenance (O&M) personnel expectations.
5.410.2.2 Basis of Design (BOD). [N] A written explanation of how the design of the building systems meets the OPR shall be completed at the design phase of the building project. The Basis of Design document shall cover the following systems:
Renewable energy systems.
Landscape irrigation systems.
Water reuse systems.
5.410.2.3 Commissioning plan. [N] Prior to permit issuance a commissioning plan shall be completed to document how the project will be commissioned. The commissioning plan shall include the following:
- General project information.
- Commissioning goals.
- Systems to be commissioned. Plans to test systems and components shall include: a. An explanation of the original design intent. b. Equipment and systems to be tested, including the extent of tests.
c. Functions to be tested.
d. Conditions under which the test shall be performed. e. Measurable criteria for acceptable performance. 4. Commissioning team information. 5. Commissioning process activities, schedules and responsibilities. Plans for the completion of commissioning shall be included.
CALGreen § 504.8.3 High relevance — show source text
NONRESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST [OSHPD 1, 2 and 4] — continued
FEATURE OR MEASURE COMPLIANCE LEVELS Col3 Col4 NOTES FEATURE OR MEASURE Mandatory
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenFEATURE OR MEASURE Mandatory
CALGreenTier 1 Tier 2 Tier 2 **A6.504.8.3 Paints and coatings.**Architectural paints and coatings shall comply with Table
A6.504.8.3.
A6.504.8.3.2 Verification.
**A6.504.8.4 Carpet systems.**All carpet installed in the building interior shall meet the
testing and product requirements of one of the standards listed in Section A6.504.8.3.
**A6.504.8.4.1 Carpet cushion.**All carpet cushion installed in the building interior shall
meet the requirements of the Carpet and Rug Institute Green Label program.
**A6.504.8.4.2 Carpet adhesive.**All carpet adhesive shall meet the requirements of Table
A6.504.8.1.
**A6.504.8.5 Composite wood products.**Hardwood plywood, particleboard and medium
density fiberboard composite wood products used on the interior or exterior of the building
shall meet the requirements for formaldehyde as specified in Table A6.504.8.
**A6.504.8.5.2 Documentation.**Verification of compliance with this section shall be
provided as requested by the enforcing agency. Documentation shall include at least one
of the following.
1. Product certifications and specifications
2. Chain of custody certifications
3. Other methods acceptable to the enforcing agency
**A6.504.4.9 Acoustical ceilings and wall panels.**Comply with Chapter 8 in Title 24, Part 2
and with the VOC-emission limits defined in the CHPS Low-emitting Materials List. **A6.504.5 Hazardous particulates and chemical pollutants.**Minimize and control pollutant
entry into buildings and cross-contamination of regularly occupied areas.
**A6.504.5.1 Entryway systems.**Install permanent entryway systems measuring at least six
feet in the primary direction of travel to capture dirt and particulates at entryways directly
connected to the outdoors as listed in Items 1 through 3 in Section A6.504.5.1.
**A6.504.9 Environmental tobacco smoke (ETS) control. CALGreen § 8-10 Medium relevance — show source text
8-10 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
Title 23, Waters, California Code of Regulations
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 8-11
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-12 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
Commissioning Referenced Standards for Non-Energy Systems
The following CALGreen Referenced Standards are included herein as a convenience for the users of the California Green Building Standards Code, but they are not considered to be part of the code unless they are officially adopted by a local jurisdiction.
Contents Page Part 1: Standards for Compliance with Building Commissioning 8-14 Part 2: Commissioning Sample Forms and Templates 8-23
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 8-13
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
PART 1 STANDARDS FOR COMPLIANCE WITH BUILDING COMMISSIONING
Reference: Section 5.410.2, Commissioning.
Introduction:
The purpose of this code is to improve public health, safety and general welfare by enhancing the design and construction of buildings through the use of concepts that reduce negative and increase positive environmental impacts. Commissioning is a vital element in this effort.
Definitions used in the CALGreen Cx Reference standard:
Acronyms
BOD Basis of Design
Cx Commissioning
FPT Functional Performance Test
HVAC Heating, Ventilating and Air-Conditioning
O&M Operations and Maintenance
OPR Owner’s Project Requirements
Glossary:
Acceptance Criteria— The conditions that must be met for systems or equipment to meet defined and expected outcomes.
Commissioning (Cx)— Building commissioning as required in this code involves a quality assurance process that begins during design and continues to occupancy. Commissioning verifies that the new building operates as the owner intended and that building staff are prepared to operate and maintain its systems and equipment. Exceptions are allowed for dry storage warehouses of any size and conditioned spaces under 10,000 square feet accessory to them; and for tenant improvements under 10,000 square feet within a larger space.
Owner— The individual or entity holding title to the property on which the building is constructed.
Commissioning Coordinator— The person who coordinates the commissioning process. This can be either a third-party commissioning provider or an experienced member of the design team or owner in-house staff member.
Commissioning Team— The key members of each party involved with the project designated to provide insight and carry out tasks necessary for a successful commissioning project. Team members may include the commissioning coordinator, owner or owner’s representative, building staff, design professionals, contractors or manufacturer’s representatives and testing specialists.
CALGreen § 7.3 Medium relevance — show source text
d. Executed installation checklists
e. Executed Functional Performance Test (FPT) forms
f. Recommendations for end-of-warranty review activities
7.3 Enforcement:
At their discretion, the inspector confirms demonstrated compliance during on-site enforcement by: a) Receipt of a copy of the commissioning report, or b) Receipt of a form signed by the owner or owner’s representative attesting that the Cx Report has been completed.
8-22 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
PART 2 SAMPLE FORMS AND TEMPLATES FOR COMMISSIONING
Note: Following are examples of templates and/or forms that may be used or adopted for verification compliance with commissioning. Code users may provide their own documents as permitted by the enforcing agency. For each subsection of commissioning, samples are provided; in a few cases with narrative templates, and in most cases with compliance forms. Simplified forms or more detailed forms, but not both, may be selected to submit for each project.
CALGreen COMPLIANCE FORM
OWNER’S PROJECT REQUIREMENTS (OPR)
The following form may be required to be printed on the permit set of construction drawings or submitted separately. Italicized text indicates direct or partial quotes from the CALGreen Code.
CALGreen Commissioning Requirement 5.410.2.1, Owner’s Project Requirements (OPR)
5.410.2.1 Owner’s or Owner representative’s Project Requirements (OPR). [N] The expectations and requirements of the building appropriate to its phase shall be documented before the design phase of the project begins. This documentation shall include the following: 1. Environmental and sustainability goals. 2. Building sustainable goals. 3. Indoor environmental quality requirements. 4. Project program, including facility functions and hours of operation, and need for after hours operation. 5. Equipment and systems expectations. 6. Building occupant and operation and maintenance (O&M) personnel expectations.
Col1 OPR ELEMENTS INCLUDED 1. Environmental and sustainability goals. 2. Building sustainable goals. 3. Indoor environmental quality requirements. 4. Project program, including facility functions and hours of operation,
and need for after-hours operation. 5. Equipment and systems expectations. 6. Building occupant and O&M personnel expectations.
Owner/Owner’s Representative Signature Date
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 8-23
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
OWNER’S PROJECT REQUIREMENTS (OPR)
COMPLIANCE CHECKLIST
INCORPORATE THIS FORM IN THE PLANS
Project Address: _________________________________________________________
Permit Number: _____________________________
CALGreen § 602.1 Medium relevance — show source text
VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3
A5.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A5-3 A5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . APPENDIX A5-13 A5.3 Water Efficiency and Conservation . . . APPENDIX A5-19 A5.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-25 A5.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A5-35 A5.6 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-41 A5.601 CALGren Tier 1 and Tier 2. . . . . . . . . . APPENDIX A5-41
A5.602 CALGreen Verification Guidelines Mandatory Measures Checklist . . . . . . . . . . . . . . . APPENDIX A5-44
A5.602.1 CALGreen Verification Guidelines
Tier 1 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-48
A5.602.2 CALGreen Verification Guidelines
Tier 2 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-55
APPENDIX A6 VOLUNTARY STANDARDS FOR HEALTH
FACILITIES [OSHPD 1, 2 & 4] . . . . . . . . . . . APPENDIX A6.1-3 A6.1 Site Planning and Design . . . . . . . . . . . APPENDIX A6.1-3 A6.2 Energy Efficiency . . . . . . . . . . . . . . . . . . APPENDIX A6.1-3 A6.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . APPENDIX A6.1-32 A6.5 Environmental Quality . . . . . . . . . . . . APPENDIX A6.1-33
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INDEX-1
HISTORY NOTE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HIST-1
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE vii
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
viii 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE
CHAPTER 1 – ADMINISTRATION
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
|Adopting
CALGreen § 105.6.1 Medium relevance — show source text
[A] 105.6.1 Refusal to issue a permit. Where the application or construction documents do not conform to the requirements of pertinent laws, the code official shall reject such application in writing, stating the reasons therefor.
[A] 105.7 Validity of permit. The issuance or granting of a permit or approval of plans, specifications and computations shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinance of the jurisdiction. Permits presuming to give authority to violate or conceal the provisions of this code or other ordinances of the jurisdiction shall not be valid.
[A] 105.8 Expiration. On or after January 1, 2019, every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 12 months after its issuance or if the work authorized on the site by such permit is suspended or aban- doned for a period of 12 months after the time the work is commenced. The building official is authorized to grant, in writing, one or more extensions of time for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demon- strated. (See Health and Safety Code Section 18938.5 and 18938.6.)
[A] 105.9 Retention of permits. Permits shall at all times be kept on the premises designated therein and shall at all times be subject to inspection by the code official or other authorized representative.
[A] 105.10 Revocation of permits. Permits issued under this code can be suspended or revoked where it is determined by the code official that:
- It is used by a person other than the person to whom the permit was issued.
- It is used for a location other than that for which the permit was issued.
- Any of the conditions or limitations set forth in the permit have been violated.
- The permittee fails, refuses or neglects to comply with any order or notice duly served on him or her under the provisions of this code within the time provided therein.
- There has been any false statement or misrepresentation as to material fact in the application or plans on which the permit or application was made.
- The permit is issued in error or in violation of any other ordinance, regulations or provisions of this code.
The code official is allowed to, in writing, suspend or revoke a permit issued under the provisions of this code whenever the permit is issued in error or on the basis of incorrect information supplied, or in violation of any ordinance or regulation or any of the provisions of this code.
SECTION 106—CONSTRUCTION DOCUMENTS
[A] 106.1 General. Plans, engineering calculations, diagrams and other data shall be submitted in not fewer than two sets, or in a digital format where allowed by the code official, with each application for a permit. The construction documents shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. Where special conditions exist, the code official is authorized to require additional documents to be prepared by a registered design professional.
Exception: Submission of plans, calculations, construction inspection requirements and other data, if it is found that the nature of the work applied for is such that reviewing of plans is not necessary to obtain compliance with this code.
CALGreen § 106.9 Medium relevance — show source text
FEATURE OR MEASURE COMPLIANCE LEVELS Col3 Col4 NOTES FEATURE OR MEASURE Mandatory
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenFEATURE OR MEASURE Mandatory
CALGreenTier 1 Tier 2 Tier 2 DIVISION A6.1 – PLANNING AND DESIGN SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development **A6.106.9 Building orientation.**Locate and orient the building as follows:
1. When site and location permit, orient the building with the long sides facing north and
south.
2. Protect the building from thermal loss, drafts and degradation of the building envelope
caused by wind and wind-driven materials such as dust. DIVISION A6.2 – ENERGY EFFICIENCY SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures A6.203.1 Energy performance. [OSHPD 1]
**A6.203.1.1 CALGreen Tier 1. [OSHPD 1]**Buildings must comply with the latest edition of
“Savings By Design, Healthcare Modeling Procedures.”
A.5.203.1.2 CALGreen Tier 2. [OSHPD 1] Buildings must exceed the latest edition of “Savings
By Design, Healthcare Modeling Procedures” by 15 percent. SECTION A6.204 Prescriptive Measures **A6.204.1 ENERGY STAR equipment and appliances.**All equipment and appliances provided
by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment
or appliance. A6.204.4 Commissioning. Building commissioning for all building systems covered by T24,
Part 6, process systems and renewable energy systems shall be included in the design and
construction processes of the building project. Commissioning requirements shall include as
a minimum items listed in Section A6.204.4.
**A6.204.4.1 Owner’s Project Requirements (OPR).**Documented before the design phase of
the project begins the OPR shall include items listed in Section A6.204.4.
**A6.204.4.2 Basis of Design (BOD).**A written explanation of how the design of the building
systems meets the OPR shall be completed at the design phase of the building project and
updated periodically to cover the systems listed in Section A6.204.4.2.
**A6.204.4.3 Commissioning plan.CALGreen § 8-29 Medium relevance — show source text
shown in the specifications and cross referenced| |2|List of commissioned equipment and systems| |3|Cx roles and responsibilities of all parties| |4|Meeting requirements| |5|Commissioning schedule management procedures| |6|Procedures for addressing outstanding issues or noncompliance| |7|Requirements for execution and documentation of installation and equipment start-up| |8|Specific testing requirements for each system type| |9|Submittal review and approval requirements| |10|Contents and approval process of the commissioning plan| |11|Cx documentation and reporting requirements| |12|Facility staff training requirements and verification procedures| |13|O&M manual review and approval procedures| |14|Systems manual development and approval procedures| |15|Definitions|
Commissioning Agent Acknowledgment
I have reviewed the construction documents listed above and verified their compliance with the Owner’s Project Requirements (OPR), Basis of Design (BOD) and commissioning plan.
Name: _______________________________________
Company Name (if applicable): _____________________________________________
Agent’s Signature: __________________________________ Date: ______________
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 8-29
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
COMMISSIONING PLAN
COMPLIANCE FORM
The following form may be required to be printed on the permit set of construction drawings or submitted separately.
CALGreen Commissioning Requirement 5.410.2.3, Commissioning Plan
5.410.2.3 Commissioning plan. [N] Prior to permit issuance a commissioning plan shall be completed to document how the project will be commissioned. The commissioning plan shall include the following:
(See Cx plan elements checklist below.)
The commissioning plan should be started during the design phase of the building project. Include the checked elements listed below and approved by the owner or owner’s representative.
Col1 COMMISSIONING PLAN ELEMENTS1 INCLUDED 1. General project information 2. Commissioning goals 3. Systems to be commissioned—see BOD 3a. An explanation of original design intent 3b. Equipment and systems to be commissioned and tested, including extent of tests 3c. Functions to be tested and conditions of tests1 3d. Conditions under which the test shall be performed 3e. Measurable criteria for acceptable performance 4. Cx team information 5. Cx process activities, schedules and responsibilities - These are not the detailed step-by-step test procedures but are lists of features, elements, modes and conditions of tests for specific equipment.
Owner / Owner’s Representative Signature Date
8-30 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
COMMISSIONING PLAN
COMPLIANCE CHECKLIST
INCORPORATE THIS FORM IN THE PLANS
Project Address: ________________________________________________________
Permit Number: _____________________________
ITEM # COMMISSIONING PLAN ITEMS1 PAGE NUMBER IN
COMMISSIONING
PLAN DOCUMENTGENERAL PROJECT INFORMATION 1 Project name, owner, CALGreen § 602.2 Medium relevance — show source text
Documentation Author's / Responsible Designer's Declaration Statement
Check the appropriate box(es) for the list below.
□ Mandatory: I attest that the mandatory provisions checklist is accurate and complete.
□ Tier 1 compliant: I attest that the total number of voluntary measures selected meet or exceed the total number required
to achieve Tier 1 compliance.
□ Partial Tier 1 compliant: I attest that the total number of voluntary measures selected do not meet the total number
required to achieve Tier 1 compliance: however, partial Tier 1 compliance has been achieved.Col2 Signature: Company: Date: Address: License: City/State/Zip: Phone: APPENDIX A5-54 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A5 — NONRESIDENTIAL VOLUNTARY MEASURES
A5.602.2
CALGreen VERIFICATION GUIDELINES
TIER 2 CHECKLIST
Application: This checklist shall be used for nonresidential projects that meet the following: new construction, or building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3, AND are adopting Tier 2 voluntary measures.
Note: All applicable mandatory requirements in Chapter 5 shall be met prior to applying Tier 2 voluntary measures.
Instructions:
Comply with all Tier 2 prerequisite measures from the various categories shown on the table below.
Add a “ Y ” to all mandatory and Tier 2 prerequisite measures in the appropriate columns.
Select the required number of additional electives from those categories shown on the table below and add a “ Y ” on the selected elective and add an “ N ” on the rest.
Count the total number of Tier 2 prerequisite measures plus the additional electives and write down the total number at the end of the checklist. Determine if the required number of Tier 2 measures have been selected to achieve Tier 2 compliance.
Y = Yes (section has been selected and/or included) N = No (section has not been selected and/or included) O = Other (provide explanation)
[N] = New construction pursuant to Section 301.3
[A] = Additions and/or Alterations pursuant to Section 301.3
CHAPTER 5
DIVISIONSCol2 SECTION TITLE CODE
SECTIONY N O PLAN SHEET,
SPEC OR
ATTACHDIVISION 5.1
Planning and
Design
(continued)Mandatory Deconstruction and reuse of existing structures,
Scope with Exception5.105.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Reuse of existing building & Verification of compliance with
note5.105.2 and 5.105.2.1 DIVISION 5.1
Planning and
Design
(continued)Mandatory Storm water pollution prevention for projects that disturb
less than 1 acre of land5.106.1 through
5.106.
Frequently asked questions
What construction documents are required for CALGreen compliance?
Construction documents must be submitted with the permit application and be clear enough to show the location, nature and scope of green features and demonstrate conformance with CALGreen; the enforcing agency may require additional documents prepared by a licensed design professional when necessary (§102.1–§102.2) .
How do I show verification of green measures?
Documentation of conformance for applicable green measures must be provided to the enforcing agency; CALGreen accepts alternate documentation if the enforcing agency finds it demonstrates substantial conformance. Residential projects must also submit the Residential Occupancies Application Checklist with references to the measure‑specific documentation used to show compliance (§102.3) .
What commissioning documents should be included in the construction documents?
Commissioning measures (including the OPR, Basis of Design, and a project‑specific Commissioning Plan) must be shown in the construction documents; the Code requires functional performance testing, a commissioning report and O&M/manual deliverables as part of verification and final acceptance (§5.410.2 and §5.410.2.3) .
More in California Green Building Standards Code (CALGreen)
- Administration (Chapter 1)
- Nonresidential Voluntary Measures (Appendix A5 — divisions A5.1–A5.6, electives & verification)
- Residential Mandatory Measures — Planning & Design; Energy; Water; Materials; Environmental Quality (Chapter 4)
- Definitions (Chapter 2)
- Voluntary Standards for Health Facilities (Appendix A6 / OSHPD guidance)
- Green Building – scope, mixed occupancies, phased projects (Chapter 3)
- Residential Voluntary Measures (Appendix A4 — divisions A4.1–A4.6, tiers & model ordinance)
- Nonresidential Mandatory Measures — Planning & Design; Energy; Water; Materials; Environmental Quality (Chapter 5)
- Compliance verification, construction documents & checklists (Section 102, Chapter 7, Appendix checklists)
- Referenced Organizations and Standards (Chapter 6)
- Voluntary Tiers and CALGreen Tier 1 / Tier 2 (performance tiers, thresholds)
- Installer and Special Inspector Qualifications (Chapter 7)