509.4 Type of Venting System to be Used.
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
The type of venting system to be used shall be in accordance with Table 509.4. [NFPA 54:12.5.1]
509.4.1 Plastic Piping. Where plastic piping is used to vent an appliance, the appliance shall be listed for use with such venting materials and the appliance manufac
turer’s installation instructions shall identify the specific plastic piping material. The plastic pipe venting materials shall be labeled in accordance with the product standards specified by the appliance manufacturer or shall be listed and labeled in accordance with UL 1738. [NFPA 54:12.5.2]
TABLE 509.4
TYPE OF VENTING SYSTEM TO BE USED {NFPA 54: TABLE 12.5.1}
| APPLIANCES | TYPE OF VENTING SYSTEM |
LOCATION OF REQUIREMENTS |
|---|---|---|
Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Type B gas vent | Section 509.6 |
Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Chimney | Section 509.5 |
Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Single-wall metal pipe |
Section 509.7 |
Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Listed chimney lin- ing system for gas venting |
Section 509.5.3 |
Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Special gas vent listed for these appliances |
Section 509.4.3 |
Listed vented wall fur- naces |
Type B-W gas vent | Section 509.6 |
Category II, Category III, and Category IV appliances |
As specified or furnished by manufacturers of listed appliances |
Section 509.4.1 and Section 509.4.3 |
Appliances that can be converted to use solid fuel Unlisted combination gas- and oil-burning appliances Combination gas- and solid fuel-burning appliances Appliances listed for use with chimneys only Unlisted appliances |
Chimney | Section 509.5 |
Listed combination gas- and oil-burning appliances |
Type L vent | Section 509.6 |
Listed combination gas- and oil-burning appliances |
Chimney | Section 509.5 |
Decorative appliance in vented fireplace |
Chimney | UMC Section 911.2 |
Gas-fired toilets |
Single-wall metal pipe |
Section 509.7 |
Direct-vent appliances |
— | Section 509.2.6 |
Appliances with integral vents |
— | Section 509.2.7 |
509.4.2 Plastic Vent Joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s installation instructions. Plastic pipe venting materials listed and labeled in accordance with UL 1738 shall be installed in accor dance with the vent manufacturer’s installation instruc
TABLE 509.4
TYPE OF VENTING SYSTEM TO BE USED {NFPA 54: TABLE 12.5.1}
92 2025 CALIFORNIA PLUMBING CODE
WATER HEATERS
tions. Where primer is required, it shall be of a contrasting color. [NFPA 54:12.5.3] 509.4.3 Special Gas Vents. Special gas vents shall be listed and labeled in accordance with UL 1738 and installed in accordance with the special gas vent manufacturer’s installation instructions. [NFPA 54:12.5.4]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
▸Chapter 5 — WATER HEATERS
Overview- 501.1 Applicability.
- 501.2 California Energy Code Water Heating System
- 502.1 General.
- 503.1 Inspection of Chimneys or Vents.
- 503.2 Final Water Heater Inspection.
- 504.1 Location.
- 504.2 Vent.
- 504.3 Clearance.
- 504.4 Pressure-Limiting Devices.
- 504.5 Temperature Limiting Devices.
- 504.6 Temperature, Pressure, and Vacuum Relief Devices.
- 504.7 Lead Content.
- 505.1 Water Heaters.
- 505.2 Safety Devices.
- 505.3 Oil-Fired Water Heaters.
- 505.4 Indirect-Fired Water Heaters.
- 506.1 General.
- 506.2 Indoor Combustion Air.
- 506.3 Indoor Opening Size and Location.
- 506.4 Outdoor Combustion Air.
- 506.5 Combination Indoor and Outdoor Combustion Air.
- 506.6 Engineered Installations.
- 506.7 Mechanical Combustion Air Supply.
- 506.8 Louvers, Grilles, and Screens.
- 506.9 Combustion Air Ducts.
- 507.1 Dielectric Insulator.
- 507.2 Seismic Provisions.
- 507.3 Appliance Support.
- 507.4 Ground Support.
- 507.5 Drainage Pan.
- 507.6 Added or Converted Equipment or Appliances.
- 507.7 Type of Gas(es).
- 507.8 Safety Shutoff Devices for Unlisted LP-Gas Appliance Use…
- 507.9 Use of Air or Oxygen Under Pressure.
- 507.10 Protection of Gas Appliances from Fumes or Gases other …
- 507.11 Process Air.
- 507.12 Flammable Vapors.
- 507.13 Installation in Residential Garages.
- 507.14 Installation in Commercial Garages.
- 507.15 Installation in Aircraft Hangars.
- 507.16 Venting of Flue Gases.
- 507.17 Extra Device or Attachment.
- 507.18 Addition to Existing System.
- 507.19 Avoiding Strain on Gas Piping.
- 507.20 Gas Appliance Pressure Regulators.
- 507.21 Bleed Lines for Diaphragm-Type Valves.
- 508.2 Installation of Appliances on Roofs.
- 508.3 Appliances on Roofs.
- 507.22 Combination of Appliances and Equipment.
- 507.23 Installation Instructions.
- 507.24 Protection of Outdoor Appliances.
- 507.25 Accessibility for Service.
- 507.26 Clearance to Combustible Materials.
- 508.1 General.
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.1 Listing.
- 509.2 Connection to Venting Systems.
- 509.3 Minimum Safe Performance.
- 509.4 Type of Venting System to be Used.
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents.
- 509.7 Single-Wall Metal Pipe.
- 509.9 Condensation Drain.
- 509.10 Vent Connectors for Category I Appliances.
- 509.8 Through-the-Wall Vent Termination.
- 509.13 Manually Operated Dampers.
- 509.14 Automatically Operated Vent Dampers.
- 509.15 Obstructions.
- 510.1 Additional Requirements to Single Appliance Vent.
- 509.11 Vent Connectors for Category II, Category III, and Cate…
- 509.12 Appliances Requiring Draft Hoods.
- 510.2 Additional Requirements to Multiple-Appliance Vent.
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS