506.2 Indoor Combustion Air.
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
The required volume of indoor air shall be determined in accordance with the method in Section 506.2.1 or Section 506.2.2 except that where the air infiltration rate is known to be less than 0.40 ACH (air change per hour), the method in Section 506.2.2 shall be used. The total required volume shall be the sum of the required volume calculated for all appliances located within the space. Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors, and through combustion air openings sized and located in accordance with Section 506.3, are considered a part of the required volume. [NFPA 54:9.3.2] 506.2.1 Standard Method. The minimum required volume shall be 50 cubic feet per 1000 British thermal units per hour (Btu/h) (4.83 m [3] /kW). [NFPA 54:9.3.2.1]
506.2.2 Known Air Infiltration Rate Method. Where the air infiltration rate of a structure is known, the minimum required volume shall be determined as follows [NFPA 54:9.3.2.2]:
(1) For appliances other than fan-assisted, calculate using the following Equation 506.2.2(1). [NFPA 54:9.3.2.2(1)]
[Equation 506.2.2(1)]
I other
Required Volume other ≥ [21 ft] ACH [3] 1000 Btu/h
( )
(2) For fan-assisted appliances, calculate using the following Equation 506.2.2(2). [NFPA 54:9.3.2.2(2)]
[Equation 506.2.2(2)]
15 ft [3] I
fan
Required Volume fan ≥ ACH 1000 Btu/h
( )
Where:
Iother = All appliances other than fan-assisted input in (Btu/h) Ifan = Fan-assisted appliance input in (Btu/h) ACH = Air change per hour (percent of volume of space exchanged per hour, expressed as a decimal)
Required Volume other ≥ [21 ft] [3]
ACH
(
I other
[21 ft] [3]
ACH 1000 Btu/h
( )
15 ft [3] Required Volume fan ≥ ACH
(
15 ft [3] I
fan ACH 1000 Btu/h FIGURE 506.3
( )
ALL COMBUSTION AIR FROM ADJACENT INDOOR SPACES
THROUGH INDOOR COMBUSTION AIR OPENINGS
[NFPA 54: FIGURE A.9.3.2.3(1)]
For SI units: 1 cubic foot = 0.0283 m [3], 1000 British thermal units
per hour = 0.293 kW
(3) For purposes of these calculations, an infiltration rate greater than 0.60 ACH shall not be used in Equation 506.2.2(1) and Equation 506.2.2(2).
[NFPA 54:9.3.2.2(3)]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
▸Chapter 5 — WATER HEATERS
Overview- 501.1 Applicability.
- 501.2 California Energy Code Water Heating System
- 502.1 General.
- 503.1 Inspection of Chimneys or Vents.
- 503.2 Final Water Heater Inspection.
- 504.1 Location.
- 504.2 Vent.
- 504.3 Clearance.
- 504.4 Pressure-Limiting Devices.
- 504.5 Temperature Limiting Devices.
- 504.6 Temperature, Pressure, and Vacuum Relief Devices.
- 504.7 Lead Content.
- 505.1 Water Heaters.
- 505.2 Safety Devices.
- 505.3 Oil-Fired Water Heaters.
- 505.4 Indirect-Fired Water Heaters.
- 506.1 General.
- 506.2 Indoor Combustion Air.
- 506.3 Indoor Opening Size and Location.
- 506.4 Outdoor Combustion Air.
- 506.5 Combination Indoor and Outdoor Combustion Air.
- 506.6 Engineered Installations.
- 506.7 Mechanical Combustion Air Supply.
- 506.8 Louvers, Grilles, and Screens.
- 506.9 Combustion Air Ducts.
- 507.1 Dielectric Insulator.
- 507.2 Seismic Provisions.
- 507.3 Appliance Support.
- 507.4 Ground Support.
- 507.5 Drainage Pan.
- 507.6 Added or Converted Equipment or Appliances.
- 507.7 Type of Gas(es).
- 507.8 Safety Shutoff Devices for Unlisted LP-Gas Appliance Use…
- 507.9 Use of Air or Oxygen Under Pressure.
- 507.10 Protection of Gas Appliances from Fumes or Gases other …
- 507.11 Process Air.
- 507.12 Flammable Vapors.
- 507.13 Installation in Residential Garages.
- 507.14 Installation in Commercial Garages.
- 507.15 Installation in Aircraft Hangars.
- 507.16 Venting of Flue Gases.
- 507.17 Extra Device or Attachment.
- 507.18 Addition to Existing System.
- 507.19 Avoiding Strain on Gas Piping.
- 507.20 Gas Appliance Pressure Regulators.
- 507.21 Bleed Lines for Diaphragm-Type Valves.
- 508.2 Installation of Appliances on Roofs.
- 508.3 Appliances on Roofs.
- 507.22 Combination of Appliances and Equipment.
- 507.23 Installation Instructions.
- 507.24 Protection of Outdoor Appliances.
- 507.25 Accessibility for Service.
- 507.26 Clearance to Combustible Materials.
- 508.1 General.
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.1 Listing.
- 509.2 Connection to Venting Systems.
- 509.3 Minimum Safe Performance.
- 509.4 Type of Venting System to be Used.
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents.
- 509.7 Single-Wall Metal Pipe.
- 509.9 Condensation Drain.
- 509.10 Vent Connectors for Category I Appliances.
- 509.8 Through-the-Wall Vent Termination.
- 509.13 Manually Operated Dampers.
- 509.14 Automatically Operated Vent Dampers.
- 509.15 Obstructions.
- 510.1 Additional Requirements to Single Appliance Vent.
- 509.11 Vent Connectors for Category II, Category III, and Cate…
- 509.12 Appliances Requiring Draft Hoods.
- 510.2 Additional Requirements to Multiple-Appliance Vent.
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS