506.8 Louvers, Grilles, and Screens.
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
The required size of openings for combustion, ventilation, and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver, grille, or screen is known, it shall be used in calculating the size opening required to provide the free area specified. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers have 25 percent free area, and metal louvers and grilles have 75 percent free area. Nonmotorized louvers and grilles shall be fixed in the open position. [NFPA 54:9.3.7.1]
506.8.1 Minimum Screen Mesh Size. Screens shall not be smaller than [1] ⁄ 4 of an inch (6.4 mm) mesh. [NFPA 54:9.3.7.2]
506.8.2 Motorized Louvers. Motorized louvers shall be interlocked with the appliance so they are proven in the full open position prior to main burner ignition and during main burner operation. Means shall be provided to prevent the main burner from igniting should the louver fail to open during burner startup and to shut down the main burner if the louvers close during burner operation.
[NFPA 54:9.3.7.3]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
▸Chapter 5 — WATER HEATERS
Overview- 501.1 Applicability.
- 501.2 California Energy Code Water Heating System
- 502.1 General.
- 503.1 Inspection of Chimneys or Vents.
- 503.2 Final Water Heater Inspection.
- 504.1 Location.
- 504.2 Vent.
- 504.3 Clearance.
- 504.4 Pressure-Limiting Devices.
- 504.5 Temperature Limiting Devices.
- 504.6 Temperature, Pressure, and Vacuum Relief Devices.
- 504.7 Lead Content.
- 505.1 Water Heaters.
- 505.2 Safety Devices.
- 505.3 Oil-Fired Water Heaters.
- 505.4 Indirect-Fired Water Heaters.
- 506.1 General.
- 506.2 Indoor Combustion Air.
- 506.3 Indoor Opening Size and Location.
- 506.4 Outdoor Combustion Air.
- 506.5 Combination Indoor and Outdoor Combustion Air.
- 506.6 Engineered Installations.
- 506.7 Mechanical Combustion Air Supply.
- 506.8 Louvers, Grilles, and Screens.
- 506.9 Combustion Air Ducts.
- 507.1 Dielectric Insulator.
- 507.2 Seismic Provisions.
- 507.3 Appliance Support.
- 507.4 Ground Support.
- 507.5 Drainage Pan.
- 507.6 Added or Converted Equipment or Appliances.
- 507.7 Type of Gas(es).
- 507.8 Safety Shutoff Devices for Unlisted LP-Gas Appliance Use…
- 507.9 Use of Air or Oxygen Under Pressure.
- 507.10 Protection of Gas Appliances from Fumes or Gases other …
- 507.11 Process Air.
- 507.12 Flammable Vapors.
- 507.13 Installation in Residential Garages.
- 507.14 Installation in Commercial Garages.
- 507.15 Installation in Aircraft Hangars.
- 507.16 Venting of Flue Gases.
- 507.17 Extra Device or Attachment.
- 507.18 Addition to Existing System.
- 507.19 Avoiding Strain on Gas Piping.
- 507.20 Gas Appliance Pressure Regulators.
- 507.21 Bleed Lines for Diaphragm-Type Valves.
- 508.2 Installation of Appliances on Roofs.
- 508.3 Appliances on Roofs.
- 507.22 Combination of Appliances and Equipment.
- 507.23 Installation Instructions.
- 507.24 Protection of Outdoor Appliances.
- 507.25 Accessibility for Service.
- 507.26 Clearance to Combustible Materials.
- 508.1 General.
- 508.4 Appliances in Attics and Under-Floor Spaces.
- 509.1 Listing.
- 509.2 Connection to Venting Systems.
- 509.3 Minimum Safe Performance.
- 509.4 Type of Venting System to be Used.
- 509.5 Masonry, Metal, and Factory-Built Chimneys.
- 509.6 Gas Vents.
- 509.7 Single-Wall Metal Pipe.
- 509.9 Condensation Drain.
- 509.10 Vent Connectors for Category I Appliances.
- 509.8 Through-the-Wall Vent Termination.
- 509.13 Manually Operated Dampers.
- 509.14 Automatically Operated Vent Dampers.
- 509.15 Obstructions.
- 510.1 Additional Requirements to Single Appliance Vent.
- 509.11 Vent Connectors for Category II, Category III, and Cate…
- 509.12 Appliances Requiring Draft Hoods.
- 510.2 Additional Requirements to Multiple-Appliance Vent.
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS