Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
422.4 Toilet Facilities Serving Employees and Cus-tomers — 2025 California Plumbing Code
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 422.4 · Effective January 1, 2026 · Official source: Building Standards Commission
tomers. [Not adopted for OSHPD 1, 2, 3, 4 & 5] Each building or structure shall be provided with toilet facilities for employees and customers. Requirements for customers and employees shall be permitted to be met with a single set of restrooms accessible to both groups. Required toilet facilities for employees and customers located in shopping malls or centers shall be permitted to be met by providing a centrally located toilet facility accessible to several stores. The maximum travel distance from entry to any store to the toilet facility shall not exceed 300 feet (91 440 mm). Required toilet facilities for employees and customers in other than shopping malls or centers shall have a maximum travel distance not to exceed 500 feet (152 m).
»
pancy classification shall be determined in accordance with the California Building Code . Occupancy classification not shown in Table 422.1 shall be considered separately by the Authority Having Jurisdiction.
[OSHPD 1, 2, 3, 4 & 5] Plumbing fixtures shall be provided in the minimum number shown in Table 4-2.
Exception: [BSC & DSA-SS] Using occupancy classifica- tion, described as function of space, determine occupant load factor from Table 4-1 Occupant Load Factor, of this chapter.
422.1.1 Fixture Calculations. The minimum number of fixtures shall be calculated at 50 percent male and 50 percent female based on the total occupant load. Where information submitted indicates a difference in the distribution
of the sexes such information shall be used to determine the number of fixtures for each sex. Once the occupancy load and occupancy are determined, Table 422.1 shall be applied to determine the minimum number of plumbing fixtures required. Where applying the fixture ratios in Table 422.1 results in fractional numbers, such numbers shall be rounded to the next whole number. For multiple occupancies, fractional numbers shall be first summed and then rounded to the next whole number. For toilet facilities designed for use by all genders, the minimum number of fixtures shall be the aggregate calculated at 50 percent female and 50 percent male in accordance with Table 422.1. Where all-gender fixtures are provided in addition to separate men’s and women’s facilities, those fixtures shall be included in determining the number of fixtures provided in an occupancy. [BSC & DSA-SS] The substitution of a water closet for each urinal shall be permitted provided the total number of fixtures installed complies with Table 422.1. 422.1.2 Single Use, Family or Assisted-Use Toilet, and Bathing Facilities. Where single use, family or assisted-use toilet, and bathing rooms are required, in applicable building regulations, the facilities shall be installed in accordance with those regulations. Fixtures located in single use, family or assisted-use, and bathing room facilities shall contribute to the total number of required fixtures in accordance with Section 422.1.
422.1.3 [DSA-AC] Effective January 1, 1990, in new construction and those existing facilities which occu- pancy type are listed in Tables 422.1 and 4-4 for public use, which apply for permit to undertake construction, structural alterations, repairs or improvement which exceed 50 percent of the square footage of the entire facility, shall install water closets, urinals, lavatories and drinking fountains as stipulated in Tables 422.1 and 4-4 for public use. Community and/or municipal parks with a bleacher capacity not exceeding 500 seats shall be exempt from the requirements of this section and Tables 422.1 and 4-4. Each bathroom shall comply with Part 2, Chapter 11A and 11B of the California Building Code.
422.1.4 [OSHPD 1, 2, 3, 4 & 5] OSHPD facilities shall also comply with requirements of the California Building Code, Sections 1224, 1225, 1226, 1227 and 1228.